| 1 | Excavating in trenches n exc 1.5 mtr wide and n exc 1.5m in depth , for foundation ,etc or for shafts, wells , cesspits, main holes etc.n exc 10 sqm on plan and n exc 1.5 mtr depth and getting out on soft/ lose soil and added additional 1.5 m or part thereof in depth beyond the first 1.5 mtr. |
| 2 | Returning, filling in, including spreading , levelling , watering and well ramming in layers not exc 25cm of any soil. |
| 3 | Removing excavated materials(soils) n exc 50m and depositing where directed at a level n exc 1.5m above the starting point. |
| 4 | Supply and spreading of dry river bed sand for cushioning and covering the under ground cable in trenches all as specified and as directed(Note : Punned down thickness shall be measured) |
| 5 | Supply, laying and replcement of PCC covers, class LV type-1 flat size 250x150x40mm, ISI marked complete all as specified and directed. |
| 6 | Supply & lay HDPE pipe 65mm bore for laying of LT cables etc complete with all accessores all as specified and directed |
| 7 | Supply and Laying in trenches or drawn through pipe or fixed on wall / poles , LT UG cable 1100 Volts, heavy duty XLPE insulated, screened, PVC bedded, galvanised steel strip or wired armoured with aluminium conductor after removing old one of following size:- |
| 8 | (a) 10 sqmm 4 core |
| 9 | (b ) 25 Sqmm 4 core |
| 10 | (c) 50 Sqmm 31/2 core |
| 11 | (d) 70 Sqmm 31/2 core |
| 12 | (f) 95 Sqmm 31/2 core |
| 13 | (g)120 Sqmm 31/2 core |
| 14 | Material and labour for making good the damaged Tar Road by using additional stone metal, PCC etc |
| 15 | Supply and Fixing bus bar enclosure 800 mm x 600 mm x 200 mm made out of 3.15 mm thick CRCA steel duly powder coated and including 200 amp, 25 kA MCCB 4 pole, thermal magnetic based fitted in bus bar enclosure using 200 Amp rated bus bar, 25x10mm aluminium and RYB indication lamps duly protected by 2A SP MCB outdoor type welded to suitable size MS angle iron frame and embedded in PCC 1:2:4 type B-1 ; Complete all as specified and as directed by the Engineer-in-charge.Note - Height of the enclouser from ground level 0.5 meter . |
| 16 | Supply and Fixing bus bar enclosure 800 mm x 600 mm x 200 mm made out of 3.15 mm thick CRCA steel duly powder coated and including100 amp, 25 kA MCCB 4 pole, thermal magnetic based fitted in bus bar enclosure using 250 Amp rated bus bar, 25x10mm aluminium and RYB indication lamps duly protected by 2A SP MCB outdoor type welded to suitable size MS angle iron frame and embedded in PCC 1:2:4 type B-1 ; Complete all as specified and as directed by the Engineer-in-charge.Note - Height of the enclouser from ground level 0.5 meter . |
| 17 | Material and labour for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6.0 mm thick, buried vertically in ground (Each pit not less than 2.25 mtrs deep below normal ground level with top edge of plate not less than 1.50 M below normal ground level) connected to GI strip 32 x 6 mm , by means of bolts, nuts, and check nuts and washers etc encased in GI protection pipe 40 mm dia light grade pipe for protection of GI earth strip both to be provided to the extet of 7.5 meters, all as shown on electrical plate No 3 of MES SSR - 2004 Part - I, GI protection pipe buried in ground, laid under floors / plinths or mixed on walls / pole etc or concealed in walls etc; with provision of mixture of charcoal dust and common salt packed upto minimum 150 mm all around the earth plate, including PCC 1:2:4 type B-1 earth pit with M.S angle iron frame, cast iron cover with locking arrangement, with GI 20 mm dia medium grade pipe and MS funnel with wire mesh for watering arrangement, including necessary excavation and earth work in any type of soil / strata and testing on completion complete all as specified and directed.Note:- i) Cost of GI strip 32 x 6 mm and protection pipe 40 mm dia is deemmed to be included in rate quoted ii) Excavation and returning filling of Soil any type is deemed to be included in rates. |
| 18 | Material and labour for dismantling of OH conductor of any size complete all as specified and as directed . |
| 19 | Material and Labour for dismantling of cross arms complete all as specified and as directed. |
| 20 | Material and Labour for dismantling of insulators complete all as specified and as directed . |
| 21 | Material and labour cement conctere 1:4:8 type D-2 (using 40mm grade aggregate) as in foundation of pole and similar work complete all as specified and directed. |
| 22 | Material and labour for PCC (1:3:6) type C-2, (using40mm graded stone aggregate) as in coping of pole and similar work complete all as specified and directed. |
| 23 | Supply ,Installing, test and commissioning LT panel board, factory made, out door, cubical type , vermin proof, dust proof, cubical type, made out of 3.15 mm thick CRCA sheet and inner sheet of 2.0mm thick and bottom angle iron frame of size 50x50x5mm 90 cm long and size suitable to accommodate the following accessories, with insulated alluminium busbar 500 amps capacity , 3 phase , 4 wire system, both sides openable (front and back) with locking arrangement , duly powder coated internally and externally with minimum seven tank process traetment connecting with cable with lugs including internal wiring with copper cables of suitable size using lugs comprising the following accessories all as directed.(a)MCCB 315 Amp,415 V four pole with thermal magnetic setting with Breaking Cap 36 KA-01 No (Incoming)(b) MCCB 200 Amps 415V 04 pole with thermal magnetic setting breaking cap 25KA - 06 Nos (For Out Going)(c) MCCB 100 Amps 415V 04 pole with thermal magnetic setting breaking cap 25KA - 03 Nos (For Out Going)(d) Volt Meter (digital Type (0 -500 Volts)-01 No(e ) Ammeter (digital type) with CTs 0-300Amps)-01 No(f) Phase indication lamps LED type with holder-01 Set(Set of Three)Notes:- 1. The Panel Should be CPRI approved 2. The rates Quoted shall include for earth work and excavation for angle iron frame for foundation of panel board up to 0.45 m below GL in any type of soil and PCC 1:4:8 type D2 filling in foundation. The ground clearance of panel board shall be 0.45 M from GL to the bottom of panel board.3. Contractor shall submitted the drawing of LT panel for approval of GE. |
| 24 | Supply ,Installing, test and commissioning LT panel board, factory made, out door, cubical type , vermin proof, dust proof, cubical type, made out of 3.15 mm thick CRCA sheet and inner sheet of 2.0mm thick and bottom angle iron frame of size 50x50x5mm 90 cm long and size suitable to accommodate the following accessories, with insulated alluminium busbar 400 amps capacity , 3 phase , 4 wire system, both sides openable (front and back) with locking arrangement , duly powder coated internally and externally with minimum seven tank process traetment connecting with cable with lugs including internal wiring with copper cables of suitable size using lugs comprising the following accessories all as directed.(a)MCCB 200 Amp,415 V four pole with thermal magnetic setting with Breaking Cap 25 KA-01 No (Incoming)(b) MCCB 160 Amps 415V 04 pole with thermal magnetic setting breaking cap 25KA - 03 Nos (For Out Going)(c) MCCB 100 Amps 415V 04 pole with thermal magnetic setting breaking cap 16KA - 01 Nos (For Out Going)(d) MCCB 63 Amps 415V 04 pole with thermal magnetic setting breaking cap 16KA - 02 Nos (For Out Going)(d) Volt Meter (digital Type (0 -500 Volts)-01 No(e ) Ammeter (digital type) with CTs 0-300Amps)-01 No(f) Phase indication lamps LED type with holder-01 Set(Set of Three)Notes:- 1. The Panel Should be CPRI approved 2. The rates Quoted shall include for earth work and excavation for angle iron frame for foundation of panel board up to 0.45 m below GL in any type of soil and PCC 1:4:8 type D2 filling in foundation. The ground clearance of panel board shall be 0.45 M from GL to the bottom of panel board.3. Contractor shall submitted the drawing of LT panel for approval of GE. |
| 25 | Supply ,Installing, test and commissioning LT panel board, factory made, out door, cubical type , vermin proof, dust proof, cubical type, made out of 3.15 mm thick CRCA sheet and inner sheet of 2.0mm thick and bottom angle iron frame of size 50x50x5mm 90 cm long and size suitable to accommodate the following accessories, with insulated alluminium busbar 400 amps capacity , 3 phase , 4 wire system, both sides openable (front and back) with locking arrangement , duly powder coated internally and externally with minimum seven tank process traetment connecting with cable with lugs including internal wiring with copper cables of suitable size using lugs comprising the following accessories all as directed.(a)MCCB 200 Amp,415 V four pole with thermal magnetic setting with Breaking Cap 25 KA-01 No (Incoming)(b) MCCB 160 Amps 415V 04 pole with thermal magnetic setting breaking cap 25KA - 02 Nos (For Out Going)(c) MCCB 63 Amps 415V 04 pole with thermal magnetic setting breaking cap 16KA - 04 Nos (For Out Going)(d) Volt Meter (digital Type (0 -500 Volts)-01 No(e ) Ammeter (digital type) with CTs 0-300Amps)-01 No(f) Phase indication lamps LED type with holder-01 Set(Set of Three)Notes:- 1. The Panel Should be CPRI approved 2. The rates Quoted shall include for earth work and excavation for angle iron frame for foundation of panel board up to 0.45 m below GL in any type of soil and PCC 1:4:8 type D2 filling in foundation. The ground clearance of panel board shall be 0.45 M from GL to the bottom of panel board.3. Contractor shall submitted the drawing of LT panel for approval of GE. |
| 26 | Supply and fixing termooplastic polycarbonate cable junciton box with polycarbonate glands of size 300mm x 200mm x 105mm hinged door tyoe with heavy duty connector/terminal block 100 amps 4 way, shock proof safe IP-55 wather proof , Tamper proof, rust, dust and water proof, internally embedded gasket with provision for cable entry through gland alongwith MS clamps and mounting brackets aas required at site with and including MCB SP 6 Amps 10 KA aluminium Loop in box with Heavy duty 4 way connectoer and MCB SP 6 Amps B series -01 no. incl clamps made of GI flat with not bolts etc |
| 27 | Supplying and fixing 1100 volts grade heavy duty cable size 6 Sqmm 2 core stranded conductor PVC insulated aluminium conductor served with inner sheathing of PVCtape and overall PVC sheathed in service connections as specified and directed |
| 28 | Supply and fixing LED street light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminium housing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multipel optics complete with IP 65/66 protection complete all as specified and directed |
| 29 | Taking down carefully Distribution board 4/8/12 way SPN including fixture and fittings etc complete all as specified and directed |
| 30 | Taking down carefull Distribution board VTPN/Energy meter pannel including fixture and fittings etc complete all as specified and directed |
| 31 | Supply and fixing in replacment for vertical sheet steel metal enclouser distribution boards, double door factory made , 3 phase 415 volts 4 way with 200 Amps rating copper bus bar and PVC insulated copper wire of suitable size from the MCCB to the out going circuits one incoming MCCB and suitable outgoing MCB's circuits comprising of 3 phase 4 sire of suitable rating complete all as specified and directed including following accessories :- MCCB 100 Amps ,25 KA,TP,415 VOLTS,50 Hz=01 Nos |
| 32 | Supply and fixing in replacment for vertical sheet steel metal enclouser distribution boards, double door factory made , 3 phase 415 volts 4 way with 200 Amps rating copper bus bar and PVC insulated copper wire of suitable size from the MCCB to the out going circuits one incoming MCCB and suitable outgoing MCB's circuits comprising of 3 phase 4 sire of suitable rating complete all as specified and directed including following accessories :- MCCB 63 Amps ,25 KA,TP,415 VOLTS,50 Hz=01 Nos |
| 33 | Supply and fixing in replacement Distribution Board double Door made out of CRCA mild steel sheet surface with insulated material like polyester or with epoxy powder coating surface mounting SPN 12 way , 240 volts with bus bar rating 200 Amps, dust and vermin proof suitable for incorporation of MCB’s and isolators etc complete all as specified. (Note : cost of removing old wooden box and making good of surface as original by brick work, plastering, whitewash/colour/distemper etc is included in quated rate) |
| 34 | Supply and fixing in replacement Distribution Board double Door made out of CRCA mild steel sheet surface with insulated material like polyester or with epoxy powder coating surface mounting SPN 8 way , 240 volts with bus bar rating 200 Amps, dust and vermin proof suitable for incorporation of MCB’s and isolators etc complete all as specified. (Note : cost of removing old wooden box and making good of surface as original by brick work, plastering, whitewash/colour/distemper etc is included in quated rate) |
| 35 | Supply and fixing in replacement Distribution Board double Door made out of CRCA mild steel sheet surface with insulated material like polyester or with epoxy powder coating surface mounting SPN 4 way , 240 volts with bus bar rating 200 Amps, dust and vermin proof suitable for incorporation of MCB’s and isolators etc complete all as specified. (Note : cost of removing old wooden box and making good of surface as original by brick work, plastering, whitewash/colour/distemper etc is included in quated rate) |
| 36 | Supply, Installation, testing and commissioning, in replacement powder coated, factory made, Panel, Indoortype, conforming to IP 52 protection, size 1.0 x 0.90 x 0.60 m, made of robust steel sheetconstruction, 3.00mm thick with counter sunk holes, at bottom for base mounting brackets and sheet steel gland plates for cable entry, formed gasket around doors with provision of lock insert,earthing straps, wiring plan pockets, door stay, angle iron frame and grouted in suitable size ofplatform made of PCC 1:2:4, type-1, panel prewired with suitable size of PVC insulated copperconductor cable, multi stranded,housed with the following accessories: (a) MCCB 4 Pole, 100 Amp, 25 KA with spreader terminals and adjustable thermal setting -01 No(Incoming)(b)MCB DP 63 Amp-04 Nos(c) Aluminium Bus bars of rating, 200A-1 Set(d) PVC box for fixing electronic energy meter of suitable size - 04 Nos |
| 37 | Supply and fixing in replacement MCCB 415 Vlt, 25 KA, 4 pole 63 Amp completed all as specified and directed. |
| 38 | Supply and fixing in replacement MCCB 415 Vlt, 25 KA, 4 pole 100 Amp completed all as specified and directed |
| 39 | Supply and fixing in replacement MCCB 415 Vlt, 25 KA, 4 pole 160 Amp completed all as specified and directed |
| 40 | Supply and fixing in replacement of MCB single pole, 240 volts, 6 to 32 Ampere, rupturing capacity 10 KA, ‘C’ curve type complete all as specified and directed. |
| 41 | Supply and fixing in replacement MCB double pole, 240 volts, 40 to 63 Ampere, rupturing capacity 10 KA, ‘C’ curve type complete all as specified and directed. |
| 42 | Supply and fixing in replacement, Sub main wiring with two single core 10 sqmm (nominal area stranded copper conductor FRLS PVC insulated and unsheathed cable drawn in existing non metalic PVC rigid conduit medium grade of suitable size with all standared fitting, including one run of continuous PVC insulated standed copper conductor PVC insulated stranded copper conductor FRLS cable 6 sqmm (nominal area for earth continuty, including taking out and removal of old sub main wiring, complete all as specified and directed. Note:- 1 Two runs of 10 sqmm main cable one run of 10 sqmm for earth cable shall be measured as one unit one running metre. |
| 43 | Supply and fixing ing in replacement, Sub main wiring with two single core 10 sqmm (nominal area stranded copper conductor FRLS PVC insulated and unsheathed cable drawn in and including non metalic PVC rigid conduit medium grade of suitable size with all standared fitting , on surface including one run of continuous PVC insulated standed copper conductor PVC insulated stranded copper conductor FRLS cable 10 sqmm (nominal area for earth continuty. including taking out and removal of old sub main wiring and making good disturbed surface as per exisiting as required, complete all as specified and directedNote:- 1 Two runs of 10 sqmm main cable one run of 10 sqmm for earth cable & conduit shall be measured as one unit one running metre. |
| 44 | Supply and fixing in replacement, Sub main wiring with two single core 6 sqmm (nominal area stranded copper conductor FRLS PVC insulated and unsheathed cable drawn in existing non metalic PVC rigid conduit medium grade of suitable size with all standared fitting, including one run of continuous PVC insulated standed copper conductor PVC insulated stranded copper conductor FRLS cable 6 sqmm (nominal area for earth continuty, including taking out and removal of old sub main wiring, complete all as specified and directed. Note:- 1 Two runs of 6 sqmm main cable one run of 6 sqmm for earth cable shall be measured as one unit one running metre. |
| 45 | Supply and fixing ing in replacement, Sub main wiring with two single core 6 sqmm (nominal area stranded copper conductor FRLS PVC insulated and unsheathed cable drawn in and including non metalic PVC rigid conduit medium grade of suitable size with all standared fitting , on surface including one run of continuous PVC insulated standed copper conductor PVC insulated stranded copper conductor FRLS cable 6 sqmm (nominal area for earth continuty. including taking out and removal of old sub main wiring and making good disturbed surface as per exisiting as required, complete all as specified and directedNote:- 1 Two runs of 6 sqmm main cable one run of 6 sqmm for earth cable & conduit shall be measured as one unit one running metre. |
| 46 | Supply and fixing ing in replacement, Sub main wiring with two single core 4 sqmm (nominal area stranded copper conductor on surface FRLS PVC insulated and unsheathed cable drawn in existing non metalic PVC rigid conduit medium grade of suitable size with all standared fitting , including one run of continuous PVC insulated standed copper conductor PVC insulated stranded copper conductor FRLS cable 4 sqmm (nominal area for earth continuty, including taking out and removal of old sub main wiring including making good disturbed surface as required as per existing, complete all as specified and directed.Note:- 1 Two runs of 4 sqmm main cable one run of 4 sqmm for earth cable shall be measured as one unit/ one running metre. |
| 47 | Supply and fixing ing in replacement, Sub main wiring with two single core 4 sqmm (nominal area stranded copper conductor on surface FRLS PVC insulated and unsheathed cable drawn in and including non metalic PVC rigid conduit medium grade of suitable size with all standared fitting, on surface, including one run of continuous PVC insulated standed copper conductor PVC insulated stranded copper conductor FRLS cable 4 sqmm (nominal area for earth continuty, including taking out and removal of old sub main wiring including making good disturbed surface as required as per existing, complete all as specified and directed. |
| 48 | Material and labour for in replacement Earthing complete with galvanized steel earth plate electrods of size 60cmx60cmx6mm thick burried directly in ground vertically (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level connected to galvanized iron or steel earth wire 4 mm dia by means of bolts nuts and GI washers of Galvanised iron protected by steel pipe 15 mm(light grade) all as shown in electrical plate No.03 of SSR Part-I and connecting to earthing test point (earth test point to be provided at 5 mtr distance from earth pit) and testing on completion including necessary excavation and earth work. The rate also include charcoal dust and salt in alternate layers 25 mm dia light grade GI pipe, funnel, wire mesh, Concrete 1:3:6 type C-1 for pit and RCC pit cover. The extra cost of the watering pipe, bends, elbows shall be included in the unit rate. Note : RCC pit cover shall be precast of RCC 1:2:4 type B-1 80mm thick reinforced with XPM weighing not less than 4 Kg/Sqm, complete all as specified and directed. Please Enable Macros to View BoQ information |