| 1 | Supply, Installation, Testing & Commisioning of Indoor type, floor mounted Four breaker cubical panel suitable size fabricated from CRCA steel sheet of 2 mm thick for frame work, enclosures and doors, 3 mm thick for gland plates, dust, damm & vermin proof, IP-4X, fully interlocked, horizontal isolation, extensible type, horizontal draw out, air insulated, metal clad switchboard having single isolation features complete with circuits as detailed below. The switchboard shall be complete with necessary PVC insulated copper busbars, small wiring, labels, cable eyes, cable termination to receive XLPE cables and suitable for operation on 11 kV, 3 phase, 50 Hz, earthed system with a rupturing capacity of 250 MVA at 11KV for 3 Sec as per specification. |
| 2 | 1 NO. ICOG BREAKER PANEL EQUIPPED WITH: |
| 3 | 1 No. Air insulated metal clad housing |
| 4 | 1 set of 3 phase PVC insulated copper busbars 800 Amp rating |
| 5 | 6 Nos. single pole cluster type Isolating contacts i.e. plug and switches. |
| 6 | 1 No. Triple pole draw out truck mounted 800 Amp, 11 kV Vacuum Circuit Breaker. |
| 7 | 1 No. Trip free motor spring charged closing mechanism complete with necessary auxiliary switches, emergency hand trip device and mechanical 'OFF' & 'ON' indicator. |
| 8 | 1 No. 24 volt DC shunt trip coil. |
| 9 | 1 No. 24 volt DC closing coil. |
| 10 | 1 No. 230 volt AC spring charge motor. |
| 11 | 3 Nos. Cast resin dual core current transformers of ratio 100A/5A, 15 VA burden Class 5P10 for protection and class 0.5 for metering. |
| 12 | 3 Nos. Single Phase cast resin horizontal draw out line potential transformer ratio 11 kV/110 volts, connected delta/star with HV and LV connections, H.V. and L.V. fuses, Isolating plugs for H.V. and L.V. connection. |
| 13 | 1 set of thermostatically controlled Strip heater to prevent absorption of moisture. |
| 14 | INSTRUMENT AND RELAY PANEL EQUIPPED WITH: |
| 15 | 1 No. multifunction meter for V, Amp, KW, KVAr, KVA, KWH, KVAH, KVARh, P.F. Amp-h, Hz measurements with Ethernet port. |
| 16 | 1 No. Triple pole Microprocessor I.D.M.T. overcurrent and earth fault relay, with two outer elements connected for overcurrent and the middle element for earth fault protection, Overcurrent setting 50% - 200%, Earth fault setting 20% -80% and with instantaneous element on all 3 pole settings 500-2000% on overcurrent and 200-800% on earth fault (51, 51N, 50 and 50N) |
| 17 | 1 No. circuit breaker control switch for electrical (T/N/C). |
| 18 | 1 No. Master trip relay (86) |
| 19 | 1 No. Trip circuit suppervision relay (95) |
| 20 | 1 set of Red/Green indicating lamps for close and open position. |
| 21 | 1 No. Amber indicating lamp for auto trip. |
| 22 | 1 No. clear indicating lamp for trip circuit healthy. |
| 23 | 1 set of white indicating lamps one per phase. |
| 24 | 1 No. blue indicating lamp for spring charged. |
| 25 | 1 No. Push button on front door for emergency trip. |
| 26 | 1 No. cable box suitable for cable termination to receive Incoming and Outgoing 11 kV XLPE Cable 2x3 Core 240Sq. mm. |
| 27 | 1 No. hooter. |
| 28 | 1 set of ferrules, control MCBs, limit switch and wiring as required. |
| 29 | 1 No. Bus Earthing Truck & 1 No. Cable Earthing Truck |
| 30 | Supply, Installation, testing and commissioning of TRANSFORMERS, 3 phase, 50 Hz outdoor type copper wound, delta/star connected (vector group-DYn 11), oil immersed, naturally oil cooled (ONAN), core type Distribution transformer with no load voltage ratio of 11000/415 Volts and with OLTC (+5% to -15% at 1.25%). The transformer shall be suitable for operation at ambient temperature of 50 deg C and shall be supplied with suitable neutral ternimal on LT side and all accessories such as lifting lugs,breather, Buchholz's relay with alarm and trip contacts, magnetic oil guage, air release valve, oil conservator, dial type temperature indicator, earthing terminals, explosion vent, drain valve with plug inclusive of first filling of oil as per IS 335 (with latest amendents), diagram and rating plate & marshalling box. The transformer shall conform to IS 1180- of level-I in all respects like insulation levels, temperature rise, impedance voltage and losses. |
| 31 | 630KVA |
| 32 | MAIN LT PANEL -1 |
| 33 | Design,manufacture,supply inspection, handling, assembling, affecting proper connections, testing and commissioning of 14SWG CRCA sheet steel fabricated cubical type MAIN LT PANEL , floor mounting ,dust & vermin proof, front operated construction, enclosure, powder coated after proper treatment with 9 tank process with top/bottom removable glandplates, as required, double compression type cable glands, earthbus, hinged and lockable doors to achieve dust and vermin proof complete with all interconnections small wiring by min.2.5sq.mm. FRLS copperwires, ckt labels etc. The Aluminium Bus Bar shall be of suitable length, 500volts, 3phase 50Hz TPN, electrolytic aluminium. The panel feeders shall be suitable for terminating suitable nos. 3.5/4 core armoured aluminium cable or Aluminium Bus Duct as required. Fault level shall be 35 KA. |
| 34 | LT Panel-1 |
| 35 | 1 No. 400 Amp FP MCCB microprocessor based releases for O/C, S/C & earth fault protection with instantaneous. (50 KA) |
| 36 | 1 No. Energy analyser (digital type) consisting of I,V,KW,KWH,KVA,PF,HZ,MDI (EM6400 of Conzerve or equi.) with RS485 communication port for communication/report generation. |
| 37 | 1 No. Three Phase Voltmeter, Acc. Cl: 1.0 with Voltmeter Selector Switch |
| 38 | 1 No. Three Phase Ammeter, Acc. Cl: 1.0 with Ammeter Selector Switch |
| 39 | 1 Set R, Y, B Phase Indicating Lamp LED Type |
| 40 | 1 Set Breaker On/Off/Trip Indicating Lamp LED Type |
| 41 | 1 No. Voltage Monitoring Relay with Protection: Under / Over voltage, Phase failure, Phase asymmetry |
| 42 | Auto manual selector switch. |
| 43 | Multifunction Meter |
| 44 | BUSBAR RATING:- 630A TPN ,415Volts, 3 phase 50HZ 35kA Aluminium Bus bar |
| 45 | OUTGOINGS - |
| 46 | 250A 4P 25kA MCCB -1Nos. |
| 47 | 160A 4P 25kA MCCB -1No. |
| 48 | 100A 4P 25kA MCCB -3No. |
| 49 | MAIN LT PANEL -2 |
| 50 | Design,manufacture,supply inspection, handling, assembling, affecting proper connections, testing and commissioning of 14SWG CRCA sheet steel fabricated cubical type MAIN LT PANEL , floor mounting ,dust & vermin proof, front operated construction, enclosure, powder coated after proper treatment with 9 tank process with top/bottom removable glandplates, as required, double compression type cable glands, earthbus, hinged and lockable doors to achieve dust and vermin proof complete with all interconnections small wiring by min.2.5sq.mm. FRLS copperwires, ckt labels etc. The Aluminium Bus Bar shall be of suitable length, 500volts, 3phase 50Hz TPN, electrolytic aluminium. The panel feeders shall be suitable for terminating suitable nos. 3.5/4 core armoured aluminium cable or Aluminium Bus Duct as required. Fault level shall be 35 KA. |
| 51 | LT Panel-1 |
| 52 | 1 No. 600 Amp FP MCCB microprocessor based releases for O/C, S/C & earth fault protection with instantaneous. (50 KA) |
| 53 | 1 No. Energy analyser (digital type) consisting of I,V,KW,KWH,KVA,PF,HZ,MDI (EM6400 of Conzerve or equi.) with RS485 communication port for communication/report generation. |
| 54 | 1 No. Three Phase Voltmeter, Acc. Cl: 1.0 with Voltmeter Selector Switch |
| 55 | 1 No. Three Phase Ammeter, Acc. Cl: 1.0 with Ammeter Selector Switch |
| 56 | 1 Set R, Y, B Phase Indicating Lamp LED Type |
| 57 | 1 Set Breaker On/Off/Trip Indicating Lamp LED Type |
| 58 | 1 No. Voltage Monitoring Relay with Protection: Under / Over voltage, Phase failure, Phase asymmetry |
| 59 | Auto manual selector switch. |
| 60 | Multifunction Meter |
| 61 | BUSBAR RATING:- 630A TPN ,415Volts, 3 phase 50HZ 35kA Aluminium Bus bar |
| 62 | OUTGOINGS - |
| 63 | 400A 4P 25kA MCCB -4Nos. |
| 64 | Supply of XLPE LT Cable Underground Al-Armoured |
| 65 | 400 sq. mm 3-1/2 core |
| 66 | 240 sq. mm 3-1/2 core |
| 67 | 185 sq. mm 3-1/2 core |
| 68 | 150 sq. mm 3-1/2 core |
| 69 | 95 sq. mm 3-1/2 core |
| 70 | 25 sq. mm 3-1/2 core |
| 71 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed/ XLPE aluminium conductor cable of 1.1 kv grade as required. |
| 72 | 400 sq. mm 3-1/2 core |
| 73 | 240 sq. mm 3-1/2 core |
| 74 | 185 sq. mm 3-1/2 core |
| 75 | 150 sq. mm 3-1/2 core |
| 76 | 95 sq. mm 3-1/2 core |
| 77 | 25 sq. mm 3-1/2 core |
| 78 | Laying of one no PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of following size direct in ground icluding excavation sand cushioning and protective covering and refilling the trench etc as required |
| 79 | upto 35 sqmm |
| 80 | Above 35 sqmm and upto 95 sqmm |
| 81 | Above 95 sqmm and upto 185 sqmm |
| 82 | Above 185 sqmm and upto 400 sqmm |
| 83 | Supply and burying of G.I. earth plate 600 mm X 600 mm X 6 mm thick for earthing including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/coke and salt) as required. |
| 84 | Supply and burying of copper earth plate 600 mm X 600 mm X 3 mm thick for earthing including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt) as required. |
| 85 | Supply and laying of 25mm x 5mm G.I. strip from earth electrode directly in the ground as required complete in all respect. |
| 86 | Supply and laying of 50mm x 5mm G.I. strip from earth electrode directly in the ground as required complete in all respect. |
| 87 | Supply and laying of 25mm x 5mm copper strip at 0.50 meter below ground as strip earth electrode including connection / terminating with nut ,bolt spring washer etc. jointing shall be done by overlaping and with 2 sets of brass nut bolt&spring washer spaced at 50mm) |
| 88 | Supply and laying of 50mm x 5mm copper strip at 0.50 meter below ground as strip earth electrode including connection / terminating with nut ,bolt spring washer etc. jointing shall be done by overlaping and with 2 sets of brass nut bolt&spring washer spaced at 50mm) |
| 89 | S/Erection of section/dead end double polestructure of following type of supports duly grouted.Plinthed, plastered and painted in the same manner as already specified for respective supports with M.S. channels with packing piece and bolt and nuts as required Quantity as Specification including cost of material, labour and T&P required for proper completion of work as per direction of E/I. Double Pole made of 11 Mtr. Long SP-55 ST Pole (Bottom Portion Galvamised) .. |
| 90 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed pvc conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C |
| 91 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed PVC conduit as required.DSR 2022 -SI- 1.14 |
| 92 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 93 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 94 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 95 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 96 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 97 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 98 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 99 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, “C” curve including connections, painting etc. as required. |
| 100 | Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. |
| 101 | Supplying and fixing brass batten/ angle holder including connection etc. as required. |
| 102 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required DSR 2022 SI No. 2.13 |
| 103 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required |
| 104 | Single Pole |
| 105 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powdr painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 106 | 4 way (4 + 12), Double door |
| 107 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A \\"C\\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the ocket out let and complete with connections, testing and commissioning etc. as required. |
| 108 | Supply and fixing of following sizes of PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required : |
| 109 | 20 mm |
| 110 | 25 mm |
| 111 | Supply and burring of safe Earthing Electrode T – 19 (Hot Dip Galvanized) Length 3000 mm outer pipe 50 mm inner pipe 25 , terminal Dia 12 mm outer G.I. pipe of 16 swg and inner G.I. pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square C.I. frame with hinged cover and masonry housing |
| 112 | Supply, Installation, Testing and Commissioning of 1200 mm sweep BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B. 3 nos, blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor notless than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min, 350 RPM (tolerance as per IS: 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise 75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required |
| 113 | Supply and fixing of LED Street light Fitting with mandatory driver set having die cast aluminium body with toughend glass/ UV stabilized PC Cover and lenses suitable for 110 Watt to 130 Watt and Confirming to IP 66, and IK07 and above protection having Company LOGO Engraved complete in all respect including Labour. |
| 114 | 13200-15600 system lumens, High Power LED with lenses, 120 Lm/W, PF>0.95, THD <10% at full load, CRI >70, Potted driver Set in Metal housing (Not Circuitory), Phase to phase Protection at 440V & >300V auto cut and re-start feature, 4KV internal Surge protection, with 5 years warrantee.CAT-AAA As per PWD SOR 2024 S.I. NO. 23.17 (Without GST Rate 12189 x 0.8475 = 10330.17 Say Rs. 10330.00) |
| 115 | Providing and fIxing of 125A TPN MCCB capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required. 125A TP &N MCCB |
| 116 | Providing / Fixing of Fire Fighting Terrace pump set suitable for automatic operation consisting of the following as per the specification. a) Horizontally mounted, centrifugal type single/multi stage fire pump having cast iron body, bronze impeller,7.5 H.P against a total head of 35 mtrs. Complete with pressure gauge & gun metal cocks on delivery side including bypass arrangement. |
| 117 | 900 LPM at 35 m Head |
| 118 | Providing/Fixing of cubical type floor mounted Fire pump control panel fabricated from 16 G M.S. sheet duly powder coated finish of approved shade and comprising of : a) One 100 amp. TP+NL M.C.C.B with rotary handle of beacking capacity 35 KA. b)One Volt meter (0-500 V) with selector switch. c) One set indicating lamps. (MR) \\" |
| 119 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required: |
| 120 | 100 mm dia |
| 121 | Supplying and fixing Single headed internal/external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required: |
| 122 | Single Headed Gunmetal Please Enable Macros to View BoQ information |
| 123 | Single Headed Gunmetal Please Enable Macros to View BoQ information |