| 1 | DSR item No.26.2 Online UPS- Input supply: Three Phase, Output supply: Three PhaseSupplying, installation, Testing & Commissioning of following capacity at full load (Unity Power Factor) at operating temperature 0 to 40 deg C, Relative humidity 0 to 95%, Online double conversion true sine wave Uninterrupted hot swapable (allow for the replacement or addition of battery modules without shutting down the entire system) modular Power Supply (UPS) system with N+1 modules (N denotes total number of modulesrequired for rated capacity). (Please refer DNIT for complete specification of item no.1) |
| 2 | 200KVA (Each Power module shall be ≤ 50 KVA) |
| 3 | DSR item No.4.1 Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastener etc. as required. |
| 4 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 5 | 375 mm width X 50 mm depth X 2.0 mm thickness |
| 6 | DSR item No.2.5 Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 7 | 4 way (4 + 12), Double door |
| 8 | 12 way (4 + 36), Double door |
| 9 | DSR item No.2.10 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 10 | Single pole |
| 11 | DSR item No.11.1 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 12 | 4 X 16 sq. mm (28mm) |
| 13 | 3½ X 35 sq. mm (32mm) |
| 14 | 3½ X 300 sq. mm (70mm) |
| 15 | DSR item No.15.16 Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 16 | 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 17 | DSR item No.5.4 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 18 | DSR item No.5.6 Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 19 | DSR item No.5.14 Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 20 | DSR item No.5.15 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 21 | UPS PANELSupplying, Installation, Testing & Commissioning of Modular, Sectionalized (Form-4B Construction) Low Voltage Panel suitable for 415 V, 3 Phase, 4 wire 50 Hz AC supply system as per standard IEC 61439 Part-1 & Part-2 as Totally Type Tested Assembly and of suitable size fabricated in compartmentalized design from CRCA sheet steel of 2mm thick for frame work and covers & doors of 1.6mm thick sheet, 3 mm thick for gland plates (Please refer DNIT for complete specification of item no.11) |
| 22 | Providing and fixing following rating MCCB 4 pole 415 Volt (Thermal magnetic / microprocessor release) for adjustable Over load and adjustable short circuit protection, 36 KA Breaking capacity (Ics=100% of Icu) with positive isolation. The overload & short circuit release shall be of adjustable type, suitable for isolation The MCCB is to be installed in existing cubicle panel / angle iron board/ VTPN BDB / MCCB enclosure including drilling holes in cubicle panel / angle iron board, making connections with suitable rating of copper wire / copper strip etc. as required. The job includes the cost of spreaders terminal links. The job also includes cost of MS enclosure or direct/ extended rotary handle etc. as required to complete the job to the entire satisfaction of Engineer-in-charge. The MCCB should be of Lauritz Knudsen/ Siemens/ Schneider/ Legrand/ ABB/Hager make only. |
| 23 | 125 Amp 4 Pole MCCB (Thermal Magnetic release). |
| 24 | 100 Amp 4 Pole MCCB (Thermal Magnetic release). |
| 25 | Supply and laying of XLPE insulated PVC sheathed Aluminum conductor armoured cable of 1.1 KV grade as per IS 7098 (Part-I) 1988 (amended up to date) of the following sizes to be laid in existing Trench/Ducts/Cable Tray/ RCC/ HUME/ METAL/ DWC pipe / on surface with the help of MS clamps of suitable size asrequired at site to the entire satisfaction of Engineer-in-Charge. The job includes labour charges of laying the cable and making connections with suitable size aluminum lugs/thimbles etc. The cable shall be of Polycab / Havells / R.R. Kabel/ KEI/ Finolex make only. |
| 26 | Size 16 sq.mm 4 core (On Cable Tray/ In open Duct) |
| 27 | Size 35 sq.mm 3.5 core (On Cable Tray/ In open Duct) |
| 28 | Size 300 sq.mm 3.5 core (On Cable Tray/ In open Duct) |
| 29 | Size 300 sq.mm 3.5 core (In Pipe) |
| 30 | Supply and laying of single core 185 sq. mm copper conductor FRLS cable to be laid in existing pipe/ on surface. The job includes labour charges for laying of cable and making connections with suitable size copper lugs/thimbles etc. to complete the job to the entire satisfaction of Engineer-in-charge. The cable shall be of Polycab / Havells / R.R. Kabel/ KEI/ Finolex make only. Please Enable Macros to View BoQ information |