| Sl. No. | Item Description |
| 1 | Submission of design, drawing,(vetted from any recognized University such as I.I.T), testing of bearing capacity of soil and supply of all material, labour T&P etc. and construct as per tenderer's own seismic proof design and drawings (approved by the department) complete intze Type on raft or pile cum raft foundation with columns and braces R.C.C. Over Head Tank following capacity and staging from made up ground level at site to the top of bottom ring beam of tank, with a minimum free board of 15cm. The design of the tank shall base on safe bearing capacity of soil at site as 8 T/m2 and depth of foundation as 2.50m from existing ground level on pile/raft foundation. made up level of OHT will be taken as 0.70 m above existing gound level. Extra earth required for made up level will be arranged by the contractor at his own cost. If the bearing capacity of soil less than 8 T/m2 than the contractor will submit the design on the same B.C. No extra payment will be paid for this. All other details of tank not covered here shall also be as per specifications enclosed. All Components of OHT will be casted in M-30 concrete with cement, coarse sand and approved stone grit as per I.S. 11682 and I.S. 456. Minimum depth of founditation below original ground level will be 2.50 M. Seismic effects and wind load should be taken into consideration as I.S. 1893 for earthquake resistance and I.S. 875 part-III for wind load on structure. Two coloumn R.C.C. stair case with 1.0 m minimum clear width attached with tank body as an access to Balcony and Top Dome of tank from ground level as per design & drawing with 1.25 m high railling and gate with cabin as per specification including supply of all materials. M.S. ladder made of 50 X 50 X 6 mm angle section and 20 mm plain M.S. bars (specification of M.S. should be as per IS 800-2007) with hand rails of 20 mm medium class G.I. pipes on both sides in three rows from balcony to top dome resting on an RCC plateform (75 X 75 cm and 10 cm thick) projecting from top ring beam and one alluminium ladder inside the tank body ( from manhole in top dome to bootom dome). 1 m wide R.C.C. balcony around the tank at the junction point of vertical wall and conical wall. Proper R.C.C. railing and 20 mm dia medium class G.I. pipe (in 3 rows) on both sides of stair case, arround the balcony at each landing from landing with top ring beam upto manhole on the top dome and at the periphery. The G.I. pipes will be supported on R.C.C. posts of 100 mm dia or on the posts made of 50 X 50 X 6 mm M.S. angle section, spaced at intervals not more than 1.5 m. Proper ventilator at top dome in circular shape of 1.2 m dia along with an R.C.C. cover of minimum 1.50 m dia and 7.5 cm thickness, pillar of vintilator should be minimum 50 cm dia. The space between top dome and R.C.C. cover should be covered with mosquito net of standered qualitity along with expended mentaled jail. Electro Magnetic Flow Meter. Lightening conductor as per I.S.S. 2309 of its latest amendments of latest electricity rules. It should consist proper elevation rod with 5 or more fork points proper down conductors of prescribed mental of proper size prescribed by ISS 2309-1969 and ISS 3013-1966. D.I. manhole of min 60 X 60 cm size made of M.S. channel section with adequate cover made of M.S. sheet of minimum 3mm thickness hinged with manhole with locking arrangment. This manhole should be fixe at top dome at proper place. Supply, fixing, jointing of following size of D.I. D/F Pipes with D.I. D/F specials conforming to IS 8329/2000 as vertical pipes for inlet, outlet, over flow and washout as per latest / relevent I.S. specifications with all jointing materials for proper completion of work including other appurtenant works and execuvation in all types of soil. Construction of bed blocks in 1:2:4 PCC with cement, coarse sand and approved stone grit under each duck foot bend to support the vertical pipes. These bed blocks should supported on the raft not on the soil. Construction of Sluice valve chamber for above sluice valve as per departmental type design and drawing including supply and fixing of C.I. sluice valve including locking arrangement. Construction of washout/ overflow chamber as per departmental type design and drawing. Construction of R. C. C.(1:1.5:3) Floor with minimum reinforcement, Drain & Rain water harvesting, Bye pass arrangement each Rising main , byepass arrangement of over flow pipe all complete and all other necessary work as per departmental drawing and design. Painting of OHT with wheather proof paint (like apex etc.), and Painting of iron work with 1 coat primer & 2 coats of approved emultion paint as per direction of engineer incharge. Testing & Commission etc. all complete work. |
| 2 | ZONE-2 700 KL/20M Staging, Outlet 200 mm (DMA-01) -1 No.And Outlet 160 mm (DMA-02)-1 No, inlet 200 mm-03 Nos., Over flow-300 mm-1No., Wash out 150 mm -1 No. Supply and Fixing of following sizes D.I. D/F sluice valves with hand wheels as per I.S.S. 700/1969 or its latest pressure 10 kg/sqcm including cartage from its store to the site of work, lowering them into trenches, fixing in position & testing etc.complete. |
| 3 | ZONE-3 2200 KL/22M Staging, Outlet 200 mm (DMA-01) -1 No.And Outlet 160 mm (DMA-02)-1 No, inlet 200 mm-03 Nos., Over flow-300 mm-1No., Wash out 150 mm -1 No. Supply and Fixing of following sizes D.I. D/F sluice valves with hand wheels as per I.S.S. 700/1969 or its latest pressure 10 kg/sqcm including cartage from its store to the site of work, lowering them into trenches, fixing in position & testing etc.complete. |
| 4 | ZONE-1 Repairing /Renovaton of Existing 450KL/16.0 M OHT Staging in Zone -1 including leakeage /seepage ,repair with nipple grouting in bottom dome ,conical wall., vertical wall and its finishing and repairing in brace, coloumns ,staircase,balcony etc complete, supply and fixing of ss ladder in water container and in balcony as per requirement ,repairing of railing and sataircase, door ,replacement of ventilator ,lightening conductor , Earthing wire, construction of Rcc floor with 1:1.5:3 ratio ,painting of OHT with apex as per colour code of upjn , repairing of sluice valve and constructon of its chambers, Replacement of inlet,outlet,washout ,overflow pipes ,suppy and fixing of mesh around ventilation of OHT. |
| 5 | RISING MAINSupply of the following sizes of D.I. pipes Class K-9 conforming to latest I.S. 8329 / 2000 including their jointing materials and railway freight taxes insurance charges and cartage from store to site of work etc. complete |
| 6 | Zone-1, 125mm dia, D.I. K-9 |
| 7 | Zone-2, 150mm dia, D.I. K-9 |
| 8 | Zone-3, 200mm dia, D.I. K-9 |
| 9 | Excavation for rising main trenches in ordinary soil,(lime, clay or sand including lift up to 1.5m and lead up To 50m and refilling, watering, ramming of excavated earth in to trenches and disposal of surplus earth up to 50 m from the center of the foundation trenches. |
| 10 | Carting from the store (up to 8 Km.) The following sizes of D.I. double pipe k-9 and specials to the site of work lowering them in to trenches and laying true to alignment and gradient including jointing, testing of pipeline and including supply of jointing material such as nut & bolts, rubber insertion, white lead etc. com- plate but excluding cost of trenching and cutting of pipes etc. For making of lengths but including making joints. |
| 11 | Zone-1, 125mm dia, D.I. K-9 |
| 12 | Zone-2, 150mm dia, D.I. K-9 |
| 13 | Zone-3, 200mm dia, D.I. K-9 |
| 14 | Supply of following sizes of CI D/F Sluice valves as per IS 780-1960 tested to 10Kg / Cm2 fixing in pipelines trenches, jointing and testing etc. complete. |
| 15 | Zone-1, 125mm dia, D.I. K-9 |
| 16 | Zone-2, 150mm dia, D.I. K-9 |
| 17 | Zone-3, 200mm dia, D.I. K-9 |
| 18 | Carting laying and jointing of the following sizes of CI D/F Sluice valves into the trenches including cost of all jointing material, labour T&P and testing etc. complete of work. 150mm CI D/F Sluice valves |
| 19 | Zone-1, 125mm dia, D.I. K-9 |
| 20 | Zone-2, 150mm dia, D.I. K-9 |
| 21 | Zone-3, 200mm dia, D.I. K-9 |
| 22 | Supply of all materials, labours T&P etc. and construction of masonary type sluice valve chamber. |
| 23 | Construction of RCC Thrust Block at Bands of pipes |
| 24 | DISTRIBUTION SYSTEMSupply and carting ,laying of the following sizes of DI /HDPE pipes (including all specials and solvent) confirming to latest relevant I.S.S with H.D.P.E/DI couplers etc complete in all respect F.O.R. destination including all taxes and insurance.IS -8329/2000 and IS Code 4984:2016 HDPE GRADE-PE-100 HDPE Pipe will be jointed by electrofusion method with all specials and jointing materials as per satisfaction of site incharge. |
| 25 | ZONE-1 DI K-7 PIPE (IS - 8329 / 2000) |
| 26 | 250 mm dia DIK-7 |
| 27 | 200 mm dia DIK-7 |
| 28 | HDPE PIPE (IS - 4984 / 2016) |
| 29 | 160 mm dia HDPE PIPE-PN6 |
| 30 | 140 mm dia HDPE PIPE-PN6 |
| 31 | 110 mm dia HDPE PIPE-PN6 |
| 32 | 90 mm dia HDPE PIPE-PN6 |
| 33 | ZONE-2 DI K-7 PIPE (IS - 8329 / 2000) |
| 34 | 300 mm dia DIK-7 |
| 35 | 200 mm dia DIK-7 |
| 36 | HDPE PIPE (IS - 4984 / 2016) |
| 37 | 160 mm dia HDPE PIPE-PN6 |
| 38 | 140 mm dia HDPE PIPE-PN6 |
| 39 | 110 mm dia HDPE PIPE-PN6 |
| 40 | 90 mm dia HDPE PIPE-PN6 |
| 41 | ZONE-3 DI K-7 PIPE (IS - 8329 / 2000) |
| 42 | 500 mm dia DIK-7 |
| 43 | 400 mm dia DIK-7 |
| 44 | 350 mm dia DIK-7 |
| 45 | 250 mm dia DIK-7 |
| 46 | 200 mm dia DIK-7 |
| 47 | HDPE PIPE (IS - 4984 / 2016) |
| 48 | 160 mm dia HDPE PIPE-PN6 |
| 49 | 140 mm dia HDPE PIPE-PN6 |
| 50 | 110 mm dia HDPE PIPE-PN6 |
| 51 | 90 mm dia HDPE PIPE-PN6 |
| 52 | Carting of following size of pipes laying , jointing of DI/HDPE pipe in trenches including lowering ,testing ,and supply of all jointing materials etc complete , HDPE pipe joint by electrofusion methood only |
| 53 | ZONE-1 DI K-7 PIPE (IS - 8329 / 2000) |
| 54 | 250 mm dia DIK-7 |
| 55 | 200 mm dia DIK-7 |
| 56 | HDPE PIPE (IS - 4984 / 2016) |
| 57 | 160 mm dia HDPE PIPE-PN6 |
| 58 | 140 mm dia HDPE PIPE-PN6 |
| 59 | 110 mm dia HDPE PIPE-PN6 |
| 60 | 90 mm dia HDPE PIPE-PN6 |
| 61 | ZONE-2 DI K-7 PIPE (IS - 8329 / 2000) |
| 62 | 300 mm dia DIK-7 |
| 63 | 200 mm dia DIK-7 |
| 64 | HDPE PIPE (IS - 4984 / 2016) |
| 65 | 160 mm dia HDPE PIPE-PN6 |
| 66 | 140 mm dia HDPE PIPE-PN6 |
| 67 | 110 mm dia HDPE PIPE-PN6 |
| 68 | 90 mm dia HDPE PIPE-PN6 |
| 69 | ZONE-3 DI K-7 PIPE (IS - 8329 / 2000) |
| 70 | 500 mm dia DIK-7 |
| 71 | 400 mm dia DIK-7 |
| 72 | 350 mm dia DIK-7 |
| 73 | 250 mm dia DIK-7 |
| 74 | 200 mm dia DIK-7 |
| 75 | HDPE PIPE (IS - 4984 / 2016) |
| 76 | 160 mm dia HDPE PIPE-PN6 |
| 77 | 140 mm dia HDPE PIPE-PN6 |
| 78 | 110 mm dia HDPE PIPE-PN6 |
| 79 | 90 mm dia HDPE PIPE-PN6 |
| 80 | Supply of the following sizes of Hand Wheel Type Sluice Valves /Scour valve destination including all taxes and insurance. |
| 81 | 400 mm dia |
| 82 | 350 mm dia |
| 83 | 300 mm dia |
| 84 | 250 mm dia |
| 85 | 200 mm dia |
| 86 | 150 mm dia |
| 87 | 100 mm dia |
| 88 | Scour valve 80 mm dia |
| 89 | Supply of underground sluice valves type 80 mm fire hydrant consisting of 80 mm dia tail pieces, 80 mm dia duck foot band and 63 mm dia standard make iron coupling with cap and chain etc. complete to ISS 909 at site. |
| 90 | Supply of 50 mm dia screwed down type air valve with gun metal seat at site stone. |
| 91 | Carting of following sizes D.I.D/F Sluice valve and specials from departmental store to site of work and lowering them into the trenches, fixing in position and jointing them with pipelines and testing etc. complete (including supply of jointing materials) |
| 92 | 400 mm dia |
| 93 | 350 mm dia |
| 94 | 300 mm dia |
| 95 | 250 mm dia |
| 96 | 200 mm dia |
| 97 | 150 mm dia |
| 98 | 100 mm dia |
| 99 | scour valve 80 mm dia |
| 100 | Carting of underground sluice valves type 80 mm fire hydrant consisting of 80 mm dia tail pieces, 80 mm dia duck foot band and 63 mm dia standard make iron coupling with cap and chain etc. complete to ISS 909 at site. |
| 101 | Carting of 50 mm dia screwed down type air valve with gun metal seat at site stone. |
| 102 | Excavation for pipe line trenches in Ordinary soil,(lime, clay or sand Including lift up to 1.5m and lead up To 50m and refilling, watering, Ramming of excavated earth in to trenches and disposal of surplus earth up to 50 m from the center of the foundation trenches. |
| 103 | Dismantling of following type of surface including sorting out and staking of serviceable materials of disposal of unserviceable materials up to a distance of 50 m. |
| 104 | B.O.E. ROAD |
| 105 | BITUMINOUS ROAD |
| 106 | C.C. ROAD |
| 107 | INTERLOCKING TILES |
| 108 | Permanent Reinstatement of following type of Road surface for laying of pipe line including supply of all materials labour,T&P etc. complete in the direction of engineer in charge. |
| 109 | B.O.E. ROAD |
| 110 | BITUMINOUS ROAD |
| 111 | C.C. ROAD |
| 112 | INTERLOCKING TILES |
| 113 | Supply of all materials, labour T&P etc. required and construct surface box/masonry type sluice / scour valve chamber as per type design including supply and materials labour, T&P etc. complete. |
| 114 | S.V. Chamber (Surface box type) |
| 115 | S.V. Chamber (Masonry type) |
| 116 | Air valve chamber |
| 117 | Fire hydrant chmaber |
| 118 | Provision for crossing of nala, & culverts (for 2.50m - 3.50m wide) including shiftijng of telephone cabel etc.along the alignment of pipe line including supply of C.I Tyton pipe and special and also jointing material their laying and jiointing testing etc,complite. |
| 119 | Trenchless Technology for the Year 2023350mm dia HDD Trenchless Technology |
| 120 | Provision for crossing of nala & culverts (for 1.50m - 2.50m wide) including shiftijng of telephone cabel etc.along the alignment of pipe line including supply of C.I Tyton pipe and special and also jointing material their laying and jiointing testing etc,complite. |
| 121 | SCHEDULE FOR HOUSE CONNECTIONMaking New house connection with distribution main supply, carting of specials, lowering them into trenches, fixing them in proper alignment and jointing, including bailing out of water, necessary execvation for connection including all labour, T&P etc. required for proper completion of the works. |
| 122 | 90 mm to 110 mm dia pipe line |
| 123 | 125 mm to 160 mm dia pipe line |
| 124 | 180 mm to 250 mm dia Pipe line |
| 125 | 300 mm dia to 350 mm dia pipe line |
| 126 | Dismantling of following type of surface including sorting out and staking of serviceable materials of disposal of unserviceable materials up to a distance of 50 m. for house connection work. |
| 127 | B.O.E. ROAD |
| 128 | BITUMINOUS ROAD |
| 129 | C.C. ROAD |
| 130 | INTERLOCKING TILES |
| 131 | Permanent Reinstatement of following type of Road surface for making house connection including supply of all materials labour, T&P etc. complete in the direction of engineer in charge. |
| 132 | B.O.E. ROAD |
| 133 | BITUMINOUS ROAD |
| 134 | C.C. ROAD 1:1.5:3 WITH 1:4:8 BASE CONCRETE |
| 135 | INTERLOCKING TILES |
| 136 | Making Shifting house connection with distribution main supply, carting of specials, lowering them into trenches, fixing them in proper alignment and jointing, including bailing out of water, necessary execvation for connection including all labour, T&P etc. required for proper completion of the works. |
| 137 | 90 mm to 110 mm dia pipe line |
| 138 | 125 mm to 160 mm dia pipe line |
| 139 | 180 mm to 250 mm dia Pipe line |
| 140 | 300 mm dia to 350 mm dia pipe line |
| 141 | Dismantling of following type of surface including sorting out and staking of serviceable materials of disposal of unserviceable materials up to a distance of 50 m. for house connection work. |
| 142 | B.O.E. ROAD |
| 143 | BITUMINOUS ROAD |
| 144 | C.C. ROAD |
| 145 | INTERLOCKING TILES |
| 146 | Permanent Reinstatement of following type of Road surface for making house connection including supply of all materials labour, T&P etc. complete in the direction of engineer in charge. |
| 147 | B.O.E. ROAD |
| 148 | BITUMINOUS ROAD |
| 149 | C.C. ROAD 1:1.5:3 WITH 1:4:8 BASE CONCRETE |
| 150 | INTERLOCKING TILES |
| 151 | Construction of Pump House cum Chloronome and development works Provide all materials, labour, T&P Complete pump house of size (3.60x 3.0x 3.00) m Chloronome of size (2.25 x 2.25 x 3.00) m size including byepass chamber as per type design. |
| 152 | ZONE-1, Zone-3 |
| 153 | BOUNDARY WALL, GATE SITE DEVELOPMENT & APPROACH ROAD (As per Drawing) Proposed W/W |
| 154 | Construction of Boundary wall alround water works compound and Tubewell complete including supply of all materials, labour, T&P etc. complete required for proper completion of the works. |
| 155 | Supply and fixing of 3.6 M wide gate and 1.2 M wide MS wicket gate including fabrication and supply of steel and construction of boundary pillars etc. complete. |
| 156 | Construction of Interlocking type approach road including supply of all materials, labour, tools and plants etc. complete. |
| 157 | Provide all materials, labour T&P etc. required for proper completion of work including levelling, dressing excavation and filling of earth where necessary for develop of water works site including carriage of earth. |
| 158 | Provision for inside square drain including supply of all materials labour and T & P etc. complete. |
| 159 | Construction of Reccharging unit of ground water by rain water in water works sites as per drawing including supply of all material ,labour T&P etc required for proper completion of works |
| 160 | Construction LCS AND MCS ROOM |
| 161 | E&M work |
| 162 | CONSTRUCTION OF TUBEWELL (300x150 mm dia) ZONE-1 |
| 163 | Transportation, Erection, Dismantling of Rig Machine and its T&P |
| 164 | Transportation, Erection, Dismantling of Compressor 250/350 PSI |
| 165 | Transportation, Erection, Dismantling of 1 Cusec/ 3 Cusec O.P. Unit and Yield test |
| 166 | Supply of Tubewell Assembly M.S.Tubewell assembly with all required parts like plain pipe, Slotted pipe (as required upto 50% of plain pipes) rings, well cap bail plug, clamp reducer, central guide, suport structure etc. as required & as per typed design complete in all respect. (Note- Axial Length of Reducer without Ring shall be measured with casing pipe) |
| 167 | 300 mm dia M.S. Pipe |
| 168 | 150 mm dia M.S. Plain/slotted |
| 169 | PEA-GRAVEL (As per IS:4097) |
| 170 | 1.65 mm to 4.50 mm size Pea gravel of Lalkuwan quarry duly screened, washed and properly stacked at site for Tubewell |
| 171 | Drilling of bore for tubewell constrution by DC/RC Rig machine complete in all respect including reqired all material, labour etc. as per IS :2800(Part I & II): |
| 172 | Drilling of bore by 600 mm dia bit GL to 54 mt. BGL. |
| 173 | Drilling of bore by 500 mm dia bit from 54 mt GL to 100 mt. BGL. |
| 174 | Drilling of bore by 500 mm dia bit 100 m BGL to 129 m. BGL. |
| 175 | Lowering of tube well assembly With M.S. rings, Bail Plug, Reducer Including welding: |
| 176 | Lowering of 300 mm dia M.S. Housing pipe from GL to 48 m.BGL |
| 177 | Lowering of 150 mm dia M.S. Plain/slotted pipe 48 m. BGL to 100 m. BGL |
| 178 | Lowering of 150 mm dia M.S. Plain/slotted pipe 100 m. BGL to 117 m. BGL |
| 179 | Development of tube well by 250 PSI air compressor and 1 cusec O.P. Unit to yield sand free discharge. |
| 180 | Development and testing of tube well by Air Compressor. |
| 181 | Development and testing of tube Well O.P.Unit to yield sand free Discharge. |
| 182 | Chemical and Bacteriological |
| 183 | test (Analysis of water sample) |
| 184 | Logging of borehole by departmental/approved electric logger |
| 185 | ESTIMATE FOR CONSTRUCTION OF TUBEWELL (300x200 mm dia) ZONE -2 |
| 186 | Transportation, Erection, Dismantling of Rig Machine and its T&P |
| 187 | Transportation, Erection, Dismantling of Compressor 250/350 PSI |
| 188 | Transportation, Erection, Dismantling of 1 Cusec/ 3 Cusec O.P. Unit and Yield test |
| 189 | Supply of Tubewell Assembly M.S.Tubewell assembly with all required parts like plain pipe, Slotted pipe (as required upto 50% of plain pipes) rings, well cap bail plug, clamp reducer, central guide, suport structure etc. as required & as per typed design complete in all respect. (Note- Axial Length of Reducer without Ring shall be measured with casing pipe) |
| 190 | 300 mm dia M.S. Pipe |
| 191 | 200 mm dia M.S. Plain/slotted |
| 192 | PEA-GRAVEL (As per IS:4097) |
| 193 | 1.65 mm to 4.50 mm size Pea gravel of Lalkuwan quarry duly screened, washed and properly stacked at site for Tubewell |
| 194 | Drilling of bore for tubewell constrution by DC/RC Rig machine complete in all respect including reqired all material, labour etc. as per IS :2800(Part I & II): |
| 195 | Drilling of bore by 600 mm dia bit GL to 55 mt. BGL. |
| 196 | Drilling of bore by 500 mm dia bit from 55 mt GL to 100 mt. BGL. |
| 197 | Drilling of bore by 500 mm dia bit 100 m BGL to 140 m. BGL. |
| 198 | Lowering of tube well assembly With M.S. rings, Bail Plug, Reducer Including welding: |
| 199 | Lowering of 300 mm dia M.S. Housing pipe from GL to 48 m.BGL |
| 200 | Lowering of 200 mm dia M.S. Plain/slotted pipe 48 m. BGL to 100 m. BGL |
| 201 | Lowering of 200 mm dia M.S. Plain/slotted pipe 100 m. BGL to 130 m. BGL |
| 202 | Development of tube well by 250 PSI air compressor and 1 cusec O.P. Unit to yield sand free discharge. |
| 203 | Development and testing of tube well by Air Compressor. |
| 204 | Development and testing of tube Well O.P.Unit to yield sand free Discharge. |
| 205 | Chemical and Bacteriological |
| 206 | test (Analysis of water sample) |
| 207 | Logging of borehole by departmental/approved electric logger |
| 208 | CONSTRUCTION OF TUBEWELL (300x200mm dia) ZONE-3 |
| 209 | Transportation, Erection, Dismantling of Rig Machine and its T&P |
| 210 | Transportation, Erection, Dismantling of Compressor 250/350 PSI |
| 211 | Transportation, Erection, Dismantling of 1 Cusec/ 3 Cusec O.P. Unit and Yield test |
| 212 | Supply of Tubewell Assembly M.S.Tubewell assembly with all required parts like plain pipe, Slotted pipe (as required upto 50% of plain pipes) rings, well cap bail plug, clamp reducer, central guide, suport structure etc. as required & as per typed design complete in all respect.(Note- Axial Length of Reducer without Ring shall be measured with casing pipe) |
| 213 | 300 mm dia M.S. Pipe |
| 214 | 200 mm dia M.S. Plain/slotted |
| 215 | PEA-GRAVEL (As per IS:4097) |
| 216 | 1.65 mm to 4.50 mm size Pea gravel of Lalkuwan quarry duly screened, washed and properly stacked at site for Tubewell |
| 217 | Drilling of bore for tubewell constrution by DC/RC Rig machine complete in all respect including reqired all material, labour etc. as per IS :2800(Part I & II): |
| 218 | Drilling of bore by 600 mm dia bit GL to 60 mt. BGL. |
| 219 | Drilling of bore by 500 mm dia bit from 60 mt GL to 100 mt. BGL. |
| 220 | Drilling of bore by 500 mm dia bit 100 m BGL to 170 m. BGL. |
| 221 | Lowering of tube well assembly With M.S. rings, Bail Plug, Reducer Including welding: |
| 222 | Lowering of 300 mm dia M.S. Housing pipe from GL to 54 m.BGL |
| 223 | Lowering of 200 mm dia M.S. Plain/slotted pipe 54 m. BGL to 100 m. BGL |
| 224 | Lowering of 200 mm dia M.S. Plain/slotted pipe 100 m. BGL to 155 m. BGL |
| 225 | Development of tube well by 250 PSI air compressor and 1 cusec O.P. Unit to yield sand free discharge. |
| 226 | Development and testing of tube well by Air Compressor. |
| 227 | Development and testing of tube Well O.P.Unit to yield sand free Discharge. |
| 228 | Chemical and Bacteriological |
| 229 | test (Analysis of water sample) |
| 230 | Logging of borehole by departmental/approved electric logger |
| 231 | PUMPING PLANT & VOLTAGE STABILIZER FOR NEW/EXISTING TUBEWELL ZONE -1 |
| 232 | Supply, Installation, testing and Commissioning of 600 lpm ,52 mtr Head Pumping Plant including 24 met coloumn pipe, NRV,CI D/F Bend 90 deg., CI A/F Tee, D/F pipe (1.5 met long-2 Nos and 1 met long- 1 No ), Earthing, Painting,Toolset,wiring of pump house (with internal&external electrification),chainpully block and all pumping plant accessories with nut bolts and rubber packing etc. |
| 233 | SITC of suitable capacity soft starter with RS485 port- 400 V Class. |
| 234 | SITC of 100 mm dia size mannually operated sluice valves (e&m sor, deduction of actuator rate from actuator valve rate) |
| 235 | SITC of 25 kva stabilizer for above |
| 236 | SITC of equipments for the items as given below : |
| 237 | CE/UL certified Pressure transmitter with display,snubber & gauge coak |
| 238 | Automatic Chlorination System compatible to SCADA system |
| 239 | CE/UL certified hydostatic type sub soil water level transmitter for tubewell. |
| 240 | Misc. Items such as Prtection Ring, Cutout, Electric resistance Rubber sheet, Transformer oil etc.-Sor 2019 |
| 241 | Coloumn Pipe 3 mtr long |
| 242 | ESTIMATE FOR NEW PUMPING PLANT & VOLTAGE STABILIZER ZONE -2 |
| 243 | Supply, Installation, testing and Commissioning of 900 lpm ,66 mtr Head Pumping Plant including 24 met coloumn pipe, NRV,CI D/F Bend 90 deg., CI A/F Tee, D/F pipe (1.5 met long-2 Nos and 1 met long- 1 No ), Earthing, Painting,Toolset,wiring of pump house (with internal&external electrification),chainpully block and all pumping plant accessories with nut bolts and rubber packing etc. |
| 244 | SITC of suitable capacity soft starter with RS485 port- 400 V Class. |
| 245 | SITC of 100 mm dia size mannually operated sluice valves (e&m sor, deduction of actuator rate from actuator valve rate) |
| 246 | SITC of 40 kva stabilizer for above |
| 247 | SITC of equipments for the items as given below : |
| 248 | CE/UL certified Pressure transmitter with display,snubber & gauge coak |
| 249 | Automatic Chlorination System compatible to SCADA system |
| 250 | CE/UL certified hydostatic type sub soil water level transmitter for tubewell. |
| 251 | Misc. Items such as Prtection Ring, Cutout, Electric resistance Rubber sheet, Transformer oil etc.-Sor 2019 |
| 252 | Coloumn Pipe 3 mtr long |
| 253 | NEW PUMPING PLANT & VOLTAGE STABILIZER ZONE-3 |
| 254 | Supply, Installation, testing and Commissioning of 1800 lpm , 63 mtr Head Pumping Plant including 24 met coloumn pipe, NRV,CI D/F Bend 90 deg., CI A/F Tee, D/F pipe (1.5 met long-2 Nos and 1 met long- 1 No ), Earthing, Painting,Toolset,wiring of pump house (with internal&external electrification),chainpully block and all pumping plant accessories with nut bolts and rubber packing etc. |
| 255 | SITC of suitable capacity soft starter with RS485 port- 400 V Class. |
| 256 | SITC of 150 mm dia size Manuallly operated sluice valves |
| 257 | SITC of 60 kva stabilizer for above |
| 258 | SITC of equipments for the items as given below : |
| 259 | Automatic Chlorination System compatible to SCADA system |
| 260 | Pressure transmitter with display |
| 261 | CE/UL certified hydrostatic type sub soil water level transmitter for tubewell |
| 262 | Misc. Items such as Prtection Ring, Cutout, Electric resistance Rubber sheet, Transformer oil etc. |
| 263 | Coloumn Pipe 3 mtr long |
| 264 | ESTIMATE FOR LOCAL CONTROL STATION |
| 265 | CE/UL & BIS Certified industrial grade LARGE SIZE LED MONITOR with lates configuration as per specification. |
| 266 | Desktop/PC with i5/i7 processor for as per spec mentioned in tachnical bid documents. |
| 267 | CE/UL Certified 3 KVA UPS with batteries as per spec mentioned in tachnical bid documents. |
| 268 | Full development version of required TAGS SCADA Software with coustomization of software for LCS as per spec mentioned in tachnical bid documents. |
| 269 | GSM based wireless/Broadband/Equivalent communication system to transfer & receive data & gather data form remote sites to control station,All accessories include signal enhancer antenna along with running expences till DLP. |
| 270 | CE/UL certified Firewall for network protection and gateway for providing data to other lcs/mcs. |
| 271 | Surge protector for eternet communication protection. |
| 272 | industrial grade Ethernet Switch. |
| 273 | canon/hp Laser printer1018 or equivalent |
| 274 | Installation,Commissioning ,testing including required furniture,internal wiring,PVC panelling of walls/false ceiling work and Split A/C . |
| 275 | Security Survelliance IP Camera with required hard drive to store data of atleast 15 Days |
| 276 | Charges for operation during trial & Run of 3 months |
| 277 | SCADA /AUTOMATION WORK OF NEW PUMPING PLANT ZONE-03 |
| 278 | CE & UL Certifeid PLC/RTU in IP 54 enclousure suitable to communicate with GSM based modem unit with CPU and power supply with analog anddigital parameter and features as specifeid for tubewell to store and transmit data on GSm backbone RTU/PLC designed with logic to transfer data at multiple statiuonas specifeid. |
| 279 | GSM/GPRS based wireless communication with 4G modem for RTU/PLOc capable to transfer & gather data from remote site to controlstation all accessoreis included with signalenhancer antenna made for pumping plant internet charges as specifeid |
| 280 | CE/UL certifeid Intelligent Smart Energy Meter |
| 281 | CE/UL Certifeid Electromagnetic Flow Meter 150 mm size |
| 282 | auto Phase reversal unit of 125 amp rating with inbuilt delay and enclosure control panel etc. |
| 283 | CE/UL certifeid Surge Protecter for control panel. |
| 284 | CE/UL Certifeid 7 hmi touch screen suitable to communication with PLC/RTU for display & control of process parameters |
| 285 | Complete cabling including power cables of all equipment. |
| 286 | control panel with IP54 protection ,industrial grade for all equipments.separate for control (24V) and power equipment with capacitor bank panel to improve power factor. |
| 287 | Installation, commissioning & testing trial for tubewell |
| 288 | OHT AUTOMATION SYSTEM ZONE-03 |
| 289 | CE/UL certifeid Radar Type level transmitter for OHT. |
| 290 | SITC of UPS 10 kva 3phase suitable for operation of Actuators installed at outlet line in case of Power Failure at time of Distribution water supply |
| 291 | Lighting at Water works campus with solar panel and LED light of 3 sets |
| 292 | Installation, commissioning & testing trial for OHT |
| 293 | E/M WORKS IN DMA ZONE-03 |
| 294 | Designing, Supplying, Installing, commissioning & testing of CE & UL certified Electromagnatic flow Meter with Battery and data communication though GSM Module to PLC SCADA including pressure transducers fittings to facilitate the installation in remote places as specified in the specification of employers requirements for following line sizes- |
| 295 | 250 mm. dia For feeder line to DMA-1 |
| 296 | 250 mm. dia For feeder line to DMA-2 |
| 297 | 250 mm. dia For feeder line to DMA-3 |
| 298 | 200 mm. dia For feeder line to DMA-4 |
| 299 | 250 mm. dia For feeder line to DMA-5 |
| 300 | 350 mm. dia For feeder line to DMA-6 |
| 301 | Designing, Supplying, Installing, commissioning & testing of actuator operated CI/DI Globe Valve suitable for drinking water of followings Sizes- |
| 302 | 250 mm. dia For feeder line to DMA-1 |
| 303 | 250 mm. dia For feeder line to DMA-2 |
| 304 | 250 mm. dia For feeder line to DMA-3 |
| 305 | 200 mm. dia For feeder line to DMA-4 |
| 306 | 250 mm. dia For feeder line to DMA-5 |
| 307 | 350 mm. dia For feeder line to DMA-6 |
| 308 | Designing, Supplying, Installing, commissioning & testing of Pressure Transmitter Battery Operated CE marked with following technical parameters and Interfacing with PLC module alongwith data communication with SCADA System including Mounting arrangement. Output 4-20 mA / HART / RS 485 Power supply - 24V DC Display - 4\\" LED Accuracy - +/- 0.1 % of full scale or better Enclosure- IP 68 |
| 309 | Designing, Supplying, Installing, commissioning & testing of Battery operated Residual Chlorine Analyzer single parameter system ready to operate to measure free or total chlorine , Panel made of white PVC (hard foam core, 1100x350x13 mm) with mounting possibility, Pressure reducer, dosing valve for flow regulation, flow through armature, Optical flow measuring, Inlet and Outlet with 0.5\\" hose connection, Temp. 0-50 C, Single parameter controller with PID Controller, 2 current outputs, 3 relay outputs and RS 485 Interface, chlorine measuring sensor for free chlorine membrane covered sensor 0.01 - 2 mg/l , low ph dependency ph 4-9 , 0-50 C, 25 mm dia, 4-20 mA, connection cable 2m., 2-wire, 2 x stripped ends, tinned along with Battery & its required accessories for power backup for continuous operation complete for DMAs. |
| 310 | Providing ,erecting and commissioning of MS dismantling joint as per requirement and departments approved drawing and specifications, including machining and rubber ring and suitable for 16 kg/cm2 working pressure with required flanges of suitable side with nut and bolt etc. complete. The joint should have long bolts so that during normal working pressure there should be no sliding movement of sliding flanges LOF (length over flange) should not be less than 75% of dia.suitable for drinking water of followings Sizes- |
| 311 | 200 mm. dia |
| 312 | 250 mm. dia |
| 313 | 350 mm. dia |
| 314 | Installation, commissioning & testing trial for tubewell ZONE 1 |
| 315 | Installation, commissioning & testing trial for OHT ZONE -01 |
| 316 | SCADA /AUTOMATION WORK OF NEW/ EXISTING TUBEWELL ZONE-1 & NEW TUBEWELLS ZONE-02 |
| 317 | CE & UL Certifeid PLC/RTU in IP 54 enclousure suitable to communicate with GSM based modem unit with CPU and power supply with analog anddigital parameter and features as specifeid for tubewell to store and transmit data on GSm backbone RTU/PLC designed with logic to transfer data at multiple statiuonas specifeid. |
| 318 | GSM/GPRS based wireless communication with 4G modem for RTU/PLOc capable to transfer & gather data from remote site to controlstation all accessoreis included with signalenhancer antenna made for pumping plant internet charges as specifeid |
| 319 | CE/UL certifeid Intelligent Smart Energy Meter |
| 320 | CE/UL Certifeid Electromagnetic Flow Meter 100 mm size (mjp sor) |
| 321 | auto Phase reversal unit of 100 amp rating with inbuilt delay and enclosure control panel etc. |
| 322 | CE/UL certifeid Surge Protecter for control panel. |
| 323 | CE/UL Certifeid 7 hmi touch screen suitable to communication with PLC/RTU for display & control of process parameters |
| 324 | Complete cabling including power cables of all equipment. |
| 325 | control panel with IP54 protection ,industrial grade for all equipments.separate for control (24V) and power equipment with capacitor bank panel to improve power factor. |
| 326 | Installation, commissioning & testing trial for tubewell ZONE 2 |
| 327 | OHT AUTOMATION SYSTEM ZONE-01 |
| 328 | CE/UL certifeid Radar Type level transmitter for OHT. |
| 329 | SITC of UPS 10 kva 3phase suitable for operation of Actuators installed at outlet line in case of Power Failure at time of Distribution water supply |
| 330 | Lighting at Water works campus with solar panel and LED light of 3 sets |
| 331 | OHT AUTOMATION SYSTEM ZONE-02 |
| 332 | CE/UL certifeid Radar Type level transmitter for OHT. |
| 333 | SITC of UPS 10 kva 3phase suitable for operation of Actuators installed at outlet line in case of Power Failure at time of Distribution water supply |
| 334 | Lighting at Water works campus with solar panel and LED light of 3 sets |
| 335 | Installation, commissioning & testing trial for OHT |
| 336 | E/M WORKS IN DMA ZONE-01 |
| 337 | Designing, Supplying, Installing, commissioning & testing of CE & UL certified Electromagnatic flow Meter with Battery and data communication though GSM Module to PLC SCADA including pressure transducers fittings to facilitate the installation in remote places as specified in the specification of employers requirements for following line sizes- |
| 338 | 200 mm. dia For feeder line to DMA-1 |
| 339 | 200 mm. dia For feeder line to DMA-2 |
| 340 | Designing, Supplying, Installing, commissioning & testing of actuator operated CI/DI Globe Valve suitable for drinking water of followings Sizes- |
| 341 | 200 mm. dia For feeder line to DMA-1 |
| 342 | 200 mm. dia For feeder line to DMA-2 |
| 343 | Designing, Supplying, Installing, commissioning & testing of Pressure Transmitter Battery Operated CE marked with following technical parameters and Interfacing with PLC module alongwith data communication with SCADA System including Mounting arrangement. Output 4-20 mA / HART / RS 485 Power supply - 24V DC Display - 4\\" LED Accuracy - +/- 0.1 % of full scale or better Enclosure- IP 68 |
| 344 | Designing, Supplying, Installing, commissioning & testing of Residual Chlorine Analyzer single parameter system ready to operate to measure free or total chlorine , Panel made of white PVC (hard foam core, 1100x350x13 mm) with mounting possibility, Pressure reducer, dosing valve for flow regulation, flow through armature, Optical flow measuring, Inlet and Outlet with 0.5\\" hose connection, Temp. 0-50 C, Single parameter controller with PID Controller, 2 current outputs, 3 relay outputs and RS 485 Interface, chlorine measuring sensor for free chlorine membrane covered sensor 0.01 - 2 mg/l , low ph dependency ph 4-9 , 0-50 C, 25 mm dia, 4-20 mA, connection cable 2m., 2-wire, 2 x stripped ends, tinned along with Battery & its required accessories for power backup for continuous operation complete for DMAs. |
| 345 | Providing ,erecting and commissioning of MS dismantling joint as per requirement and departments approved drawing and specifications, including machining and rubber ring and suitable for 16 kg/cm2 working pressure with required flanges of suitable side with nut and bolt etc. complete. The joint should have long bolts so that during normal working pressure there should be no sliding movement of sliding flanges LOF (length over flange) should not be less than 75% of dia.suitable for drinking water of followings Sizes- |
| 346 | 200 mm. dia |
| 347 | E/M WORKS IN DMA ZONE-02 |
| 348 | Designing, Supplying, Installing, commissioning & testing of CE & UL certified Electromagnatic flow Meter with Battery and data communication though GSM Module to PLC SCADA including pressure transducers fittings to facilitate the installation in remote places as specified in the specification of employers requirements for following line sizes- |
| 349 | 200 mm. dia For feeder line to DMA-1 |
| 350 | 300 mm. dia For feeder line to DMA-2 |
| 351 | Designing, Supplying, Installing, commissioning & testing of actuator operated CI/DI Globe Valve suitable for drinking water of followings Sizes- |
| 352 | 200 mm. dia For feeder line to DMA-1 |
| 353 | 300 mm. dia For feeder line to DMA-2 |
| 354 | Designing, Supplying, Installing, commissioning & testing of Pressure Transmitter Battery Operated CE marked with following technical parameters and Interfacing with PLC module alongwith data communication with SCADA System including Mounting arrangement. Output 4-20 mA / HART / RS 485 Power supply - 24V DC Display - 4\\" LED Accuracy - +/- 0.1 % of full scale or better Enclosure- IP 68 |
| 355 | Designing, Supplying, Installing, commissioning & testing of Battery operated Residual Chlorine Analyzer single parameter system ready to operate to measure free or total chlorine , Panel made of white PVC (hard foam core, 1100x350x13 mm) with mounting possibility, Pressure reducer, dosing valve for flow regulation, flow through armature, Optical flow measuring, Inlet and Outlet with 0.5\\" hose connection, Temp. 0-50 C, Single parameter controller with PID Controller, 2 current outputs, 3 relay outputs and RS 485 Interface, chlorine measuring sensor for free chlorine membrane covered sensor 0.01 - 2 mg/l , low ph dependency ph 4-9 , 0-50 C, 25 mm dia, 4-20 mA, connection cable 2m., 2-wire, 2 x stripped ends, tinned along with Battery & its required accessories for power backup for continuous operation complete for DMAs. |
| 356 | Providing ,erecting and commissioning of MS dismantling joint as per requirement and departments approved drawing and specifications, including machining and rubber ring and suitable for 16 kg/cm2 working pressure with required flanges of suitable side with nut and bolt etc. complete. The joint should have long bolts so that during normal working pressure there should be no sliding movement of sliding flanges LOF (length over flange) should not be less than 75% of dia.suitable for drinking water of followings Sizes- |
| 357 | 200 mm. dia |
| 358 | 300 mm. dia |
| 359 | Three month Trial & Run |
| 360 | Three month Trial & Run Expenditure on hypo chloride solution and Chaukidar, Watch &Ward for Existing Tubwells zone 1 |
| 361 | Three month Trial & Run Expenditure on hypo chloride solution and Chaukidar, Watch &Ward for New Tubwells zone 2 |
| 362 | Three month Trial & Run Expenditure on hypo chloride solution and Chaukidar, Watch &Ward for New Tubwells zone 3 Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail