| 1 | Following works are to be carried out at 132 KV S/S Sahara City Homws , Lucknow for the construction of new 33 KV SAHARA PRIME CITY Bay\\" along with associated works including all cost of men, misc, consumables, T&P, Crane etc. to complete the Job satisfactorily |
| 2 | PART- A : - WORK |
| 3 | Earth Mat work |
| 4 | Laying of 40mm dia MS round bar 700 mm below the ground level by the cutting straightening welding painting excavation of trench back filling of trench after laying of earth mat including shifting of M S round bar from store place at the Sub-Station to switchyard. |
| 5 | Fabrication of 3 Meter long electrodes with 40 mm dia MS round bar having 150 mm long conical shape by digging cutting, straightening etc. and then placing it vertical inside the ground with Top 700mm below the ground level including shifting of MS round bar from storage place at the Sub-Station to switchyard. |
| 6 | Making a cross joint of above laid 40 mm dia MS round bar 700 mm below the ground level by due welding at all 4 corners including welding of suitable size 2 No MS angle pieces on opposite corners of the cross joint. |
| 7 | Making of end joint of above laid 40 mm dia MS round bar with Top of the already vertically pierced MS electrodes 700mm below the ground level by due welding. |
| 8 | Making of 300mm long lap joint of above already laid round bar to connecting existing earth mat of the Sub-Station. |
| 9 | carriage work |
| 10 | Proper shifting, Sorting,counting, weighting and stacking of Galvanized sub station structure on private vehicle from storage place to loading site from any of sub station within ETC-I Lucknow. |
| 11 | Safe carriage of sub station structure from from any of sub station within ETC-I Lucknow to 132KV S/S Sahara city Homes Lucknow including vehicle fare/ Toll Taxes etc if any |
| 12 | Un loading of structure at 132Kv Sahara city Homes & its proper shifting, counting as per instruction of supervisioning Engineer. |
| 13 | Safe carriage of the following equipments including loading and unloading on trucks duty arranged by the Contractor from Stores of different sub-station of Lucknow to 132 KV Sub-Station Sahara City Homes, Lucknow. |
| 14 | Carriage of 33 KV Tripple Feeder C&R Panel |
| 15 | Carriage of 33 KV CT/PT/Isolator |
| 16 | Carriage of 33 KV VCB |
| 17 | Carriage of various size Control Cable (2KM) |
| 18 | Safe Loading of 1 No. Drums of ACSR Moose Conductor on Suitable Vechicle after due Shifting from storage Place to Loading Place at 132 KV Substation Khurram Nagar. |
| 19 | Safe Carriage of above ACSR Moose Conductor in Drum Loaded on the vechicle arranged by contractor from 132 KV S/S Khurramnagar/ Chinhat to safe unloading place at Existing 132 KV S/S Sahara City Homes. |
| 20 | Safe Unloading of above ACSR Moose Conductor in Drum from the Vechicle and Shifting of same to Safe Storage Place at 132 KV Sahara City Homes |
| 21 | Erection of Lattice type main and auxiliary structures with other associated works to complete the job as per required as per technical specification of UPPTCL CCM-04 No,CGM-02No.,CPM-4No.,YMM-4 No., ALP-3 No., ABL-3 No. |
| 22 | Laying and stringing of 33 K.V. Main Bus Bar of Twin ACSR Moose Conductor(R,Y,B) including hoisting of disc insulator tension string with associated tension fitting and disc insulator suspension string with associated suspension fitting from gantry along with shifting of the new conductors, tension fittings, suspension fittings etc. from stores at the Sub Station to the switchyard. (01 Job for each phase of each section of the Main Bus Bar ) |
| 23 | Laying and stringing of 33 KV Jack Bus Bar panther conductor(R,Y,B) including hoisting of disc insulator tension string with associated tension fitting and disc insulator suspension string with associated suspension fitting from gantry along with shifting of the new conductors, tension fittings/ suspension fittings etc. from stores at the Sub Station to the switchyard. (01 Job for each phase of each section of the Jack Bus) |
| 24 | Erection of following Equipments as per instruction manual and technical specifications including shifting of materials from Central Stores/ Site Store to Erection Site including all associated works. |
| 25 | 33 KV VCB with structure |
| 26 | 33 KV CT (400-200/1/1/1) |
| 27 | 33 KV CT Junction Box. |
| 28 | 33 KV PТ |
| 29 | 33 KV PT Junction Box. |
| 30 | 33 KV BI without earth blade |
| 31 | 33 KV LI with earth blade |
| 32 | 33 KV Post Insulator |
| 33 | Jumpering with Twin ACSR Moose / Panther Conductors from newly laid 33 K.V. Main Bus Bar / Jack Bus Bar Conductors to Main Bus/Jack Bus Isolators of 33 K.V. Feeders / by due cutting & bending of conductors and tightening of jumpers with P.G. Clamps, connectors along with shifting of the conductors, PG Clamps, connectors from stores at the Sub Station to the switchyard. |
| 34 | Fixing of 250/100 mm size Spacers (Bolted type) for ACSR Moose to Moose panther to panther between above laid 33 K.V. Main Bus Bar Conductors of Twin ACSR Moose& Twin moose jumpers of T/F. (01 Job for each spacer) |
| 35 | Cutting, Straightening and Laying 700 mm below inside ground & above ground of 40 mm dia size M.S. Flats (to be provided by the department) as per requirement for Earthing of newly erected equipments and Structures as above including welding with main Earthmat and with the object to be earthed including excavation, backfilling, painting of the Earthmat above ground level in Bus Green colour including all other associated works to complete the job satisfactorily as per Technical Specifications. |
| 36 | Earthing of Aux. Structures and Equipments with 50X6 mm size M.S. Flat |
| 37 | Earthing of cable trenches with 25X6 mm size M.S. Flat |
| 38 | Earthing of control panels and cable trenches at 2 points |
| 39 | Painting of Earthing strips above ground level with one coat of Red oxide and two coat of synthetic/ enamel paint and with bus green paint below ground level as per details below: |
| 40 | 50x6 mm (in green color) |
| 41 | 25x6 mm (in green color) |
| 42 | Laying of following sizes Control Cables in the Cable Trenches from Control and Relay Panels in Control Room to various Equipments, Junction Box etc. in Switchyard as per cable schedule, its sddling with 25X3 mm size including carriage of Cable Drums from Stores to work site & shifting back to stores including all other associated works required for the satisfactorily completion of the Job as per technical specification. |
| 43 | Laying of 2CX2.5 sq. mm size Control Cable |
| 44 | Laying of 4CX2.5 sq. mm size Control Cable |
| 45 | Laying of 6CX2.5 sq. mm size Control Cable |
| 46 | Interconnection & termination of the above laid control cables between Control and Relay Panels & erected equipments i.e. CB, СТ, СТ Junction Box, PT, PT Junction, box. Including making necessary holes in Gland Plates or Boxes whereever required along with supply of Cable glands of appropriate size and providing of Ferrules for each core of the cables & its termination with crimping type Copper Lugs alongwith preparation of interconnection Drawing and Commissioning of the Panel/ Feeders in co-ordination with T&C Wing including providing 02 sets of Hard Copies of as executed Interconnection Drawing including all other associated works required for the satisfactorily completion of the Job as per technical specification. (01 Job for Each Bay) |
| 47 | Pilfer proof Metering |
| 48 | Pilfer proofing of the cable with GI Pipe of size 2 inch complete with cutting, bending, making thread etc including elbow and other required material from 33KV switchyard to control room including all other works which are required for completion of work. (Control Cable provided by deptt.) |
| 49 | Erection of SAMAST Energy Meter and Data Communication work |
| 50 | Installation of 3P4W, 0.2s accuracy class Interface Energy Meters (one Main and check Meter) |
| 51 | Necessary interconnection from data transmission of already Installed SAMAST compliant meters to Lan switch upto DCU/Gateway and all other H/W, S/W per No. |
| 52 | Installation of communication cable (CAT-6 alongwith necessary hardware whereever required in between Energy meter to Lan switch to SDH equipments upto DCU/Gateway and all other H/W, S/W per No. |
| 53 | Installation of OFC cable armoured(6P) in HDPE conduit pipe 32 mm |
| 54 | Erection of Apex Energy Meter Panel Set (with 2 Main + 2 Check) |
| 55 | PART- B : - SUPPLY |
| 56 | Supply of 5 No. U-Bolted type Single Tension Fitting Assembly with Turn Buckle, suitable for Twin ACSR Moose Conductors and 33 K.V. Bus Bar Disc Insulator String, comprising of 4 No. 70 kN disc insulators, complete with hardware fittings, D-shackle, socket eye, ball hook, yoke plate, D-clip, tension clamp etc. as per technical specifications and sample. |
| 57 | Supply of 5 No. U-Bolted type Single Tension Fitting Assembly without Turn Buckle suitable for single ACSR panther Conductors and 33 K.V. Bus Bar Disc Insulator string, comprising of 4 No. 70 kN disc insulators, complete with hardware fittings, D-shackle, socket eye, ball hook, yoke plate, D-clip, tension clamp etc. as per technical specifications and sample. |
| 58 | Supply of Spacer, suitable for 33 K.V. Bus Bar of Twin ACSR Moose Conductors with 250 mm spacing duly made of LM-6 aluminium alloy complete with 12 mm size dia. Hot Dip G.I. Nuts & Bolts and Plain / Spring Washers as per technical specifications and sample. |
| 59 | Supply of Spacer, suitable for Jumper of Twin ACSR Panther Conductors with 100 mm spacing duly made of LM-6 aluminum alloy complete with 12 mm size dia. Hot Dip G.I. Nuts & Bolts and Plain / Spring Washers as per technical specifications and sample. |
| 60 | Supply of 33 K.V. Bus Isolator Bi-Metallic Terminal Connector suitable for Twin ACSR Panher Conductor duly made of LM-6 aluminum alloy complete with 4 Nos. 12 mm size dia. holes with Hot Dip G.I. Nut & Bolts and Spring / Plain Washers as per technical specifications and sample. |
| 61 | 33 K.V. CB. Bi-metallic Clamp duly made of Aluminium Alloy (LM 6), suitable for 33 K.V. CBs and Twin ACSR 'Panther' Conductor, complete with HDG Bolts - Nuts - Washers, as per sample. |
| 62 | 33 K.V. C.T. Bi-metallic Clamp duly made of Aluminium Alloy (LM 6), suitable for 33 K.V. CTs and Twin ACSR 'Panther' Conductor, complete with HDG Bolts - Nuts - Washers, as per sample. |
| 63 | P.G. Clamp made of LM - 6 Alloy having suitable for Moose' to 'Panther' Conductor, complete with Bolt - Nut - Washers (4 No. Nut & Bolts), as per sample. |
| 64 | P.G. Clamp made of LM - 6 Alloy having suitable for ACSR 'Panther' to 'Panther' Conductor, complete with Bolt - Nut - Washers (4 No. Nut & Bolts), as per sample. |
| 65 | 40mm Dia MS Round Bar |
| 66 | 50x6mm MS Flat |
| 67 | 25x6mm MS Flat |
| 68 | Supply of 120Watt LED street Light Luminaries fittings of Philips/Cromton Greaves/Havells/ Bajaj make in piece dia. cast aluminium alloy housing with pot optics reflector and toughened clear glass cover with frame from lamp compartment including cable termination port. Please Enable Macros to View BoQ information |