| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.opper conductor single core cable etc as required. |
| 2 | Group C |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed heavy class PVC conduit having wall thickness 2.0mm as required |
| 4 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 5 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 6 | 2X4 sq. mm + 1X4 sq. mm earth wire |
| 7 | Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 8 | 4X4 sq. mm + 2X4 sq. mm earth wire |
| 9 | Supplying and fixing suitable size GI box with modular plate and cover in FRLS on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 10 | Armoured Cable 25 Sq.mm. (3.5 core) |
| 11 | 2.2.13 Providing and fixing following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 12 | MCCB 32 A- 100 A 18 KA |
| 13 | Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 14 | 63 Amps |
| 15 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 16 | 63 Amp |
| 17 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 18 | 16 way, Double door |
| 19 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 20 | Single pole |
| 21 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required |
| 22 | 40 amps |
| 23 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 24 | Earthing with Copper earth plate 600 mmx600 mmx 6 mm thick |
| 25 | Supplying and fixing copper tape 20mmx3mm thick on parapet or surface of wall for lightning conductor as required ( for horizontal run) |
| 26 | Supplying and fixing copper tape 20mmx3mm thick on parapet or surface of wall for lightning conductor as required ( for vertical run) |
| 27 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required. |
| 28 | 8swg copper wire |
| 29 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 30 | 32 mm Dia |
| 31 | Providing and fixing of IP65 Bulkhead led fixture 10 W +/- 1 W Wall Mounted with minimum system lumen efficacy of 100 lm/W with Pressure Die Cast Aluminum housing, Polycarbonate Opal Diffuser and P.F.>0.95 with THD<10% ,CRI 80.The LED shall be tested with LM80-08 standard with Useful life of 50000 Hrs at L70 .The LEDs used in the luminaire shall have CCT of ANSI Bin 5700 K only with CRI of minimum 80.The Input voltage range shall be 140V to 280V, 50/60 HZ complete with all accessories, including connections, testing and commissioning etc.as required complete in all respects. |
| 32 | LED Bulk Head Light 10W |
| 33 | Providing and laying 19mm (Nineteen milimeters) thick cheema pink granite stone having semi round nosinglaid over 20mm (twenty millimeters) thick base of cement mortor 1:3(one cement: three sand) and jointed withement sluree mix pigment to match the shade of granite stone including rubbing polishing moulding and nosingomplete a s per approved specification, drawing and design inclusive o f cost and carriage o f materials with in al leads, lifts and other incidentals, a s per the direction and entire satisfaction of Engineer-In-Charge. Rate inclusive toll tax, GST and other taxesvimposed by the Government. |
| 34 | Providing and laying four courses water proofing treatment with bitumen felt over roofs consisting of finst and third courses of blosn bitumen 15/25 conforming to IS ippled lot it 1.10 Keper square metre of arca for each enurse second cose of fooling l e finished bitumen felt and fourth and final course of stone grit 6 deed own sire or peasized prutel spread at f eubic decimeter per square metre. includmg preparation of surface not excluding grading complete with Bitumen |
| 35 | Finishing wall with weather proof exterior grade emulsion of approved design (Apexultima) or its equarlied on undecorated wall surfaces (two coats) to give an even shade and final finish after throughly cleaning the surface to remove all dirt, dust and other foreign matter ete including sand paper smooth complete. |
| 36 | Acceptable Make |
| 37 | Copper Wire/Telephone Cable/UTP cable/ TV Cable:Finolex/KEI/ Polycab/ RR Kabel/ Havells/ Grandlay (duly ISI Marked) |
| 38 | Aluminium and copper XLPE Power Cables Armoured/Unarmoured:Finolex/KEI/ Polycab/ RR Kabel/ Havells/ Grandlay (duly ISI Marked) |
| 39 | Cat 6/ 6A Cable:Molex/ Digilink/ Schneider/ Belden/ Legrand |
| 40 | Modular Switch, Socket, Fan regulator, RJ-45, Cable TV socket, Data outlet socket, GI boxes etc. and accessories:Legrand : ARTEOR Honeywell : ORNA Panasonic : EUROPA Schinedier : ZENCELO |
| 41 | PVC Conduit with accessories:Finolex/ Supreme/ BEC/ NIC/ Polycab/ AKG (All shall be Min. 2mm thick and ISI marked) |
| 42 | MS Conduit with accessories:AKG/ NIC/ BEC/ RMCON (Note: The accessories shall be same that of conduit pipe and will comply to IS/ 4768 part 2 2003) |
| 43 | GI Pipe (for pipe pole and other items):Tata/ Jindal/ SAIL (All shall be ISI marked) |
| 44 | OFC cable and accessories:Belden/ D Link/ Tyco |
| 45 | Gland:Comet/ Dowells |
| 46 | HDPE/ DWC pipe:REX/ Duraline/ Duraplast/ Triputi |
| 47 | MCB/MCB DB/ Isolator/ RCCB/ Industrial Socket |
| 48 | MCCBs/ RCCBs/4 Pole Power contractor /Change Over:Legrand /Siemens/ Schneider/ L&T /ABB |
| 49 | 600 mm LED mirror light:L&T D Sine/ Schneider Compact NSX/ Legrand DPX3/ Siemens 2 VL/ ABB |
| 50 | LED bulk head fitting:Phillips/ Wipro/ Trilux/ Havells/ LT/ Panasonic |
| 51 | LED downlighter:Phillips/ Wipro/ LT/ Regent/ Panasonic |
| 52 | 36 watt 2'x2' panel light:Phillips/ Wipro/ LT/ Regent/ Panasonic |
| 53 | 36 watt LED batten light:Phillips/ Wipro/ LT/ Regent/ Panasonic |
| 54 | LED bed side light |
| 55 | Decorative wall light with E27 holder:Phillips/ Trilux/ Regent/ LT/ Lustre/ Panasonic/ wipro |
| 56 | 250/200 mm fresh air fan:USHA/ Khaitan/ Crompton/ Almonard |
| 57 | 300 mm sweep heavy duty exhaust fan:Usha/ Almonard/ Havells/ Orient/Bajaj/ Crompton |
| 58 | 3 /25 Ltrs. Geysers::Recold/ Bajaj/ Havells/ Crompton/ AO Smith/ Venus |
| 59 | 2 compartment energy meter board panel feeder pillar:Kalyani Switch Gear/ Power Associates/ Pristine/ Milestone/ ADLEC/ Tricolite/ ASPL/ CMKL |
| 60 | Ceiling fan:Usha/ Almonard/ Havells/ Orient/Bajaj/ Crompton |
| 61 | Or as per given against item or work and as per approval of Engineer-in-Charge Please Enable Macros to View BoQ information |