| 1 | SITC of GFRP street light pole of 9 Mtr height, Top dia min. 100 mm, bottom dia min. 190 mm with average thickness 5 mm, to withstand max, wind velocity 180 km/Hr. complete with all accessories required i/c 5/6 Amp MCB, terminal block and pole box cover is at least 2 Mtr height.a) Pole is made up of glass fibre in which fibre content is approx. 60-70 % by filament winding technique.b) GFRP anchor plate and base plate of suitable size and civil foundation as per design i/c dismantling the existing pole of any type (if present), after disconnecting electrical connection and making clear the site for the execution of work complete all specified and directed.c) GFRP pole of flange type having high longitudenal strength, UV inhibitor and complience ASTM D2343, D2344 stand and affixed id level to identify the pole.All colour designed is Ist approved by Engineer in charge |
| 2 | SITC of double side GFRP arm bracket of length 1 Mtr. having minimum thickness 5mm to withstand wind velocity 180Km/hr. |
| 3 | SITC of Single side GFRP arm bracket of length 1 Mtr. having minimum thickness 5mm to withstand wind velocity 180Km/hr. |
| 4 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 5 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 6 | Supplying and laying of following PVC insulated and PVC sheathed /XPLE armounrd Aluminum Conductor power cable of 1.1 KV grade of following size in the existing RCC/ HUME/DWC/METAL pipe as required. |
| 7 | 4 X 25 Sq. mm armounrd Aluminum conductor power cable |
| 8 | 4 X 16 Sq. mm armounrd Aluminum conductor power cable |
| 9 | 3.5 X 50 Sq. mm armounrd Aluminum conductor power cable |
| 10 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥120 <135 lm/Watt)Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report CCT 3000°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 11 | 150 watt |
| 12 | Supply of factory assembled outdoor type hut shaped double door Timer Panel dust & vermin proof powder coated with degree of protection of IP 54 self supported suitable for 3 phase 4 wire, 415 volt AC supply approximate dimension 1350 mm (H), 2200 mm (W) and 300 mm (D) fabricated out of 2mm thick CRCA sheet with locking arrangement i/c 3 mm thick sheet in bottom for gland plates, supplying & fixing following accessories as mentioned below i/c 400 AMP Aluminum bus bars inter connection, arrangement for cable entry/support/ termination 2 Nos. earthing stud inter connection with 25mm x 5mmm Copper strip (externally) 50mm x 50mm x 6mm MS angle iron base frame duly welded 100cm long welded with 4 Nos legs for grouting in foundation i/c painting, Pdg. of 1:3:6 (1 Cement : 3 Coarse sand : 6 Aggregate stone 20mm nominal size) foundation (600mm below the ground level and 400mm above the ground level) it should be covered with Aprin plate (400mm above the ground) not less than 3 mm thick etc. complete with Smart Field Device (SFD) having Processor, Electrical Parameters Measurement of entire lighting system, Fault Detection, Feeder point Switching, Analog and Digital Inputs/Outputs, Electrical Metering, Battery backup with Battery Management System for SFD system, Power Module, Live Supervision and control of feeder capability etc., with system protection accessories and communication system to connect to cloud computing based secured data Centre having following (a) Smart Field Device with inbuilt RTC, Relay modules and SIM - 1 Set(b) Multi functional 3-phase digital Energy Meter (measure voltage, current, power factor, active/reactive power, energy consumption etc.) - 5 Set (..........................Cont.........................) |
| 13 | (c) Transformer based power supply with 2KV isolation surge protection input side, 12V surge protection output side - 1 Set(d) SP/DP Control MCBs, Surge protection Device, Battery Management System, Battery Backup with Lithium Battery, Over Voltage and Under Voltage Protection, Door Tamper Sensor, 4G SIM, Cloud charger and software & Cloud Maintenance for 1 Year- 1 Jobi/c dismantling and credit of old defective feeder pillar disconnection of all connected cables and buyback for the same complete with dressing of cables and cutting of unused cables complete as per direction of engineer in charge or his representative as required.INCOMING:- 250 Amps, 35/36KA 4 Pole TM MCCB with Ics=100%Icu -01 NosRed, Yellow & blue LED for Phase and LEDs for ON, OFF and Trip Indicating lamps with protection MCBs -01 NosOUTGOING:- 125 Amps, 35/36KA 4 Pole TM MCCB with Ics=100%Icu -05 Nos. 130 A FP AC-1 Duty Power Contactor-05 Nos. ON, OFF and Trip Indicating lamps with protection MCBs -05 Nos. Danger notice plate -01 Nos. |
| 14 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 15 | Fabricating, Supplying and fixing wire mesh protection frame work made out of 40 x 40 mm x 6 mm thick angle and \\"T\\" strengthened with intermediate menberers of MS flat iron of size 32 x 6 mm x 5 mm thick welded at a distance of 30 cm horizontally and vertically and duly welded with wiremesh of size 75 mm x 25 mm made with 6 SWG wire mesh of size 75 mm x 25 mm made with 6 SWG wire on all sides and top i/c providing and fixing of double door gate with double locking arrangement ( Two nos. sliding bolts and one No. go down lock) having 0.5 mtr long legs of 40 mm x 40 mm x 6 mm thick angles iron, duly grouted in cement concrete foundation ration 1:2:4 (1 cement : 2 coarse sand: 4 graded stone aggregate) upto suitable depth painting with on coast of red oxide & two coats of synthetic enamel paint of approval colour and shade etc. complete as reqd. Please Enable Macros to View BoQ information |