| 1 | PART - A 1. Installation of 6 nos of Line DP with AB Switch for cable rising. 2. Construction of 3Ph 3W 11KV OH line of length 280 mtr with 55mm2 AAAC using 11 mtr long WPB GI Pole with 1No. of strut pole. |
| 2 | WPB 160X152(11Mtr.long,30.44 Kg/Mtr) |
| 3 | Top channel 100x50x6mm(1200 mm long ) ( 9.56 Kg/ Mtr.each channel) (GI) length 3 mtr, 2nos channel (GI) required = (2x9.56 x3) |
| 4 | Fish plate 50x6mm 2.36 kg/mtr,each 0.280 mtr length, 6 nos required=(6x2.36x0.280) |
| 5 | AB Switch mounting channel 75x40x4.8mm 7.14kg/mtr Each channel (GI) length 3 mtr, 2 nos channel (GI)required= (7.14x3x2) |
| 6 | AB Switch side support channel 100x50x6mm,9.56Kg/mtr, each channel length 0.35 mtr, 2 nos channel required= (9.56x2x0.35) |
| 7 | Channel support for down pipe 75x40x4.8mm,7.14kg/mtr each channel length 0.8 mtr, 1 nos channel required=(7.14x0.8x1) |
| 8 | Double pole belting channel (GI) 75 x 40x 4.8mm, 7.14 Kg/Mtr each channel (GI) Length 3.0 mtr, 4 nos channel (GI) required = (7.14 x 3 x 4) |
| 9 | 50x50x6mm GI Barcing angle (GI), 4.5 Kg/mtr, each angel (GI) length 3.512 mtr, 4nos angle (GI) required = ( 4.5 x 3.512x 4) |
| 10 | Danger plate |
| 11 | Back clamp for DANGER PLATE 25 x 3mm flat, 0.59 kg/mtr flat of 0.510 mtr length 2 nos= 2x0.59x 0.510) |
| 12 | HT Stay Clamp |
| 13 | H.T.Stay set (Complete) |
| 14 | H.T.Stay insulator type-C |
| 15 | 7/10 SWG Stay wire 15kg/stay |
| 16 | GI Pipe earthing 40mm, 3 MTR LONG |
| 17 | 50x6mm GI Flat for earthing, 2.36 kg/mtr |
| 18 | GI barbed wire anticlimbing device (3 kg /Pole) |
| 19 | Back clamp for anticlimbing Device 25 x 3mm flat, 0.59 kg/mtr flat of 0.510 mtr length 8 nos= 8x0.59x 0.510) |
| 20 | Lightning Arrester (12KV,10KA)(Staion Class, class-2) |
| 21 | AB Switch (11KV,400A,3 Pole,50Hz) |
| 22 | 11KV pin insulator polymer |
| 23 | H W fitting (B&S)70KN 3 (bolted) |
| 24 | Disc insulator (B&S) 70 KN Polymer |
| 25 | Wedge connector for 148sqmm AAA Conductor |
| 26 | Polycarbonate bird guard |
| 27 | GI Nut & bolts & washer of different sizes |
| 28 | Black colour paint for numbering |
| 29 | Yellow colour paint (GIS Numbering & Zebra stripping) for Background |
| 30 | Civil & Services |
| 31 | Fixing of complete 11KV Line complete stay set includes 1) Turn buckle assembly 2) Stay Rod & stay plate 3) Stay insulator 4) Stay wire 5) Stay clamps with Nuts & bolts BA will do the excavation including excavation, supply of 0.5cum CC 1:2:4 |
| 32 | Concreting ratio 1:1.5:3 (500mm x 500mm x 1800mm) 0.450 Cu mtr (Per Pole) |
| 33 | Couping ration 1:1.5:3 with dimension (500x500x450)= 0.1125 Cu mtr |
| 34 | Provide necessary civil material for construction of Earthing Chamber, excavation & installation of including earthing pipe dia up to 100mm dia for length of 3 mtr . |
| 35 | Materials for 11 KV Cut Point with 90 Degree Angle |
| 36 | WPB 160X152(11Mtr.long,30.44 Kg/Mtr) |
| 37 | Straight Cross Arm 100x50x6mm 9.56 Kg/ Mtr.each channel (GI) length 1.2 mtr, 4nos channel (GI) required = (4x9.56 x1.2) |
| 38 | Fish plate 50x6mm 2.36 kg/mtr,each 0.280 mtr length, 16 nos required=(16x2.36x0.280) |
| 39 | Straight Cross Arm 100x50x6mm 9.56 Kg/ Mtr.each channel (GI) length 1.2 mtr, 4nos channel (GI) required = (4x9.56 x1.2) |
| 40 | Danger plate 1 nos |
| 41 | Back clamp for DANGER PLATE 25 x 3mm flat, 0.59 kg/mtr flat of 0.510 mtr length 1 nos= 1x0.59x 0.510) |
| 42 | GI barbed wire anticlimbing device (3 kg /Pole) |
| 43 | Back clamp for anticlimbing Device 25 x 3mm flat, 0.59 kg/mtr flat of 0.510 mtr length 4 nos= 4x0.59x 0.510) |
| 44 | 11KV pin insulator polymer |
| 45 | H W fitting (B&S)70KN 3 (bolted) |
| 46 | Disc insulator (B&S) 70 KN Polymer |
| 47 | Earthing of support (Coil Type) |
| 48 | No-8 GI Wire |
| 49 | Wedge connector for 148sqmm AAA Conductor |
| 50 | Polycarbonate bird guard |
| 51 | HT Stay Clamp |
| 52 | H.T.Stay set (Complete) |
| 53 | H.T.Stay insulator type-C |
| 54 | 7/10 SWG Stay wire 15kg/stay |
| 55 | GI Nut & bolts & washer of different sizes |
| 56 | Black colour paint for numbering |
| 57 | Yellow colour paint for Background |
| 58 | Civil & Services |
| 59 | Fixing of complete 11KV Line complete stay set includes 1) Turn buckle assembly 2) Stay Rod & stay plate 3) Stay insulator 4) Stay wire 5) Stay clamps with Nuts & bolts BA will do the excavation including excavation, supply of 0.5cum CC 1:2:4 |
| 60 | Concreting ratio 1:1.5:3(500mmx500mmx1800mm)0.55Cu mtr (Per Pole) |
| 61 | Couping ration 1:1.5:3 with dimension (500x500x450)=0.1125 Cu mtr (Per Pole) |
| 62 | Materials for 11 KV Pin Points with WPB |
| 63 | WPB 160X152(11Mtr.long,30.44 Kg/Mtr) |
| 64 | 11KV V Cross Arm 9GI) |
| 65 | Top bracket 100x50x6mm GI Channel (GI) |
| 66 | Danger plate 11KV |
| 67 | Back clamp for DANGER PLATE 25 x 3mm flat, 0.59 kg/mtr flat of 0.510 mtr length 1 nos= 1x0.59x 0.510) |
| 68 | GI barbed wire anticlimbing device (3 kg /Pole) |
| 69 | Back clamp for anticlimbing Device 25 x 3mm flat, 0.59 kg/mtr flat of 0.510 mtr length 4 nos= 4x0.59x 0.510) |
| 70 | 11KV pin insulator polymer |
| 71 | Earthing of support (Coil Type) |
| 72 | No-8 GI Wire |
| 73 | GI Nut & bolts & washer of different sizes |
| 74 | 55sqmm AAA Conductor |
| 75 | Black colour paint for numbering |
| 76 | Yellow colour paint for Background |
| 77 | Polycarbonate bird guard |
| 78 | Civil & Services |
| 79 | Concreting ratio 1:1.5:3 (500mmx 500mmx 1800mm) 0.450 Cu mtr (Per Pole) |
| 80 | Couping ration 1:1.5:3 with dimension (500x500x450)= 0.1125 Cu mtr (Per Pole) |
| 81 | PART - B Construction of 11KV Line protecting guarding for road crossing |
| 82 | Guarding Channel (GI) 75X40X4.8mm, 7.14 Kg/Mtr, each Channel (GI) Length 2.2 mtr, 4 nos channel (GI) Required = (4x7.14x 2.2) for single pole) |
| 83 | No-6 GI Wire (0.192Kg/mtr) for main string |
| 84 | No-8 GI Wire (0.131Kg/mtr) for lacing |
| 85 | Eye Bolt (236mm, 16mm dia, 1.577 Kg/Mtr) |
| 86 | GI Pipe earthing 40mm, 3 MTR LONG |
| 87 | 50 x 6mm Flat (GI) for earthing, 2.36Kg/Mtr, (10.7 mtr for raising)= 10.7x2.36 |
| 88 | Civil & Services |
| 89 | Construction of earthing chamber including installation of earthing pipe. |
| 90 | PART- C Supply & Laying of 11KV 3C x 400mm2 UG XLPE Cable with 1 Run Spare for length 245 Mtr. |
| 91 | Supply of 1.1kv, 3 core, 400sqmm, XLPE insulation armoured UG Cable |
| 92 | Supply of Outdoor termination kits heat shrinkable type suitable for 11KV, 3 Core, 400 sqmm, HT UG Cable Kits |
| 93 | Erection Portion |
| 94 | Erection of Straight through jointing kits/ outdoor termination kits/ indoor termination kits heat shrinkable type suitable for 11KV, 3 Core, 400sqmm, aluminium UG Cable Kits |
| 95 | Installation, Laying, Commissioning & Testing of 11KV, 3 Core, 400Sqmm, XLPE U/G Cable by HDD method with HDPE Pipe (200mm dia, PN8 PE80) including supply of HDPE Pipe. |
| 96 | Civil & Services |
| 97 | Supply and erection of GI Pipe of dia 150mm, Class-B (8 mtr) |
| 98 | Supply and erection ofCable Route Marker along with cable route an interval of 30 mtrs with Civil Works |
| 99 | PART - D Construction of LT AB Cable OH line of length 0.360 Km (12 spans) using- 4C x 50 + 1C x 16sqmm (Street light) on 300Kg 9 Mtr PSC Pole. |
| 100 | 9Mtr long 300Kg PSC Pole |
| 101 | LT Stay complete |
| 102 | 7/12 SWG GI Stay wire, Grade 2 |
| 103 | LT Stay clamp |
| 104 | LT Stay Insulator |
| 105 | Pole Clamp for EYE hook for XLPE Aerial bunched cable |
| 106 | EYE Hook for XLPE Aerial bunched cable |
| 107 | Dead end clamp suitable for messenger XLPE Aerial bunched cable |
| 108 | Suspension Clamp with EYE Hook for ABC |
| 109 | 4C x 50mm2 (P)+ 1Cx50mm2(M) + 1C x 16mm2 (Street light)LT AB Cable |
| 110 | 4Way Service Distb. Box with Kit Kat fuse and Aluminium Bus Bar. |
| 111 | Insulated piercing connector. Type-A-Main 50 to 150 sqmm & Tap-50 to 150 sqmm |
| 112 | GI Pipe earthing |
| 113 | Coil earthing |
| 114 | No-8 GI Wire |
| 115 | Danger plate |
| 116 | Back clamp for DANGER PLATE 25 x 3mm flat, 0.59 kg/mtr flat of 0.510 mtr length 1 no= 1x0.59x 0.510) |
| 117 | GI barbed wire anticlimbing device (3 kg /Pole) |
| 118 | Back clamp for anticlimbing Device 25 x 3mm flat, 0.59 kg/mtr flat of 0.510 mtr length 4 nos= 4x0.59x 0.510) |
| 119 | GI Nut & bolts & washer of different sizes |
| 120 | Black colour paint for numbering |
| 121 | Yellow colour paint (GIS Numbering & Zebra stripping) for Background |
| 122 | Civil & Services |
| 123 | Fixing of LT Complete Stay Set. |
| 124 | Concreting ratio 1:1:5:3(M-20 Grade)(500mm x 500mmx1500mm)= 0.375 Cu mtr (Per pole) |
| 125 | Construction earthing chamber including installation of earthing pipe making earthing chamber including excavation, soil teatement with bentonide powder, calculation of eartg resistance, including installation of 3 mtr GI Pipe 40mm/50mm including welding of GI flat around pipe. |
| 126 | PART - ELaying of LT U/G Cable of length 160 Mtr using 4C x 150mm2 LT UG Cable with 1 Run Spare. |
| 127 | Supply of 1.1 KV, 4 Core, 150sqmm, XLPE insulation armoured-Aluminium UG Cable. |
| 128 | Erection Portion |
| 129 | Installation, Laying, Commissioning & Testing of LT XLPE UG Cable by HDD Method with HDPE Pipe |
| 130 | Supply and erection of double compression flameproof type glanding for armoured cable 3.5/4C 120-185sqmm done as per TPCODL Spec and approved make dowells. |
| 131 | PART - FDismantling of Materials |
| 132 | Dismantling of 09/11 Mtr Joist/WPB Pole-116x100mm |
| 133 | Dismantling of 9/8 Mtr PCC/ Joist Pole |
| 134 | Dismantling /Removal of V Cross Arm from pole |
| 135 | Dismantling of 11KV Pin Insulator with Pin |
| 136 | Dismantling of 11KV Disc Insulator with Hardware |
| 137 | Dismantling /Removal of MS Channel from Double Pole Strcture/ Pole |
| 138 | Dismantling of ACSR/AAAC 34/55mm2 from overhead line |
| 139 | Dismantling of various size of LT AB Cable. |
| 140 | PART - GPOWER SUPPLY TO THE STREET LIGHT FITTINGS (11 kv cut point with 90 degree - 01 no) & (DP mounted DSS-01 No) |
| 141 | WPB 160x160x6-11M 30.44 KG/MTR Line |
| 142 | 100x50x6 G.I Channel |
| 143 | G.I Flats 50x6mm |
| 144 | Danger Board 11KV |
| 145 | GI Flats 25 x 3mm |
| 146 | GI Standed wire barbed wire |
| 147 | Pin Insul polymer 11Kv 20MM FRP DIA |
| 148 | H/W/F(B&S) 70KN 3 Bolt |
| 149 | Insu Disc polymer 11KV B&S 70KN |
| 150 | Coil earthing |
| 151 | GI Earth wire no.8 SWG/4.06MM Dia |
| 152 | Wedge connector for 55sqmm conductor |
| 153 | Polycarbonate bird guard |
| 154 | Stay clamp 150x 150mm RS Joist |
| 155 | HT Stay set complete |
| 156 | Insulator stay HT |
| 157 | GI Standrad wire 7.10 SWG-7/3 25MM |
| 158 | GI Bolts & nuts assorted dimension |
| 159 | Black paint with barrel |
| 160 | Enamel paint yellow |
| 161 | Inst 11KV Complt stay set ith concrete |
| 162 | Laying of PCC M20 |
| 163 | Conductor Raddit AAAC 55 Sqmm |
| 164 | WPB 160x160x6-11M 30.44 KG/MTR Line |
| 165 | 100x50x6MM G.I Channel |
| 166 | GI Flats 50 x 6mm |
| 167 | GI Channel 75x40x4.8mm |
| 168 | GI Angle 50x50x6mm |
| 169 | Transformer 25KVA 11/.4 KV |
| 170 | LT Distribution box 25KVA S/S 11/0.4KV |
| 171 | AAAC 1KV XLPE Insu CVRD CDTR. 55SQMM |
| 172 | Cable 1.1KV LT XLPE 4C x 35sqmm Armd-ALU |
| 173 | AB S/W 11KV Trip Pole Gang ope 200A |
| 174 | HG Fuse Set 11KV 200Amp 3 pole 3 phase |
| 175 | Wedge connector for 55sqmm conductor |
| 176 | Polycarbonate bird guard |
| 177 | Insu Disc polymer 11KV B&S 70KN |
| 178 | H/W/F(B&S) 70KN 3 Bolt |
| 179 | Lighting Arrestor 1KV 10KA STION Class |
| 180 | PIN Insul polymer 11Kv 20MM FRP DIA |
| 181 | HT Stay set complete |
| 182 | Stay clamp 150x 150mm RS Joist |
| 183 | Insulator stay HT |
| 184 | GI Standrad wire 7.10 SWG-7/3 25MM |
| 185 | GI Earthing pipe 40mm dia 3m Length |
| 186 | GI Bolts & nuts assorted dimension |
| 187 | GI Standrad wire birbed wire |
| 188 | GI Flats 25 x 3mm |
| 189 | Danger Board 11KV |
| 190 | CT W/O Name plate |
| 191 | Enamel Paint Yellow |
| 192 | Black paint with barrel |
| 193 | Laying of PCC M20 |
| 194 | PCC 1:3:6 |
| 195 | Inst 11KV Complete stay set with concrete |
| 196 | Earth chamber incl inst of earthing pipe |
| 197 | Laying 1.1KV Cable upto 120sqmm |
| 198 | Supply & erection GI Fencing with Gate |
| 199 | Supply & cmpg/fixing/conn termi AL35Lug |
| 200 | Sup/Inst 3.5/4C 16-35 Sqm Glnd/Al Term |
| 201 | PART - HSUPPLY AND INSTALLATION OF STREET LIGHTS |
| 202 | Supply of 9 Mtr long internally and externally Hot Dip Galvanized Octagonal pole made up of top dia 90 mm & boƩom dia 190 mm and 3 mm thick HT Steel sheet conforming to grade S355JO, E350 with weather proof and vandal resistant pole. Base Plate Size 300X300X20 mm thick shall be welded (Inside & outside) with pole shaŌ, 4 Nos M24X850mm long J Bolt along with Temp plate, 3 Nos Nut & washer, including inbuild JB, containing (SP MCB, Terminal Stud, Backlite Sheet, SS hardwire Etc) |
| 203 | Supply of 48.4MM OD HDG Single Arm bracket (1.5Mtr Long) suitable for carrying different wattage Street light for Octagonal Pole/Tubular Pole |
| 204 | Supply of 48.4MM OD HDG Double Arm bracket (1.5Mtr Long) suitable for carrying different wattage Street light for Octagonal Pole/Tubular Pole |
| 205 | Constructing RCC Foundation of size (1000x1000x1500)mm for errection of the above pole. |
| 206 | Supply and fixing of Coil earthing. |
| 207 | Supplying, Installation and Commissioning of energy saving LED 120 watt street light with IP-66 and IK-08 protection & 140 Lumen/Watt efficasy. |
| 208 | Supply and laying of 4x16mm2 Al.Ar. U.G cable. |
| 209 | Supply and laying of 3 ½ X 25mm2 Al.Ar. UG Cable. |
| 210 | Cable trenching in all type of soil excepting rockey soil including excavation of earth,brick laying and filling of sand and loose earth to the original ground level with surface dressing after laying 1 no 1.1 KVPVC insulated PVC sheathed armoured cable removal of surplus earth to a lead up to 5km. |
| 211 | Supply and Laying of 40mm HDPE pipe for laying of Cable. |
| 212 | Construction of pedastal for the panel in ash brick of size (900x450x600)mm. |
| 213 | S/F of 63 Amp Outdoor type double door plinth mounted panel board made out of 2mm thick CR sheet duly acid treated for de-rusting, primered and powder coated with approved enamel paint having hinged door with provision for cable entry duly factory wired and locking arrangement etc. complete with following provisions.Incoming:-1. 63Amp 25KA 4P MCCB-1 NoOutgoing:-1.40Amp TPN MCCB-01 No. 2.32Amp DP MCB-2 Nos.3.200Amp copper bus bar.4. 0-100Amp Ammeter with selector switch-1Set 5. 0-500Volt Voltmeter with selector-1Set6. Indicator lamp-1Set. 7.Time switch with contactor complete set Size of panel board 36\\"x 24\\"x10\\" |
| 214 | Supply and fixing of standard earthing to the panel. Please Enable Macros to View BoQ information |