| 1 | FittinganderectingoneHTPSCSinglePoleinposition,includingfitting cross arm, digging and back filling pit in ordinary soil (as per standards), drawing sufficient length of GI earthing leads from F clamp through V cross arm to the ground for earthing (excluding provision of earthing). |
| 2 | Additionalrateforprovidingonediscset,PGclampetc.complete,onany type of HT pole for making cut point. |
| 3 | LabourchargesforloadingHTPSCpolefromthestackingplaceand unloading the same at work site (transportation by any vehicle). |
| 4 | ErectingoneLTPSCPoleinpositionincludingdigging&backfillingpit in ordinary soil. |
| 5 | Transporting poles by hired vehicle to a distance upto 5km and carrying upto 4 numbers of poles excluding loading& unloading charges. |
| 6 | LabourchargesforloadingLTPSCpolefromthestackingplaceand unloading the same at work site (transportation by any vehicle). |
| 7 | Fitting and providing one HT Stay for 11kV pole, including digging and back filling pit in ordinary soil. |
| 8 | ProvidingoneCoilEarthusingNo.8GI-earthwire(50mmdia,115turns) including digging separate pit (0.45x0.45x1.5m) at standard distance away from the pole/structure in ordinary soil & backfilling. |
| 9 | Providing one Earth using GI earth pipe of size 38.1mm dia, 2.5m length includingdiggingseparatepit(0.45x0.45x2.5m)ataminimumdistance of 1.5m away from the pole/structure and maintaining standard distance between different earth pipes in ordinary soil & backfilling. |
| 10 | Stringing of one km 3 PH 11kV line with XLPE Insulated ACSR Raccoon or equivalant (3 conductors) after fitting insulators, binding conductors to pin insulators using suitable tie and anchoring with wedge type anchoring clamps including cutting and removing tree branches wherever necessary excluding cut point works. |
| 11 | LoadingHTPSCpoletoHandcartfromthestackingplaceandunloading the same at work site (excluding transportation). |
| 12 | FittingoneAdditionalVcrossarminexistingsinglepoleincluding conveyance of materials. |
| 13 | Drilling hole of various sizes on existing Channel/Cross Arm. |
| 14 | Fitting 6 channel cross arms, AB switch, DO fuse, Station class LA, HT & LT connections upto OH lines, etc. on existing DP structure, Fixing distribution box/provision for one set (3No.) of LT fuses, drawing sufficientlengthofGIearthingleadstothegroundforearthing,excluding provision of earthing & mounting of Transformer on poles. |
| 15 | Fitting one additional Fuse unit and giving connection from Transformer to fuse and Distribution box to LT OH line. |
| 16 | TransportingTransformersbyhiredvehicletoadistancebeyond5kmand carrying upto 2 numbers of 63/100/160/250kVA Transformers / Ring Main Units (Running km). |
| 17 | Erectingone100kVATransformertoexistingDPandgivingconnections, including loading from TMR/SRS/other stacking place & unloading at site but excluding cost for transporting transformer. |
| 18 | Fitting 3 channel cross arms, AB switch, DO fuse, LA(Ord), HT < connections upto OH lines, etc. on existing DP structure, fixing distribution box/provision for one set (3No.) of LT fuses, drawing sufficientlengthofGIearthingleadstothegroundforearthing,excluding provision of earthing & mounting of Transformer on plinth. |
| 19 | Fitting one set AB switch, DO fuse (3No.), LA (3No.), giving all connectionsfromHTlinetoTransformerbushanddrawingearthleadsto the ground for earthing excluding provision of earthing and fixing channels. |
| 20 | TransportingLTABCbyhiredvehicletoadistanceupto5kmand carring up to 2 drum including loading and un loading using crane |
| 21 | FittingandprovidingoneStrutusingHTPSCpoleincludingdiggingand back filling pit in ordinary soil. |
| 22 | Fitting and erecting one HT Double Pole Structure using PSC pole in position including fitting 2 channel cross arms, digging and back fillingpit in ordinary soil, drawing sufficient length of GI earthing leads through all cross arms to the ground for earthing (excluding provision of earthing). |
| 23 | Fitting one set AB switch on existing DP, giving connection and drawing sufficientlengthofGIearthingleadstothegroundforearthing,excluding provision of earthing. |
| 24 | FittingoneAdditional2.4m/3mChannelcrossarm(100x50x6mm),in existing 11kV DP including conveyance of materials. |
| 25 | Transporting Transformers by hired vehicle to a distance upto 5km and carrying upto 2 numbers of 63/100/160/250kVA Transformers / Ring Main Units excluding loading& unloading charges. |
| 26 | Providing Transformer fencing to a height of 1.8 m above ground level using MS Angle frames of size ISA 50x50x6mm for outer frame, 2 runs of 40 x 6 MS flat for horizondal brasing and grills with MS rods 8 mm Dia @ 10cm c/c for verticals, providing gate with locking arrangements, providing danger board & name board, embeding the legs in cement concrete1:2:4,footingofsize30cmx30cmx50cm,paintingwithsynthetic enamel paint two coats over one coat of iron primer etc complete, incl cost of transportation |
| 27 | Cleaning and levelling of transformer yard/RMU, spreading 40 mm broken stone in yard for a thickness of 10 cm above bed of 10 cm thick 6 mm broken stone, after constructing a curb wall of height 20cm above ground and 10cm below level including cost of all materials and charges for conveying, spreading, consolidating etc. |
| 28 | FittingoneAdditional75x40mm,1.8mChannelcrossarminexisting single pole including conveyance of materials. |
| 29 | Pole numbering using printed Aluminium sheets of 22 SWG having size 20 x 12 cm or Painting the surface of line supports where numbers are to be inscribed, Pole numbers shall be painted in circular / rectangular background, using approved quality anti algal yellow paint in two coat after scraping and cleaning the surface at a height of 2.5 metre above groundlevel.Thenumberandlettersshouldbeinblacksyntheticenamel paint. The size of the number should be at least 2cm in height x 1.5cm in width. including cost of paint. |
| 30 | Quoted Amount of BOQ1 in figures |
| 31 | GST Rate in percentage Please Enable Macros to View BoQ information |