| 1 | Rising Main: Providing, Laying, fitting and testing of Mild Steel Pipe of 450mm NB with 5 mm wall thickness. The pipes shall be painted in two coats of anticorrosive bituminous paint over one coat of steel primer. The overall specification of the pipe shall be as under: Nominal bore. = 450mmWall thickness = 5 mmType of welding = ERW Grade = Fe410Length of each pipe = 6mPipe to be manufactured as per IS-3589 with latest amendmentsThe Pipes shall be laid and connected end to end by required welding using high quality Electrodes of Ador/ Essab in 2 Runs and the weld shall be of smooth finish and free from defects.All tools and tackles for laying and fitting of pipe shall be arranged by the firm.Make: Tata/Jindal/Suryaprakash/Equivalent as approved in EOI of SE Mech. Circle Kashmir. Pipe Manufacturers test certificate to be appended. |
| 2 | Earthwork in excavation by mechanical means (hydraulic excavator) in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5m in width) and for shafts and wells, cesspits and like not exceeding 10sqm on plan, including dressing of sides and ramming of bottoms lift up to 1.5m including getting out of excavated earth and disposal of surplus excavated earth as directed within a lead of 50m. (As per SSR 2.9 of 2024)a) All kinds of soil) |
| 3 | Supply installation testing and commissioning of DN 450mm, DI Reflux Non-return Valve PN 1.6 conforming to IS-5312 with latest amendments or equivalent international standards to following a) Body: Ductile Ironb) Cover : Ductile Iron c) Disc : Ductile Iron Coated with EPDM rubberd) Seat ring: Bronze/ SS e) Surface Protection: Electro static epoxy powder coating.Make: VAG/AVK/TALIS/ Equivalent as approved in EOI of SE Mech. Circle Kashmir. The job includes fabrication of By-pass arrangement for 450 mm dia NRV as under: -i) Creating hole of dia 50 mm dia using gas cutter.ii) Providing and fitting of 50 mm dia GI pipe of required length along with 02 No. of elbows of reputed make.iii) Providing and fitting of 01 no. brass/GM ball valve 50 mm of reputed make Welding:The by-pass arrangement is to be joined by continuous butt welding in at least 2 runs on outside surface of the pipe. Before welding a V-groove is to be made by grinding the edges of pipe by a portable grinder in order to accommodate the welding material to make the joint strong. The welded area shall be chipped properly and flux removed to ensure crack free / leak proof joints on full working pressure. Quality product electrodes of Philips/ ESSAB/ADOR make only shall be used for welding.Specification of mating flange: The flange required for fitting of above reflux valve to 450 mm dia delivery pipe shall be inconformity with the flanges of the valve. The flanges shall not be less than 25mm thick. The job included providing and fitting of suitable size M.S nuts and bolts for fitting of valve. Test certificate of the Manufacturer to be provided. The job includes testing of same at full load. |
| 4 | Supply installation and testing of DN 450, PN 1.6 sluice valves conforming to IS 14846 with latest amendments or equivalent international standard to following specification: -Material of construction: -a) Body, Bonnet : Ductile iron b) Wedge : Ductile iron c) Spindle/Stem : St Steel d) Stem nut : Bronze/SS/Brasse) Bonnet Gasket : Neoprene/EPDM rubberf) Make: VAG/AVK/TALIS/Equivalent as approved in EOI of SE Mech. Circle KashmirSpecification of mating flange: The flange required for fitting of shall be inconformity with the flanges of the valve. The flanges shall not be less than 25mm thick. The job included providing and fitting of suitable size M.S nuts and bolts for fitting of valve. Test certificate of the Manufacturer to be provided.The job includes testing of same at full load. |
| 5 | Providing, fabrication, fitting and testing of 450mm M.S long radius flanged bend for delivery side, with one end having 450mm flange and other end flange as per the pump delivery. The pipe shall confirm BIS-3589. The thickness of the flange shall not be less than 25mm. The job includes providing and fitting of nut bolts and gaskets of required size. |
| 6 | Flanged Suction pipe: Fabrication, providing, fitting, testing and commissioning of Mild steel flanged suction Pipe with following specifications: Nominal bore = 300mm Wall thickness = 5.6mmType of welding = ERWGrade = Fe410The suction pipe is to be provided in pieces of :2.4m, 1.2 m, 1m and 0.3m.Pipe to be manufactured as per BIS-3589 with latest amendments.All allied flanges to be fitted to the suction pipes shall not be less than 25mm thick. The job includes fitting material like nuts/bolts & RI Cloth washer etc and applying of metallic primer and two coats of paint. |
| 7 | Flanged bend: Fabrication, providing, installation, testing and commissioning of 300mm dia. Mild steel Flanged bend as per site requirement for suction side duly fitted with M.S flanges at both the ends. The bend shall be fabricated out of 5.6 mm thick M.S pipe. Pipe shall be as per BIS-3589 with latest amendments. The job includes providing and fitting of nut bolts and 300mm dia gaskets (02 No.). The job includes applying one coat of steel primer and two coats of bituminous paint.The allied flanges to be fitted to the suction shall not be less than 25mm thick. |
| 8 | Fabrication, providing and fitting of reducer/increaser as per pump suction. The reducer/increaser shall be fabricated out of 300mm dia M.S pipe not less than 5.6mm thick. The job includes providing and fitting of M.S flanges not less than 25mm thick to its both ends, with one end confirming to the suction side of the pump and the other having 300mm dia. The job includes providing and fitting of nut bolts and 300mm dia gaskets (01 No.). The job also includes applying one coat of steel primer and two coats of bituminous paint. |
| 9 | Fabrication, providing, erecting, testing and commissioning of 03-Ton Capacity Over Head Gantry. The job comprises of the following specifications of the material along with the involvement of material and process of fabrication --a) Vertical supports: -Fabrication, providing and erection of Gantry vertical posts (2 Nos.) 5m each to be fabricated out of ISMB 200. Both the ends of the vertical posts shall be fitted with base plates (top and bottom) of size 300mm×300mm×12mm. The vertical posts to be fitted with foundation bolts which are embedded in cement concrete block. b) Fabrication, providing and fitting of foundation bolts (L/J type) of size 25mm dia, 600mm in total length to be embedded in cement concrete block. c) Gantry Beam: -Providing and fitting of Horizontal I beam of size ISMB-200 and having a total length of 3 4Mtrs shall be fitted on top of the vertical posts, aligned properly. The base plates of size 300mm×300mm×12mm shall be fitted with both the ends of the horizontal beam. The plates to be properly holed as per requirement. d) Providing and fitting of angle iron pieces of 1 feet long out of ISA 50 ×50 ×6 to both the vertical posts by welding for easy access.(24 No.)The complete gantry is to be painted with one coat of steel primer followed by two coats of super enamel paint of desired shade of a reputed make |
| 10 | Monorail and chain pulley block: -Providing and fitting of 3-Ton capacity travelling monorail of spur gear type and 3-Ton capacity Chain Pulley block having minimum chain length of 6mtrs. The chain pulley block and the travelling trolley shall be of Indef make/Pullift/Anchor/Elephant/Equivalent as per EOI of SE Mechanical Kashmir I&FC Department srinagar. Manufacturers test certificate shall be provided at the time of supply of equipment. |
| 11 | Supply, installation, testing and commissioning of Horizontal shaft centrifugal pump coupled with AC induction squirrel cage prime mover as per following specifications:PUMP: -Make: Kirloskar/ M&P/Wpil/ Equivalent as per EOI of SE Mechanical Kashmir I&FC Department Srinagar.Type: Horizontal shaft centrifugal, Mixed/Radial flow, End Suction/Split casingDischarge: 10 Cusec/1020m3/hrTotal dynamic head: 15mLiquid to be handled: Raw waterNo. of stages: OneNPSHA: 3.35mSealing arrangement: Gland packedPump efficiency at duty point: Not less than 78% at duty pointSpeed: 980 RPMDiameter of suction: 300mmDiameter of Delivery: 250mmMaterial of Impeller: ASTM351/CF-8MMaterial of Pump Shaft: AISI SS 410Material of Shaft Sleeve : SS 410Material of Impeller Nut/Lock Nut: SS 410Type of bearing: Oil/grease lubricated Material of Pump casing: C. I close fine grainedMaterial of Pump Gland: BronzeElevation above M.S.L: 1585mCoupling: Flexible M.S. tyre type coupling bored accurately and keyed to shafts designed for load.Base frame: M.S fabricated sturdy for mounting above pump and motor designed for required load.Foundation: L&J type bolts to be grouted in cement concrete block in M20 mix.Spare parts: Tyre coupling Rubber washer for coupling (02 No.)MOTOR:-Model type: AC Squirrel cage induction motor.Rating: 100 HPSpeed: 980 RPMPower supply: 415± 10% Volts, 3-phase.Frequency: 50± 3% Hz.Class of insulation: F or aboveType of enclosure: TEFCIP Rating: 55.Duty type: S1Motor efficiency: IE2Mounting type: FootMake: ABB/Kirloskar/Crompton &Greaves/Equivalent as approved in EOI of SE Mech. Circle Kashmir.Manufacturer’s test certificate is mandatory.The suction/delivery size has been preferred based on site conditions/suction/delivery of the pump. If any change in size of pump suction/delivery as provided by OEM then the contracting firm to provide increaser/decreaser according to the suction/delivery of pump. |
| 12 | Providing/installation/testing and commissioning of horizontal mono block pumping unit single phase for priming system with all fittings complete. The details here are:Type: Mono block single phaseDischarge: 0.5 to 1 lpsHead: Range 7 to 10 mSpeed: 2900rpmQuality of water: RawMotor rating: corresponding to head and discharge. Make: Crompton/Kirloakar/Equivalent as approved in EOI of SE Mech. Circle Kashmir.The job includes providing and fitting of 20mm GI pipe 10 mtrs along with all pipe fittings, pipe specials viz., elbows, unions, tees, etc. for fabricating priming system to horizontal pumps. The job also includes ball valve of size- 20mm dia of heavy duty 1 No. for the same. The priming system shall be fabricated as per site requirement. The job also includes 2.5mm sq copper multistranded wire (10m). |
| 13 | Providing, fitting, testing and commissioning of M.S foot valve of 300mm dia fabricated out of M.S plate, square bars etc by required mechanical operations viz., cutting, bending, tapering, shaping, welding and finishing.Body: 400mm dia fabricated out of M.S plate of thickness not less than 6.3mmFlap/Weight plate: fabricated out of M.S plate of thickness 12mm along with leather washer/ rubber highly water resistant and M.S bottom disc plate complete with proper fitting arrangement.Hinge: fabricated out of M.S plate of thickness not less than 16mm with required hinge pin and rocker arm/lever arrangement.Seat: fabricated out of square bar not less than 20mm thick with proper finishing and buffing.Strainer: fabricated out of 10mm thick square bars complete.Top flange: 300mm dia not less than 20mm thickBottom flanges/ plate: not less than 16mm thick (02 No.).Coating: The foot valve body should be completely coated with anti-corrosive paint.Warranty: One year.The foot valve should be complete leak proof. The equipment should be installed and tested at site complete. The job also includes providing and fitting of nut bolts of 3kgs of size 20mm ×100mm along with 4mm thick NBR gasket of 300 mm dia (02 No.). |
| 14 | LT Distribution PanelFabrication providing, fitting, testing and commissioning of Modular Control panel of appropriate size fabricated out of 16 SWG sheet having required openings/vents and protection class: IP 54. The panel shall be fabricated out of CRCA sheets and shall be free standing, floor mounted on M.S stand (height of stand not less than 450mm), for indoor use with front hinged doors, removable bottom glands for incoming and outgoing cables, three phase aluminium bus bars complete with connections, internally wired for operation on 3 Phase AC supply 415±10% and frequency 50±3 Hz duly powder coated. The details and specifications are as under: -The Main components of the Modular Panel include: • Incoming Feeder: One No of incoming feeder housing 1 No 4 Pole 400 A MCCB with a breaking capacity of 50 Ka with adjustable Magneto thermal overload protection with release range of 320– 400A. The MCCB shall be provided with spreaders to maintain a gap between the phases. The front of the panel shall have the following flush type Meters mounted on it.a) 01 No. 3- phase digital amperemeter with required CT coils.b) 01 set of 3 No of indicating Neon bulbs.c) 01 No. 3- phase digital Voltmeter.d) 01 No digital frequency meter.e) TPN 400 Amperes Aluminium Bus Bar arrangement of adequate sections. • Outgoing Feeder: Three No of outgoing feeders with one feeder housing 1 No 3 Pole 250 A MCCB with breaking capacity of 50 Ka and Magneto thermal overload protection with release range of 200-250A and two other feeders housing 2 No., 3 Pole 200 A MCCBs with breaking capacity of 50 Ka and Magneto thermal overload protection with release range of 160-200A. All MCCBs shall be provided with spreaders to maintain a gap between the phases. The front of each of the outgoing feeders shall have the following flush type Meters mounted on it.f) 01 No. 3- phase digital amperemeter with required CT coils.g) 01 set of 3 No of indicating Neon bulbs.h) 01 No. 3- phase digital Voltmeter.a) Aluminum Bus Bar arrangement of adequate sections. • Auxiliary Feeder: One No. Auxiliary Feeder housing 01 No 4-Pole 100Amp MCCB with breaking capacity of 36 KA and thermal release and Aluminum bus bar arrangement of adequate rating for Priming pump, Lighting, and other auxiliary requirements of the pump house. The LT Panel shall be provided with at least 02 No earthing terminals for connecting to the Main Earthing circuit and shall have complete control wiring. Make of items involved in the panel shall be: L&T/Scheneider/Siemens/Equivalent as approved in EOI of SE Mech. Circle Kashmir.The equipment shall be provided with manufacturer’s test certificate. |
| 15 | FASD Starter:Providing, fitting installation testing and commissioning of Fully Automatic Star Delta Starter 3-phase, 415V pumping unit with following specifications.a) Distribution bus bar = Electric grade Al with red, blue and yellow tapping of adequate section not less than 375sqmmRating = 300 Ampb) Contactors Contactors Make = L & T/Siemens/ Schneider Line Contactor Rating (AC3) = Not less than 225AmpsDelta Contactor Rating (AC3) = Not less than 225 AmpsStar Contactor Rating (AC3) = Not less than 140 Amps Qty= 1 No. eachSuitable gap should be maintained between the contactors.c) Thermal overload relay = of Suitable amperage. Make: L&T/Rishabh/Equivalent as approved in EOI of SE Mech. Circle Kashmir Qty: 01 No.d) Ampere Meter Size = 96 mm Sq Make = L & T/ Rishabh/Equivalent as approved in EOI of SE Mech. Circle Kashmir CT Coils = Requisite CT ratio CT Coils per meter = 03 Nos (Rishbh /L&T) /Equivalent as approved in EOI of SE Mech. Circle Kashmir Type = Digital Qty= 01 No.e) Voltmeter Qty=01 No. Size =96mmSq Range = 0-500 Volts Type= Digital Make= L&T / Rishabh/Equivalent as approved in EOI of SE Mech. Circle Kashmir f) Frequency Meter: Qty: 01 No. Size: 96sqmm Frequency: 50Hz+3% Make: L&T / Rishabh/Equivalent as approved in EOI of SE Mech. Circle Kashmirg) Auxillary wiring/ Distribution wiring: Complete with required size distributed smoothly and fitted neatly.h) Auxillary MCB: Of suitable capacity and amperage (03 No.)i) Push buttons: ON,OFF switches of red and green coloursj) Timer: Timer assembly having suitable time range of Make: L&T / Seimens/Schneiderk) Single phase preventer: 01 No. of Make: L&T/Minilac/ Siemens/Schneider.l) Housing: Cubical fabricated out of 16 SWG M.S sheet having required openings/vents for cables. The housing shall have to be cut out spaces for meters and ON,OFF buttons. The enclosure shall be of excellent fit and finish, corrosion resistant duly painted and powder coated gliding hinges for smooth and noiseless movement. Also includes providing and fitting of suitable M.S stand.The equipment shall be provided with manufacturer’s test certificate. |
| 16 | Providing, fitting, laying, testing and commissioning of XLPE insulated 1.1 KV, LT armoured 03 core 185mm2 insulated aluminium cable for interconnecting motor, stabilizer and control panel. The cable shall be as per relevant IS 7098. The job also includes the fitting of cable along the walls of the Pump house by using clamps and laid underground where ever necessary as per requirement. The job also includes providing & fitting of bimetallic thimbles (12 No.) as per required size and amperage, including crimping and termination of ends with Hydraulic tool Make: Polycab/Gloster/Havells/Equivalent as approved in EOI of SE Mech. Circle Kashmir |
| 17 | Providing, fitting, laying, testing and commissioning of 1.1KV XLPE insulated 3.5 Core Al armoured 300 mm2 power cable to be used as Main Service Line shall be as per relevant IS 7098, for connection from HT transformer up to the panel. The job also includes providing & fitting of bimetallic thimbles (08 No.). as per required size and amperage, including crimping and termination of ends with Hydraulic tool. The cable has to be fitted on the walls by required clamps. Make: Polycab/Gloster/Havells/Equivalent as approved in EOI of SE Mech. Circle Kashmir |
| 18 | Providing, fitting, installation, testing and commissioning of 150kvA voltage controller/stabilizer as per specifications below:Type of voltage controller: Manually operated copper wound, 3-phase, AC power supply multi step.Type of regulator: Double plate type with electrolytic copper contacts (300mm ×300mm).Tape changer: 8 StepsInput voltage: 180-415 volts.Output voltage: 415 + 10 % volts.Frequency: 50 + 3 C/SWindings: Electrolytic grade copper of adequate section, vacuum impregnated and Oven-dried.Insulation: Fiber glass insulations to tested parameters.Cooling: Naturally, Oil cooledTemp. Rise (Max.): 30 degree Celcius above ambientMounting: On Uni-directional wheelsCorrection rate: 30 volts per stepWave form distortion: virtually nilDuty cycle: 100% continuousEnclosure: 14 SWG MS sheet enclosure in pressed CGR Sheet powder coated with radiators.Core laminates: High grade, low eddy loss, grain oriented silicon steel laminations.Load: Three phase induction motor load.Load Amperes (continuous)Rating: 150 KVAOverload in 24-hours operation: 10% above continuous Ampere rating.The voltage stabilizer shall have T-oil level indicator gauge preferably glass type tube or otherwise visible to naked eye. The top of the container to have a display panel for housing 02 numbers Digital voltmeters (0-500V) of L&T/Rishab/Scheineder/Equivalent as approved in EOI of SE Mech. Circle Kashmir make along with 4-way selector switch and set of neon indicators of L&T make for incoming and outgoing phases (06 No.’s)Insulating media (T. oil) of 11kVA grade to be provided and filled up to top level, with dielectric strength of 5Kv at 4m air gap. The T-oil of specific grade should be provided in separate barrels and filled at site upto top level. The equipment shall be provided with manufacturer’s test certificate. |
| 19 | Illumination of pump premises by way of Providing, installation, testing and commissioning of street light 120 Watt LED (Street Light Type) on top of departmental existing pole and other required places having following specs: Input: 90-240 V 50 HzPower Factor: >0.9colour Temperature: 4K - 6.5K Beam Angle: 120˚ - 170˚ Lumens: >12000Operating Temperature: -20˚C to 60˚CQuantity: 08 NoMake: Havells/Syska/Phillips/Surya/Equivalent as approved in EOI of SE Mech. Circle KashmirThe LED lights are to be pressure die cast Aluminum housing with power coated finish and having Ingress Protection up to IP-65/66.The LED is to be properly fitted and connected to the cable. The job includes Providing and installation of Junction Box with DP 16 A MCBs to each LED light. Providing, laying and Fitting of 2-Core, 10 Sq mm XLPE, 1.1KV Armoured Aluminum Cable (135m) conforming to IS: 7098 part 1st for connecting LED lights. The job also includes necessary thimblings, crimping, taping etc. The supply has to be provided from auxiliary MCCB of distribution panel to each junction box. |
| 20 | Providing, installation, testing and commissioning of fully automatic dry type 9A CVT. Make: V guard/Equivalent as approved in EOI of SE Mech. Circle Kashmir |
| 21 | Providing, fabrication and fitting of 2 No. 25mm×1000mm L &J type bolts and 1 No. clamp completely fabricated out of 80mm ×8mm×1200mm flat iron. The bolts shall be grouted in cement concrete saddle blocks with proper alignment as per site requirement. |
| 22 | Providing of solar lantern dual charger with solar plate and adapter for lighting purpose. Make: Indus/Tata/Equivalent as approved in EOI of SE Mech. Circle Kashmir |
| 23 | Providing, laying and fixing of shock proof matts with adhesive bonds material on the floor of pump house covering area around the electromechanical machinery for safeguarding the life of workmen. The matts shall be fixed after cleaning the surface. The mattes shall be as per IS 15652:2006 and shall have the following specifications:Composition: Rubber synthetic matts for electrical purposeThickness: 2mmWidth: 1mThe rubber mats shall be accepted with the manufacturer’s test certificate. |
| 24 | Supply, installation of 6 kg CO2 type fire extinguisher manufactured as per IS: 15683of 2006 with IS mark and comply with DGMS (Approval). The co2 extinguisher should be suitable for class B & C fire and also for fire involving electrical equipment. The cylinder used for fire extinguisher shall be approved by petroleum and explosive safety organization (PESO) as per gas cylinder rules 2004 and as per IS: 7285 of 2004. The body should be made of seamless steel (manganese) confirming to IS: 7285 with IS mark and should be provided with squeeze grip nozzle and should be filled with co2 confirming to IS: 15222 of 2002 with certificate. The extinguisher shall be provided with manufactures test certificate and hydraulic test certificate by BIS from PESO. |
| 25 | Illumination of pump house by way of providing and fitting of five No. of lighting points inside pump house and washroom, Two No. of heating points. The lighting point comprises of providing and fitting of switch socket, angle holders, LED bulbs of 14W each 05 no., distribution wire of 1.5 sqmm copper multistranded laid through PVC channels fixed on walls by way of required nails, rawal plugs and other required accessories. The Two No.s of heating points shall comprise of S-S combine 3-way 2 Nos 16A, distribution wire 4 sqmm copper multistranded distributed through PVC channels neatly and smoothly. |
| 26 | Earth work in excavation by manual means in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed:1 meter from cutting edge :All kinds of soils. |
| 27 | Close timbering in trenches including strutting, shoring and packing cavities (wherever required) complete. (Measurements to be taken of the face area timbered). Depth not exceeding 1.5 m. |
| 28 | Providing and laying dry stone soling, including cost of stones. |
| 29 | Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering. All work upto plinth level with: 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) |
| 30 | Providing and laying in position specified grade of reinforced cement concrete including curing but excluding the cost of centering, shuttering, finishing and reinforcement. All works upto plinth level, 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) |
| 31 | Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering. All work upto plinth level with: 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) |
| 32 | Centering and shuttering including strutting, propping etc. and removal of form for: Foundations, footings, bases of columns etc. for mass concrete. |
| 33 | 12mm Cement plaster of mix: 1 : 4 ( 1 cement : 4 fine sand) |
| 34 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 35 | Structural steel work in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. Welded |
| 36 | Providing corrugated G. S. sheet roofing including vertical/curved surface fixed with polymer coated J or L hooks, bolts and nuts 8mm diameter with bitumen and G.I limpet washers or with G.I. limpet washers filled with white lead, including a coat of approved steel primer and two coats of approved paint on overlapping of sheets complete (upto any pitch in horizontal/vertical or curved surface)excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. 1.00 mm thick with zinc coating not less than 275 gram/m2 |
| 37 | Hiring of LNT Machine for carry out/execution/resection of sump and intake channel as directed by Engineer incharge. |
| 38 | Carriage of materials by mech. Transport from different sources to dumping site including loading & unloading. |
| 39 | Stone Soling Avg Lead 21 Km |
| 40 | Stone Aggregates 40mm size for an average lead of 20 Kms |
| 41 | Stone Aggregates 20mm size for an average lead of 20 Kms |
| 42 | Sand for an average lead of 20 Kms |
| 43 | Cement avg lead of 10 Kms. |
| 44 | Steel R/f for RCC work/CGI For avg lead 12 Km |
| 45 | Carriage of materials by way of head load an Avg. lead 100 Mtr. |
| 46 | Stone Soling |
| 47 | Stone Aggregates 40mm size. |
| 48 | Stone Aggregates 20mm size. |
| 49 | Sand. |
| 50 | Cement/Steel |
| 51 | Steel |
| 52 | Structural Steel/CGI Sheet |
| 53 | Providing, fabricating, supplying and fixing an engraved black granite signboard of size 900 x 600 mm, made of polished black granite stone alab of thickness 16-18 mm, duly machine-engraved with approved inscriptions indicating the name of work and other particulars, securely enclosed in a 15 structural steel frame, including fabrication, welding, finishing, one coat of approved anti-corrosive primer and two coats of enamel paint, and fixing the complete assembly by by embedding the steel frame legs in cement concrete pedestals, including excavation, concreting, alignment, curing and all incidental works, complete in all respects as directed by the Engineer-in-Charge Please Enable Macros to View BoQ information |