| 1 | Labour only for restreching including binding of sagged/ loose ACSR conductor of any types such as squirrel /weasel /ferret etc fixed on LT poles at different location including tightening of cross arms, trimming of tree branches to clear the ACSR.complete all as Specified and directed. |
| 2 | Shifting of LT Pole from One Place to Other Place distance Under 1 KM both Pole,existing Pole Area Refilling and Fixing of Pole at New Location, including earth work and PCC complete via Norms and Directed by Engg-in Charge. |
| 3 | Taking out Existing Street / security lights any type and size and Supply and fixing LED street light fitting 90 watts , 140 V - 270 V , 50Hz AC outdoor type in replacement with high pressure die cast alluminium housing with top opening service and heat resistant complete with driver, lamp bracket , with impact and corrosion resistant including thermal management in multiple optics complete with IP 66 protection , Light source High efficiency long life LED package modules on MCPCB with LED lumen efficacy of >100 lumen per watt, Electronic Driver Powered by Built-in, isolated electronic LED driver (SMPS based constant current supply) with lower THD, Output Open / Short Circuit protection, Phase to Phase protection, Over Voltage protection, 10 kV surge protection, Surge Voltage protection & other safety tests as per IS 15885 Part-2/Sec13 completed to driver with superior finish with top maintainable driver compartment complete with the fittings arrangement for fixing on existing bracket etc complete all as Specified and directed. (Note : LM 79 and 80 test certificate submitted before executing of the work) |
| 4 | Taking out Existing Street / security lights any type and size and Supply and fixing LED street light fitting 70/72 watts , 140 V - 270 V , 50Hz AC outdoor type in replacement with high pressure die cast alluminium housing with top opening service and heat resistant complete with driver, lamp bracket , with impact and corrosion resistant including thermal management in multiple optics complete with IP 66 protection , Light source High efficiency long life LED package modules on MCPCB with LED lumen efficacy of >100 lumen per watt, Electronic Driver Powered by Built-in, isolated electronic LED driver (SMPS based constant current supply) with lower THD, Output Open / Short Circuit protection, Phase to Phase protection, Over Voltage protection, 10 kV surge protection, Surge Voltage protection & other safety tests as per IS 15885 Part-2/Sec13 completed to driver with superior finish with top maintainable driver compartment complete with the fittings arrangement for fixing on existing bracket etc complete all as Specified and directed. (Note : LM 79 and 80 test certificate submitted before executing of the work) |
| 5 | Taking out Existing Street / security lights any type and size and Supply and fixing LED street light fitting 60 watts , 140 V - 270 V , 50Hz AC outdoor type in replacement with high pressure die cast alluminium housing with top opening service and heat resistant complete with driver, lamp bracket , with impact and corrosion resistant including thermal management in multiple optics complete with IP 66 protection , Light source High efficiency long life LED package modules on MCPCB with LED lumen efficacy of >100 lumen per watt, Electronic Driver Powered by Built-in, isolated electronic LED driver (SMPS based constant current supply) with lower THD, Output Open / Short Circuit protection, Phase to Phase protection, Over Voltage protection, 10 kV surge protection, Surge Voltage protection & other safety tests as per IS 15885 Part-2/Sec13 completed to driver with superior finish with top maintainable driver compartment complete with the fittings arrangement for fixing on existing bracket etc complete all as Specified and directed. (Note : LM 79 and 80 test certificate submitted before executing of the work) |
| 6 | Taking out Existing Flood lights any type and size and Supply and fixing LED flood light fitting 150 watts , 140 V - 270 V , 50Hz AC outdoor type in replacement with high pressure die cast alluminium housing with top opening service and heat resistant complete with driver, lamp bracket , with impact and corrosion resistant including thermal management in multiple optics complete with IP 66 protection , Light source High efficiency long life LED package modules on MCPCB with LED lumen efficacy of >100 lumen per watt, Electronic Driver Powered by Built-in, isolated electronic LED driver (SMPS based constant current supply) with lower THD, Output Open / Short Circuit protection, Phase to Phase protection, Over Voltage protection, 10 kV surge protection, Surge Voltage protection & other safety tests as per IS 15885 Part-2/Sec13 completed to driver with superior finish with top maintainable driver compartment complete with the fittings with two pairs of necessary nuts and bolts with washers with suitable packing arrangement to fixing complete all as Specified and directed. (Note : LM 79 and 80 test certificate submitted before executing of the work) |
| 7 | Taking out Existing Flood lights any type and size and Supply and fixing LED flood light fitting 200 watts , 140 V - 270 V , 50Hz AC outdoor type in replacement with high pressure die cast alluminium housing with top opening service and heat resistant complete with driver, lamp bracket , with impact and corrosion resistant including thermal management in multiple optics complete with IP 66 protection , Light source High efficiency long life LED package modules on MCPCB with LED lumen efficacy of >100 lumen per watt, Electronic Driver Powered by Built-in, isolated electronic LED driver (SMPS based constant current supply) with lower THD, Output Open / Short Circuit protection, Phase to Phase protection, Over Voltage protection, 10 kV surge protection, Surge Voltage protection & other safety tests as per IS 15885 Part-2/Sec13 completed to driver with superior finish with top maintainable driver compartment complete with the fittings with two pairs of necessary nuts and bolts with washers with suitable packing arrangement to fixing complete all as Specified and directed (Note : LM 79 and 80 test certificate submitted before executing of the work) |
| 8 | Taking out Existing Street / security lights bracket any type and size and Supply and fixing of mounting bracket made of 40 mm bore (or higher size to suit the opening of fitting) light grade GI pipe of approx. 1.5 mtr length bent to shape of 1 mtr and fixed to pole with FI 40mm x 6mm clamps, 2 nos and suitable size necessary nuts & bolts ,including Bracket complete set painting of two coat red oxide and aluminium painted fittings for Street lights with swaged tubular/ PCC pole connected complete all as Specified and directed . |
| 9 | Supply and fixing in replacement of LED post top gate light fitting, 25 Watt 230 V AC decorative type with high pressure die cast aluminum hosing 40 mm dia with driver, (with burning hrs 50000) complete including taking down old light fitting all as specified and directed. MAKE: Havells/Bajaj/Philips/Crompton |
| 10 | Supply & Laying PVC insulated,Un armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 10 sqmm 2 Core complete all as specified and as directed. |
| 11 | Supply & Laying PVC insulated,Un armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 06 sqmm 2 Core complete all as specified and as directed. |
| 12 | Supply & Laying PVC insulated,Un armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 04 sqmm 2 Core complete all as specified and as directed. |
| 13 | Taking out old unsv existing OH line /UG cable any type and Supply, laying, jointing, testing and commissioning LT underground cables 10 sqmm x 4core, 1100 volts grade, XLPE insulated and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, IS-7098 (marked, laid in trenches / ducts / fixed on poles / laid under roads / paths / drain / culverts or encased in GI pipe complete all as specified and directed. (Note;- Rate quoted includes terminal Lugs / road cutting/ floor cutting/ Inter locking floor and making good damaged portion matching with existing surface with all existing finishes.) complete all as specified and directed. |
| 14 | All as per item No 13.00 but of size 16 sqmm 4 core complete all as Specified and directed. |
| 15 | All as per item No 13.00 but of size 25 sqmm 4 core complete all as Specified and directed. |
| 16 | Excavation in trenches not exceeding 1.5 m wide and exceeding 3 m in depth and getting out in Soft/Loose soil including trimming sides and bottom of trenches complete all as Specified and directed . |
| 17 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out in Soft/Loose soil including trimming sides and bottom of trenches complete all as Specified and directed . |
| 18 | Returning, filling-in, including spreading, watering and well ramming in layers not exceeding 25 cm thick each, in soft /loose soil complete all as Specified and directed . |
| 19 | Removing excavated surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as Specified and directed . |
| 20 | Material and labour for river washed and screened, dry sand for filling in trenches below 8 cm laid before laying of cable and 15 cm sand cable laid after laying the cable and around underground cables for cushioning of cables complete all as specified and directed. |
| 21 | M & L Bricks for protection cover to under ground cable (with standard size fly ash bricks) with width equal to length of brick laid dry and flat abutting each other with gaps between adjacent brick not exceeding 10mm complete all as Specified and directed . |
| 22 | Supply and laying galvanised steel tubing 40mm bore , light grade, IS-1239 marked with all fittings (IS marked) and laid in trenches / under roads / in drains / fixed to poles/walls incl taking out the existing same pipe ( incl required size flat iron clamp bolts, nuts and washers ) complete all as Specified and directed . |
| 23 | All as per ser item No.22 but of size 50 mm bore complete all as Specified and directed. |
| 24 | M&L for auguring of hole suitable for passing 40mm to 50 mm bore pipe in true horizontal position under road, PCC paths etc., by means of mechanical ring/ auger after doing ultrasound to prevent any damage to existing cables pipe line specified and directed coming in the route not exceeding 1.5 m in depth below existing surface level of road and not excd 30M in length complete all as specified. Complete all as specified and directed.Note: Pipe shall be measured and paid separately under appropriate items and any damage to existing cables of any type shall be made good by the Bidder without any extra cost to department. |
| 25 | M&L for faulty cable loop digging by drawing/taking out cable loop of any size or description cable with preparation of cable end for connection with bus bar of cable junction box duly crimping with aluminium lugs and connecting with galvanised iron nuts, bolts & washers including relaying of cable loops by providing necessary excavation and earth work any soil, protection of cable by retrieved bricks and providing new sand cushioning complete all as Specified and directed . |
| 26 | Taking out old unsv PCC Pole and Supplying, transporting to site, erecting, and fixing in position, steel tubular swaged and welded poles of Overall height 9 metres, type 410 SP-31, IS-2713 marked, with mild steel base plate (fillet welded to poles), pole cap / finial taper plug, bolts, nuts, washers etc, including painting on the outside with two coats of aluminium paint over a coat of red oxide primer on exposed surfaces and black bituminous paint on steel surface embedded in concrete and painting 05 nos band /strips with fluorescent , PO box red synthetic enamel paint ( 30 cm wide each) at a distance of 30 cm from plinth block of colour black and Green with numbering of poles, including the existing service line/ Channel/ street lights Brackets with street lights /JBs complete allied items shifting the new pole complete all as specified and directed .(Note:- Poles shall be swaged and welded at manufacturer’s factory and not at site. The inner surface shall be factory painted) |
| 27 | M&L for PCC (1:4:8)type D2 with 40 mm graded stone aggregate in foundation(below pole ) complete all as Specified and directed . |
| 28 | M&L for cement concrete (1:3:6) type C-2 using 40mm graded stone aggregate for foundation of pole etc. (around the poles in pit) complete all as Specified and directed . |
| 29 | M&L for PCC (1:2:4) type B-1 using 20 mm graded stone aggregate for coping of poles including necessary form work, fair finishing to exposed surfaces using extra cement complete all as Specified and directed . |
| 30 | Taking out existing unsv junction box any type and size and S&F pole mounting type junction box factory made of minimum size 290 x200x100mm of FRP sheet duly powder coated with front openable hinged door , locking arrangements, with 4 Nos aluminium bus bars 40 Amps rating mounted on SMC /porcelain insulator, cable glands and lugs consisting DIN type rails for fixing MCB SP 6/10 Amps, 10 kA suitable for domestic loading , -01 no. including mild steel flat iron clamp and and supporting flat Iron made out of 40x4mm FI, nuts, bolts and washers duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed. |
| 31 | Taking out existing unsv conduit any type and size and Supply & fixing Unplasticised PVC pipes of prssure rating 10Kgf/cmSq 25 mm bore and 3mm thick complete fixed on pole using suitable clamps nuts & bolts (not less than 03 Nos) complete all as specified and as directed |
| 32 | Taking out existing unsv connection wire any type and size and S&F for one runs of three core 1.5 Sqmm x 3 core (nominal area) PVC insulated and PVC sheathed multi stranded unarmed copper conductor cable LT 1100 volt grade Confirming to IS : 7098 drawn through pipe/ pole for connecting to street light and pole JB with lugs and all complete as specified and as directed. |
| 33 | M&L for preparation of old painted surfaces steel tubular swaged poles / Rails/Girder poles of LT over head line ( Except embedded portion) , 9 M long including all MS work mounted on pole , earth protection & water pipe ( if exists) including bracket(s), single or double of size 1.5m x 40/50 mm pipe ) and providing one coat of aluminium paint and providing 05 Nos bands/ straps with Two coats of retro reflective paint ( Black, Green and 30 cm wide each) from top of plinth block and numbering of poles with white reflective paint (50mm wide and 100mm hight letters) including numbering of poles encircling the letters or figures complete all as specified and directed. |
| 34 | M & L Painting of two color strip up to 1.5 mtr height on PCC/steel Pole including junction box & Marking of Pole No by Trained Painter etc complete as specified and directed by engineer-in-charge. |
| 35 | Trimming/ cutting/ prunning for branches of tree touching to LT/HT OH lines not exceeding 30 cm girth , shrub, vegetation, bushwood and saplings at least upto 3 M from outer edge of ACSR including removing of braches of trees etc through to a distance exceeding 2 KM out of stn area complete all as specified and directed .Note :- (i) Shutdown wherever required shall be taken in writting from Engr-in-Charge. |
| 36 | Taking down LED lights fittings from High Mast /pole/ walls, and making minor repairs for example, if thre is loose connection, rust on the service cable connection and cable is burnt with the same lights re-refixed the same High Mast /pole/ walls incl testing complete all as specified and directed. (Note : service connection cable shall be measured separately and paid ) |
| 37 | Taking down LED lights fittings from High Mast /pole/ walls, opening of street light/ Flood Lights fittings of any type, wattage and make, making the light fittings operational to give the rated illumination by repairing/ renewal/ replacement of components viz LED panel (PCB)s, driver, electronic circuit and other minor defective parts and refixing the street light in its original position and reconnecting with renewed cable of 1.5 sqmm 3 core stranded copper conductor, PVC insulated and PVC sheathed cable of required 1.5 meter length complete all as specified and directed.Note:- All renewed items shall be measured separately at supplied only under relevant item(ii) Reparing to street light fittings shall be carried out at MES store yard of AGE E/M ES at Meerut. |
| 38 | Supply only LED panel (PCB) suitable for 40/50 watt LED street light fittings, 140V to 270V with system efficiency >100 lumens (minimum) per watt and power efficiency >= 90% complete all as specified and directed. |
| 39 | Supply only LED panel (PCB) suitable for 60 /72 watt LED Street light fittings, 140V to 270V with system efficiency >100 lumens (minimum) per watt and power efficiency >= 90% complete all as specified and directed. |
| 40 | Supply only LED panel (PCB) suitable for 90 /100 watt LED street light fittings, 140V to 270V with system efficiency >100 lumens (minimum) per watt and power efficiency >= 90% complete all as specified and directed. |
| 41 | Supply only LED panel (PCB) suitable for 100 watt LED Flood light fittings, 140V to 270V with system efficiency >100 lumens (minimum) per watt and power efficiency >= 90% complete all as specified and directed. |
| 42 | Supply only LED panel(PCB) suitable for 150 watt LED Flood light fittings, 140V to 270V with system efficiency >100 (minimum) per watt and power efficiency >= 90% complete all as specified and directed . |
| 43 | Supply only LED panel (PCB) suitable for 200-250 watt LED Flood light fittings, 140V to 270V with system efficiency >100 lumens (minimum) per watt and power efficiency >= 90% complete all as specified and directed. |
| 44 | Supply only Driver suitable for 45/48 /50watt LED light fittings, 140V to 270V universal driver with built in surge protection>5KV, 50 Hz +/- 3%, P.f.>0.95, Thd<10% with system efficiency >100 lumens (minimum) per watt and power efficiency >= 90% and protection IP 65 or better .complying LM-79/IS:16106. complete all as specified and directed. |
| 45 | Supply only Driver suitable for 60/70/72watt LED light fittings, 140V to 270V universal driver with built in surge protection>5KV, 50 Hz +/- 3%, P.f.>0.95, Thd<10% with system efficiency >100 lumens (minimum) per watt and power efficiency >= 90% and protection IP 65 or better .complying LM-79/IS:16106.complete all as specified and directed . |
| 46 | Supply only Driver suitable for 90 watt LED light fittings, 140V to 270V universal driver with built in surge protection>5KV, 50 Hz +/- 3%, P.f.>0.95, Thd<10% with system efficiency >100 lumens (minimum) per watt and power efficiency >= 90% and protection IP 65 or better .complying LM-79/IS:16106. complete all as specified and directed. |
| 47 | Supply only Driver suitable for 100 to 250 watt LED Flood light fittings, 140V to 270V universal driver with built in surge protection>5KV, 50 Hz +/- 3%, P.f.>0.95, Thd<10% with system efficiency >100 lumens (minimum) per watt and power efficiency >= 90% and protection IP 65 or better .complying LM-79/IS:16106. complete all as specified and directed. |
| 48 | Repair/maintenance of timer switch assembly of any type and make after dismantling the same from pole, detecting fault, rectifying the same, testing and refixing in the same position after repair/replacement of defective part all as specified. complete all as specified and directed .Note:- All renewed items shall be measured separately at supplied only rates under relevant item |
| 49 | Supply and fixing street light lexic power timer contactor,3 pole,63 Amps complete all as specified and directed. |
| 50 | Supply and fixing Anolog type timer swich 32 Amps range, AC 220/240 volt, 60 Hz , with IEC 60730-1/ IEC 60730-2-7 complete all as specified and directed. |
| 51 | Supply and fixing Astronomical type timer swich 32 Amps range AC 220/240 volt, 60 Hz , with IEC 60730-1/ IEC 60730-2-7 complete all as specified and directed. |
| 52 | Taking down unsv burnt timer panel any type and size and Supplying and fixing in repair automatic operation street light timing switch having lighting control (ON-OFF) through Astronomical Calculation of Sun rise/ sun set by setting date, time and degree of longitude and latitude without separate light sensors and prewired with suitable size of copper conductor single core PVC insulated and sheathed cable and all mechanism fitted into panel, outdoor type , pole mounted with FI 25x4mm clamps , nuts, bolts and washers dully painted, connecting and testing factory made , epoxy powder coated, Single Phase street light panel, Astronomical 24 hrs, suitable for 6KW (max) complete with 32 Amps TP Contactor, and 40 Amps TPN MCBs and fixed on pole/ wall/ feeder pillar complete all as specified and directed. |
| 53 | Taking down unsv burnt timer panel any type and size and Supplying and fixing in repair automatic operation street light timing switch having lighting control (ON-OFF) through Astronomical Calculation of Sun rise/ sun set by setting date, time and degree of longitude and latitude without separate light sensors and prewired with suitable size of copper conductor single core PVC insulated and sheathed cable and all mechanism fitted into panel, outdoor type , pole mounted with FI 25x4mm clamps , nuts, bolts and washers dully painted, connecting and testing factory made , epoxy powder coated, three Phase street light panel, Astronomical 24 hrs, suitable for12 KW (max) complete with 63 Amps TP Contactor, and 63 Amps TPN MCBs and fixed on pole/ wall/ feeder pillar complete all as specified and directed. |
| 54 | Taking out unsv DBs and MCB any type and Supply and fixing SPN DBs 2way for MCB complete with SPN Isolator 63 Amp, suitable for domestic loading, 240 Volt complete all as specified and directed . |
| 55 | Taking down of existing unserviceable Isolator DP and S & F Isolator DP, 40 Amps, 240 Volts , 'C' curve rating and to be housed in existing sheet metal enclosures ( distribution boxes) complete all as specified and directed ). |
| 56 | Taking down of existing unserviceable Isolator TPN and S & F Isolator TPN, 63 Amps, 415 Volts , 'C' curve rating and to be housed in existing sheet metal enclosures ( distribution boxes) complete all as specified and directed . |
| 57 | Dismantling old existing MS cross arms of any type/shape complete all as Specified and directed . |
| 58 | Dismantling old existing Insulators of any type/shape complete all as Specified and directed . |
| 59 | Material and labour for Earthing complete with galvanized steel pipe electrode of size 40mm bore, medium grade burried directly and preferably vertically in ground (earth pit not less than 2.5m deep below normal ground level) with top edge of plate not less than 1.25m below normal ground level, surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt, filling in alternate layer and earth plate connected to galvanized iron earth lead strip of size 32x6mm as earthing conductor by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical (Part I) (2009) connected to earth test point/ main switch/DB all as including testing on completion with and including provision of concrete pit in PCC M15, type B-1 using 20mm graded stone aggregates with 40mm thick precast RCC (1:2:4), type B -1cover reinforced with XPM (weight notless than 4 kg/Sqm) and frame of angleiron 25x25x3mm with lugs 2 Nos and with 6mm dia mild steel bar handle made shape,galvanised iron mediumgrade 20mm bore pipe for watering placed on top edge of earth plate,common salt and charcoal filling, testpoint made out of phosphorous bronze with fixing arrangement, funnel, wiremesh including earth work in any type of soil returning filling in and removal of surplus soil to a distance notexceeding 50 metre and connection to earth test and testing on completion all as specified and as directed for Earthing in Lightning Protection System. Please Enable Macros to View BoQ information |