Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | ADMINISTRATIVE MAIN BLOCK |
| 2 | DOWN COMER WITH WET RISER /EXTERNAL HYDRANT SYSTEM |
| 3 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required |
| 4 | 150 mm dia |
| 5 | 100 mm dia |
| 6 | Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of50 m |
| 7 | Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia |
| 8 | Supplying and fixingfirst aid HoseReel with MS construction spray painted n postofficered,conformingtoIS884completewiththefollowingasrequired.20mm nominal internal dia water hose thermoplastic(Textile reinforced) type -2 as per IS: 1258520mm nominal internal dia gunmetal globe valve&nozzle.Drum and brackets for fixing the equipmets on wall.Connections fromriser with 25mm dia stop gunmetal valve & M.S. Pipe and socket 30M |
| 9 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required |
| 10 | Single headed Stainless steel |
| 11 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required |
| 12 | Gun Metal |
| 13 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required |
| 14 | Stainless Steel (Grade 304) |
| 15 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required 150 mm dia |
| 16 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required |
| 17 | 100mm dia |
| 18 | 150mm dia |
| 19 | Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required |
| 20 | 150 mm dia |
| 21 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shadeas required. |
| 22 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 23 | Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump) |
| 24 | Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 |
| 25 | Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325. |
| 26 | M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. (d) Suitable cement concrete foundation duly plastered |
| 27 | 900 lpm at 35 m Head |
| 28 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required |
| 29 | 4 way-150 mm dia M.S. Pipe |
| 30 | Providing & fixing of FHC(NewAge Fire Hose Cabinet (Double door) (FRP) Including cost of materials and labour etc complete .Excluding cost of pipe . |
| 31 | Providing&fixing of Exit sign Board Including cost of materials and labour etc complete . |
| 32 | Providing&fixing of Terrace motor covering Including cost of M.S.angle and profile sheet materials and labour etc complete . |
| 33 | PVC TANK AND MOTOR FIXING FOUNDATION |
| 34 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc.External work |
| 35 | 80 mm dia nominal bore |
| 36 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end): |
| 37 | 80 mm nominal bore |
| 38 | AUTOMATIC FIRE ALARM AND P.A. SYSTEM |
| 39 | Supplying, installation, testing & commissioning of manual callboxes of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required. |
| 40 | Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S. box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required. |
| 41 | Supplying, installation, testing & commissioning talk back slavestation in surface/recess suitable for operation on simplex mode complete with P.T.T. knob & speaker/microphoneenclosed in a M.S.(16 SWG)/ ABS box with break glass in front etc. complete as required. |
| 42 | Supply, installation, testing and commissioning of 25 mm Outer dia CPVC PIPE with end caps including making air sampling opening of appropriate dia on appropriate interval and allaccessories as required,(rate for area protected in sqm). |
| 43 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. |
| 44 | Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required. |
| 45 | speaker cable Single pair, 2-core, 1.5 sqmm |
| 46 | Supplying, installation, testing & commissioning sector panel suitable for following zones, complete with visual indications for short circuit fault, open circuit fault, fire condition and all otherstandard facilities as per IS:2189 with mimic diagram for all area/zone covered, complete with all connections, interconnections as required. |
| 47 | 10 Zone |
| 48 | Supplying, installation, testing & commissioning of main control and indicating panel made out of 16 SWG MS sheet to accommodate the following items duly powder coated in approved colour with louvers for ventilation, locking arrangement, audio and visual indication for fire alarm and public address system, monitoring system including connections, interconnections etc complete as required. |
| 49 | 6 zone panel for fire alarm system |
| 50 | 100 watt amplifier racks suitable for operation on 230V AC/24V DC supply conforming to IEC-268-3 complete with all |
| 51 | Talk back master station with LED PTT (press to talk) push button for operation on 230V AC/24 V DC supply conformingto IEC-268 for simplex mode of operation/communication suitable for 20 Nos.talk back unit -1 set. Annoucement control desk suitable for selection of different zones selectively and ON ALL CALL switch with visual indication etc., complete as required- 1 set. Amplifier change over switch for inter changing amplifier- 1 No. Monitor panel for loudspeaker complete output selector ON/OFF switch, fuse visual indications etc. complete as required- 1 No. Gooseneck microphone with stand and ON/OFF switch -1 No.Mains ON/OFF switch, fuse indication lamps, DC and AC voltmeters & ammeters terminal blocks etc. complete as required -1 set. Battery charger trickle cum boost to take complete load offire alarm & PA system complete with all accessories including providing & fixing of 2 nos. 12 volt,30 AH each sealed maintenance free batteries -1 set. |
| 52 | Supplying, installation, testing & commissioning of heat detector operating at 54ºC/57ºC with rate of rise cum fixed temperature (dual thermistor) type with mounting base complete with all connection etc. as required. |
| 53 | Supplying, installation, testing & commissioning of smoke detector with builtin LED and mounting base complete with all connections etc. as required. |
| 54 | Supplying, installation, testing & commissioning response indicator on surface/recess MS box having two LEDs metallic cover complete with all connections etc. as required. |
| 55 | PUBLIC ADDRESS SYSTEM |
| 56 | Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete asrequired. |
| 57 | Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required. |
| 58 | Supplying, installation, testing & commissioning of digital audio amplifier 50 Watt, 25V rms operating at 240 volt AC supply complete as required. |
| 59 | Supplying, installation, testing & commissioning of exit point directional sound speaker with voice and integral audio amplifier with selectable sound pulse patterns complete as required. |
| 60 | Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assemblycomplete as required. |
| 61 | FIRE EXTINGUISHER |
| 62 | Supply and fixing of fire extinguiser ,ABC Type 6.0 kg capacity (ISI Marked IS : 15683 & TAC approved (complete with initial charge and wall bracket ,along with supply of all materials and labour for proper completion of work |
| 63 | Supply and fixing of fire extinguiser ,CO2 Type 4.5 kg capacity (ISI Marked IS : 2878 & TAC approved (complete with initial charge and wall bracket ,along with supply of all materials and labour for proper completion of work. |
| 64 | Supply and fixing of fire bucket 9-11 litres capacity with river sand fill supply of all materials and labour for proper completion of work. |
| 65 | SITC of Emergency light 12 V DC 230 V AC ,Chargable in building complete as per required . |
| 66 | Supply and fixing of power plug with 15A/250 volt flush type switch and 5 pin 15A/250V flush type universal socket in suitable M.S. box of 175mm x 100mm x 50mm size with phenolic laminated bakelite sheet cover 3mm thick fixed with brass machine screw and cup washer. |
| 67 | Supply and laying of 1800mm x 900mm x 12mm thick chequered rubbbber matting of tested quality. |
| 68 | INTELLIGENT FIRE ALARM SYSTEM |
| 69 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5 % V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories. The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. |
| 70 | Ten loop panel |
| 71 | Two loop panel |
| 72 | Supplying, installation, testing & commissioning of central graphical fire alarm management system to centrally monitor and operate the fire alarm system complete as required. |
| 73 | Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required. |
| 74 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
| 75 | Supplying, installation, testing & commisssioning of intelligent addressable programmable sounder complete as required. |
| 76 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
| 77 | Supplying, installation, testing & commissioning of intelligent aspiration detector for area coverage of minimum 5000 sq. ft. complete as required. |
| 78 | Supplying, instalation testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed temproaturns thermistor complete with base as required. |
| 79 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. |
| 80 | Supplying, installation, testing & commissioning of addressable phone control module complete as required. |
| 81 | Supplying, installation, testing & commissioning of addressable beam detector with short croult isolator (inbull of seperate) complete with emitter and receiver including connections with remoto test features etc completa as required |
| 82 | Supplying, installation, testing & commissioning of intelligent addressable duct detector including suitable Photo detector complete with base as required. |
| 83 | Supplying, instalation testing & commissioning of addressable manual call point complete as required |
| 84 | Supplying, installation, testing & commissioning of addressable horm cum strobe complete as required. |
| 85 | Supplying, installation, testing & commissioning of addressable. strobe complete as required. |
| 86 | Supplying, installation, testing & commissioning of fire fighter telephone handset complete as required. |
| 87 | Supplying, installation, testing & commissioning of intelligent interface unit BACnet/ Modbus protocol i.e. supplying communication links between building management system and fire. alarm control panel complete as required. |
| 88 | Supplying, installation testing & commissioning of fire fighter phone jack complete as required |
| 89 | ELECTRICAL WORK |
| 90 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cablerun shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 91 | 10 sq. mm 4 core |
| 92 | Supply & fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respects. The armouring of the cable shall be properly connected with the earth as per dire |
| 93 | 10 sq. mm 4 core |
| 94 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 95 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 96 | S&F of 200 Amp. four pole change over switch on 50mm x 50mm x 6mm angle iron frame, including the cost of labour, T&P, painting and other material required for proper completion of the work as per direction and satisfaction ofEngineer in charge. |
| 97 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 98 | Supply and laying of 25 mm x 5 mm G.I. strip from earth electrode directly in the ground as required complete in all respect. |
| 99 | FIRE SPRINKLER SYSTEM |
| 100 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required |
| 101 | 150 mm dia |
| 102 | 100 mm dia |
| 103 | 80 mm dia |
| 104 | 65 mm dia |
| 105 | 50 mm dia |
| 106 | 25 mm dia |
| 107 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. |
| 108 | 150mm |
| 109 | 100mm |
| 110 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories : |
| 111 | Pendent Sprinkler |
| 112 | Upright Sprinkler |
| 113 | Cutting holes up to 15x15 cm in R.C.C. floors and roofs for passing drain pipe etc. and repairing the hole after insertion of drain pipe etc. with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), including finishing complete so as to make it leak proof. |
| 114 | Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, centerbracket, stockbar of following sizes complete as required. |
| 115 | Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required |
| 116 | 150 mm dia |
| 117 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. |
| 118 | Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required. |
| 119 | TEACHING BLOCK |
| 120 | DOWN COMER WITH WET RISER /EXTERNAL HYDRANT SYSTEM |
| 121 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required |
| 122 | 150 mm dia |
| 123 | 100 mm dia |
| 124 | Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of50 m |
| 125 | Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia |
| 126 | Supplying and fixingfirst aid HoseReel with MS construction spray painted n postofficered,conformingtoIS884completewiththefollowingasrequired.20mm nominal internal dia water hose thermoplastic(Textile reinforced) type -2 as per IS: 1258520mm nominal internal dia gunmetal globe valve&nozzle.Drum and brackets for fixing the equipmets on wall.Connections fromriser with 25mm dia stop gunmetal valve & M.S. Pipe and socket |
| 127 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required |
| 128 | Single headed Stainless steel |
| 129 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required |
| 130 | Gun Metal |
| 131 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required |
| 132 | Stainless Steel (Grade 304) |
| 133 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required |
| 134 | 150 mm dia |
| 135 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required |
| 136 | 100mm dia |
| 137 | 150mm dia |
| 138 | Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required |
| 139 | 150 mm dia |
| 140 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shadeas required. |
| 141 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 142 | Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump) |
| 143 | Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 |
| 144 | Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325. |
| 145 | M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. (d) Suitable cement concrete foundation duly plastered |
| 146 | 900 lpm at 35 m Head |
| 147 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required |
| 148 | 4 way-150 mm dia M.S. Pipe |
| 149 | Providing & fixing of FHC(NewAge Fire Hose Cabinet (Double door) (FRP) Including cost of materials and labour etc complete .Excluding cost of pipe . |
| 150 | Providing&fixing of Exit sign Board Including cost of materials and labour etc complete . |
| 151 | Providing&fixing of Terrace motor covering Including cost of M.S.angle and profile sheet materials and labour etc complete . |
| 152 | PVC TANK AND MOTOR FIXING FOUNDATION |
| 153 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc.External work |
| 154 | 80 mm dia nominal bore |
| 155 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end): |
| 156 | 80 mm nominal bore |
| 157 | AUTOMATIC FIRE ALARM AND P.A. SYSTEM |
| 158 | Supplying, installation, testing & commissioning of manual callboxes of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required. |
| 159 | Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S. box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required. |
| 160 | Supplying, installation, testing & commissioning talk back slavestation in surface/recess suitable for operation on simplex mode complete with P.T.T. knob & speaker/microphoneenclosed in a M.S.(16 SWG)/ ABS box with break glass in front etc. complete as required. |
| 161 | Supply, installation, testing and commissioning of 25 mm Outer dia CPVC PIPE with end caps including making air sampling opening of appropriate dia on appropriate interval and allaccessories as required,(rate for area protected in sqm). |
| 162 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. |
| 163 | Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required. |
| 164 | speaker cable Single pair, 2-core, 1.5 sqmm |
| 165 | Supplying, installation, testing & commissioning sector panel suitable for following zones, complete with visual indications for short circuit fault, open circuit fault, fire condition and all otherstandard facilities as per IS:2189 with mimic diagram for all area/zone covered, complete with all connections, interconnections as required. |
| 166 | 10 Zone |
| 167 | Supplying, installation, testing & commissioning of main control and indicating panel made out of 16 SWG MS sheet to accommodate the following items duly powder coated in approved colour with louvers for ventilation, locking arrangement, audio and visual indication for fire alarm and public address system, monitoring system including connections, interconnections etc complete as required. |
| 168 | 6 zone panel for fire alarm system |
| 169 | 100 watt amplifier racks suitable for operation on 230V AC/24V DC supply conforming to IEC-268-3 complete with all |
| 170 | Talk back master station with LED PTT (press to talk) push button for operation on 230V AC/24 V DC supply conformingto IEC-268 for simplex mode of operation/communication suitable for 20 Nos.talk back unit -1 set. Annoucement control desk suitable for selection of different zones selectively and ON ALL CALL switch with visual indication etc., complete as required- 1 set. Amplifier change over switch for inter changing amplifier- 1 No. Monitor panel for loudspeaker complete output selector ON/OFF switch, fuse visual indications etc. complete as required- 1 No. Gooseneck microphone with stand and ON/OFF switch -1 No.Mains ON/OFF switch, fuse indication lamps, DC and AC voltmeters & ammeters terminal blocks etc. complete as required -1 set. Battery charger trickle cum boost to take complete load offire alarm & PA system complete with all accessories including providing & fixing of 2 nos. 12 volt,30 AH each sealed maintenance free batteries -1 set. |
| 171 | Supplying, installation, testing & commissioning of heat detector operating at 54ºC/57ºC with rate of rise cum fixed temperature (dual thermistor) type with mounting base complete with all connection etc. as required. |
| 172 | Supplying, installation, testing & commissioning of smoke detector with builtin LED and mounting base complete with all connections etc. as required. |
| 173 | Supplying, installation, testing & commissioning response indicator on surface/recess MS box having two LEDs metallic cover complete with all connections etc. as required. |
| 174 | PUBLIC ADDRESS SYSTEM |
| 175 | Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete asrequired. |
| 176 | Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required. |
| 177 | Supplying, installation, testing & commissioning of digital audio amplifier 50 Watt, 25V rms operating at 240 volt AC supply complete as required. |
| 178 | Supplying, installation, testing & commissioning of exit point directional sound speaker with voice and integral audio amplifier with selectable sound pulse patterns complete as required. |
| 179 | Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assemblycomplete as required. |
| 180 | FIRE EXTINGUISHER |
| 181 | Supply and fixing of fire extinguiser ,ABC Type 6.0 kg capacity (ISI Marked IS : 15683 & TAC approved (complete with initial charge and wall bracket ,along with supply of all materials and labour for proper completion of work |
| 182 | Supply and fixing of fire extinguiser ,CO2 Type 4.5 kg capacity (ISI Marked IS : 2878 & TAC approved (complete with initial charge and wall bracket ,along with supply of all materials and labour for proper completion of work. |
| 183 | Supply and fixing of fire bucket 9-11 litres capacity with river sand fill supply of all materials and labour for proper completion of work. |
| 184 | SITC of Emergency light 12 V DC 230 V AC ,Chargable in building complete as per required . |
| 185 | Supply and fixing of power plug with 15A/250 volt flush type switch and 5 pin 15A/250V flush type universal socket in suitable M.S. box of 175mm x 100mm x 50mm size with phenolic laminated bakelite sheet cover 3mm thick fixed with brass machine screw and cup washer. |
| 186 | Supply and laying of 1800mm x 900mm x 12mm thick chequered rubbbber matting of tested quality. |
| 187 | INTELLIGENT FIRE ALARM SYSTEM |
| 188 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5 % V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories. The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. |
| 189 | Ten loop panel |
| 190 | Two loop panel |
| 191 | Supplying, installation, testing & commissioning of central graphical fire alarm management system to centrally monitor and operate the fire alarm system complete as required. |
| 192 | Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required. |
| 193 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
| 194 | Supplying, installation, testing & commisssioning of intelligent addressable programmable sounder complete as required. |
| 195 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
| 196 | Supplying, installation, testing & commissioning of intelligent aspiration detector for area coverage of minimum 5000 sq. ft. complete as required. |
| 197 | Supplying, instalation testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed temproaturns thermistor complete with base as required. |
| 198 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. |
| 199 | Supplying, installation, testing & commissioning of addressable phone control module complete as required. |
| 200 | Supplying, installation, testing & commissioning of addressable beam detector with short croult isolator (inbull of seperate) complete with emitter and receiver including connections with remoto test features etc completa as required |
| 201 | Supplying, installation, testing & commissioning of intelligent addressable duct detector including suitable Photo detector complete with base as required. |
| 202 | Supplying, instalation testing & commissioning of addressable manual call point complete as required |
| 203 | Supplying, installation, testing & commissioning of addressable horm cum strobe complete as required. |
| 204 | Supplying, installation, testing & commissioning of addressable. strobe complete as required. |
| 205 | Supplying, installation, testing & commissioning of fire fighter telephone handset complete as required. |
| 206 | Supplying, installation, testing & commissioning of intelligent interface unit BACnet/ Modbus protocol i.e. supplying communication links between building management system and fire. alarm control panel complete as required. |
| 207 | Supplying, installation testing & commissioning of fire fighter phone jack complete as required |
| 208 | ELECTRICAL WORK |
| 209 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cablerun shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 210 | 10 sq. mm 4 core |
| 211 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 212 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 213 | Supply & fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respects. The armouring of the cable shall be properly connected with the earth as per dire |
| 214 | 10 sq. mm 4 core |
| 215 | S&F of 200 Amp. four pole change over switch on 50mm x 50mm x 6mm angle iron frame, including the cost of labour, T&P, painting and other material required for proper completion of the work as per direction and satisfaction ofEngineer in charge. |
| 216 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 217 | Supply and laying of 25 mm x 5 mm G.I. strip from earth electrode directly in the ground as required complete in all respect. |
| 218 | FIRE SPRINKLER SYSTEM |
| 219 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required |
| 220 | 150 mm dia |
| 221 | 100 mm dia |
| 222 | 80 mm dia |
| 223 | 65 mm dia |
| 224 | 50 mm dia |
| 225 | 25 mm dia |
| 226 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. |
| 227 | 150mm |
| 228 | 100mm |
| 229 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories : |
| 230 | Pendent Sprinkler |
| 231 | Upright Sprinkler |
| 232 | Cutting holes up to 15x15 cm in R.C.C. floors and roofs for passing drain pipe etc. and repairing the hole after insertion of drain pipe etc. with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), including finishing complete so as to make it leak proof. |
| 233 | Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, centerbracket, stockbar of following sizes complete as required. |
| 234 | Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required |
| 235 | 150 mm dia |
| 236 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. |
| 237 | Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required. |
| 238 | SMOKE EXTRACTOR SYSTEM |
| 239 | VANE / TUBE AXIAL FLOW FRESH AIR FAN Supply, Installation, Testing & Commissioning of NORMAL & SMOKE SPILL direct driven VANE / TUBE AXIAL FLOW FRESH AIR FAN. Fan shall be AMCA Certified (For Air and Sound Performance).Fan motor shall be suitable for 415 ± 10% volts, 50 cycles, 3 phase power supply of class 'F' insulation. The fan shall be equipped with mounting bracket & spring isolators for the installation of the fans.. Fan shall be with fire proof flexible connection at inlet and outlet..Emergency Fans shall be activated from fire signal from fire alarm system Fan static pressure shall be as indicated but actual fan static pressure to be checked by vendor.All tube/vane axial fans motors in Normal operation shall be of minimum IE3 efficiency and in Emergency fans shall be of minimum IE2 efficiency. Fan total efficiency should not be less than 70 %, noise level should not be more than 80 dbA @ 3 m distance for normal operation fans and 85 dbA @ 3 m distance for emergency operation fans when measured in hemisperical reverberant room conditions. Sound attenutors of appropriate length shall be included in the cost to achieve the desired result. Note:- 1. The motor for fresh air supply shall be F class insulation with 4/6 pole & IP-55 protection. 2. Normal case supply & exhaust shall be vane axial type. 3. Smoke case supply and exhuast fan shall be tube axial type. |
| 240 | Duty : Normal/Smoke Case Fresh Air |
| 241 | Air Quantity : 13000 CFM |
| 242 | Static Pressure : 20 mm wg |
| 243 | Duty : Normal/Smoke Case Fresh Air |
| 244 | Air Quantity : 23000 CFM |
| 245 | Static Pressure : 20 mm wg |
| 246 | Duty : Normal/Smoke Case Fresh Air |
| 247 | Air Quantity : 27000 CFM |
| 248 | Static Pressure : 20 mm wg |
| 249 | Duty : Normal/Smoke Case Fresh Air |
| 250 | Air Quantity : 31000 CFM |
| 251 | Static Pressure : 20 mm wg |
| 252 | Duty : Normal/Smoke Case Fresh Air |
| 253 | Air Quantity : 36000 CFM |
| 254 | Static Pressure : 20 mm wg |
| 255 | Duty : Normal/Smoke Case Fresh Air |
| 256 | Air Quantity : 42000 CFM |
| 257 | Static Pressure : 20 mm wg |
| 258 | VANE / TUBE AXIAL FLOW EXHAUST AIR FAN |
| 259 | Supply, Installation, Testing & Commissioning of NORMAL & SMOKE SPILL direct driven VANE / TUBE AXIAL FLOW EXHAUST AIR FAN. Fan shall be AMCA Certified (For Air and Sound Performance).Fan motor shall be suitable for 415 ± 10% volts, 50 cycles, 3 phase power supply of class 'F' insulation. The fan shall be equipped with mounting bracket & spring isolators for the installation of the fans.. Fan shall be with fire proof flexible connection at inlet and outlet..Emergency Fans shall be activated from fire signal from fire alarm system Fan static pressure shall be as indicated but actual fan static pressure to be checked by vendor.All tube/vane axial fans motors in Normal operation shall be of minimum IE3 efficiency and in Emergency fans shall be of minimum IE2 efficiency. Fan total efficiency should not be less than 70 %, noise level should not be more than 80 dbA @ 3 m distance for normal operation fans and 85 dbA @ 3 m distance for emergency operation fans when measured in hemisperical reverberant room conditions. Sound attenutors of appropriate length shall be included in the cost to achieve the desired result. Note:- 1. The motor for fresh air supply shall be F class insulation with 4/6 pole & IP-55 protection. 2. Normal case supply & exhaust shall be vane axial type. 3. Smoke case supply and exhuast fan shall be tube axial type. |
| 260 | Duty : Normal/Smoke Case Exhaust Air |
| 261 | Air Quantity : 11500 CFM |
| 262 | Static Pressure : 20 mm wg |
| 263 | Duty : Normal/Smoke Case Exhaust Air |
| 264 | Air Quantity : 21000 CFM |
| 265 | Static Pressure : 20 mm wg |
| 266 | Duty : Normal/Smoke Case Exhaust Air |
| 267 | Air Quantity : 24000 CFM |
| 268 | Static Pressure : 20 mm wg |
| 269 | Duty : Normal/Smoke Case Exhaust Air |
| 270 | Air Quantity : 28000 CFM |
| 271 | Static Pressure : 20 mm wg |
| 272 | Duty : Normal/Smoke Case Exhaust Air |
| 273 | Air Quantity : 33000 CFM |
| 274 | Static Pressure : 20 mm wg |
| 275 | Duty : Normal/Smoke Case Exhaust Air |
| 276 | Air Quantity : 38000 CFM |
| 277 | Static Pressure : 20 mm wg |
| 278 | Inline Fan |
| 279 | Supplying, installing, testing and commissioning of INLINE FANS suitable for installing in any position in vertical or horizontal ducts. The casing shall be double skin, internally acoustically lined and constructed of galvanised steel. The fan shall be DIDW/SISW with forward / backward curve impeller fitted with maintenance free external rotor motor. The motor shall be suitable for 220±10% / 415±10% volt single/three phase 50 cycles AC supply. Quoted price shall be inclusive of DOL starter panel with cabling between starter panel and fan. |
| 280 | The fan shall have low sound level exceeding not more than 55 DBA at three metre distance. |
| 281 | Static Pressure of fan shall be 20 mm of wg. |
| 282 | Fan Selection arrangement shall be as follows: |
| 283 | 600 CFM @ 15 mm S.P. |
| 284 | 400 CFM @ 15 mm S.P. |
| 285 | 200 CFM @ 15 mm S.P. |
| 286 | DUCTING, GRILLS, DIFFUSER AND INSULATION |
| 287 | Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. |
| 288 | Thickness 0.63 mm sheet |
| 289 | Thickness 0.80 mm sheet |
| 290 | Thickness 1.00 mm sheet |
| 291 | Thickness 1.20 mm sheet |
| 292 | Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications. |
| 293 | Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications. |
| 294 | Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required. |
| 295 | Supplying & fixing of fire rated canvass cloth for flexble connection between plenum box & Fresh/Exhaust Air duction to smooth operation and noise balancing as per specification & complete in all respect. |
| 296 | PUMPING SYSTEM |
| 297 | PUMPING SYSTEM |
| 298 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required |
| 299 | 200 mm dia (wall thickness 6.3 mm) |
| 300 | 150 mm dia |
| 301 | Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of50 m |
| 302 | Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia |
| 303 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required |
| 304 | 150 mm dia |
| 305 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required |
| 306 | 150mm dia |
| 307 | Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required |
| 308 | 150 mm dia |
| 309 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shadeas required. |
| 310 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required |
| 311 | 4 way-150 mm dia M.S. Pipe |
| 312 | Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automaticoperation and consisting of following, complete in all respects, as required |
| 313 | Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. |
| 314 | Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. |
| 315 | M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.Suitable cement concrete foundation duly plastered |
| 316 | 2850 lpm at 70 m Head |
| 317 | Supplying, installation, testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel DrivenPump) |
| 318 | Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. |
| 319 | Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. |
| 320 | M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. |
| 321 | 2850 lpm at 70 m Head |
| 322 | Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following,complete in all respects, as required : (Jockey Pump) |
| 323 | Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520. |
| 324 | Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS : 325. |
| 325 | M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. |
| 326 | 180 lpm at 70 m Head |
| 327 | CONTROL PANELS |
| 328 | Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect,suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required |
| 329 | INCOMING |
| 330 | 630A, 50kA 4 Pole MCCB, Ics=100% Icu rating Digital Voltmeter 0-500V with selector switchAmmeter (0-630 A) with selector swtich & CTs etc.LEDtypeRYBphaseindicatinglamps,ON,OFF,tripindicating lampsSet of Copper Bus Bar 800Amps |
| 331 | OUTGOING |
| 332 | Main Fire Pump |
| 333 | 250 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 100 HP pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. |
| 334 | Jockey Pump |
| 335 | 125 A, 50kA TPN MCCB, Ics=100% Icu, with suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. |
| 336 | DIESEL ENGINE CONTROL |
| 337 | Control for diesel engine comprising -Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual modeIndicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0- 20 A DC AmmeterAll standard relays and accessories for automatic operation of diesel engineSystem Controller Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification |
| 338 | Providing & fixing of pressures witch in M .S.pipe line including connection etc. as required |
| 339 | Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required. |
| 340 | 150mm |
| 341 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm thick sand all around and protected with burat bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 342 | 120sq.mm3-1/2 core |
| 343 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc.External work |
| 344 | 80 mm dia nominal bore |
| 345 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end): |
| 346 | 80 mm nominal bore |
| 347 | UNDER GROUND TANK 100KL |
| 348 | Earth work in excavation by mechanical means (Hydraulic excavator) /manual means over areas (exceeding 30cm in depth. 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50m and lift up to 1.5m, disposed earth to be levelled and neatly dressed. |
| 349 | All kinds of soil |
| 350 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 351 | 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40mm nominal size) |
| 352 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cementconcrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana /Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate /retard setting of concrete, to improve durability and workability without impairing strength; including pumping ofconcrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing andreinforcement as per direction of the engineer-in-charge; for the following grades of concrete.Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately.In case the cement content in design mix is more than 110% of the specified minimum cement content, thecontractor shall have discretion to either re-design the mix or bear the cost of extra cement. |
| 353 | Concrete of M30 grade with minimum cement content of 350 kg /cum |
| 354 | UP TO PLINTH |
| 355 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level. |
| 356 | Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 357 | Centering and shuttering including strutting, propping etc. and removal of form for |
| 358 | Suspended floors, roofs, landings, balconies and access platform with water proof ply 12 mm thick |
| 359 | Lintels, beams, plinth beams, girders, bressumers andcantilevers |
| 360 | Column |
| 361 | PUMPROOM |
| 362 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation M-150 in superstructure above plinth level up to floor V level in all shapes and sizes in : |
| 363 | Cement mortar 1:4 (1 cement : 4 coarse sand) |
| 364 | R.C.C. work in beams, suspended floors, roofs having slope up to 15 ° landings, balconies, shelves, chajjas, lintles, bands, plain window sills, staircases and spiral staircases above plinth level up to floor five level excluding the cost of centring, shuttering, finishing and rainforcement with 1:1.5:3 (1 cement : 1.5 coarce sand including manufactured sand derived from recycled concrete Aggregate (RCA) upto 20% 3 graded stone aggregate 20 mm nominal size derived from natural source). |
| 365 | LINEL BAND |
| 366 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level. |
| 367 | Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 368 | Centering and shuttering including strutting, propping etc. and removal of form for |
| 369 | Lintels, beams, plinth beams, girders, bressumers andcantilevers |
| 370 | Lintels, beams, plinth beams, girders, bressumers andcantilevers |
| 371 | Suspended floors, roofs, landing, beams and balconies (Plan area to be measured) 1 |
| 372 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) Non-decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters. |
| 373 | 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws |
| 374 | Providing and fixing angle iron frames for doors, windows and ventilators of mild steel Angle sections of size 35x35x5 mm, joints mitred and welded by angle iron 35x35x5 mm or 35x 5 mm flat pieces to the existing T-iron frame or to the wall with dash fastener, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer, all complete as per the direction of Engineer-In-charge. |
| 375 | 40x40x5 |
| 376 | Providing and fixing factory made ISI marked steel glazed doors, windows and ventilators, side /top/centre hung, with beading and all members such as F7D,F4B, K11 B and K12 B etc. complete ofstandard rolled steel sections, joints mitred and flash butt welded and sash bars tenoned and riveted,including providing and fixing of hinges, pivots, including priming coat of approved steel primer, butexcluding the cost of other fittings, complete all as per approved design, (sectional weight of only steelmembers shall be measured for payment). |
| 377 | Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block 15x10x10 cm of C.C.1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) |
| 378 | 12 mm cement plaster of mix : |
| 379 | 1:6 (1 cement: 6 coarse sand) |
| 380 | 1:6 (1 cement: 6 coarse sand) |
| 381 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete. |
| 382 | 40 mm thick with 20 mm nominal size stone aggregate |
| 383 | Cement plaster skirting up to 30 cm height, with cement mortar 1:3 (1 cement : 3 coarse sand),finished with a floating coat of neat cement. |
| 384 | 18 mm thick |
| 385 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete. |
| 386 | 40 mm thick with 20 mm nominal size stone aggregate |
| 387 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 388 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 389 | Finishing walls with Acrylic Smooth exterior paint of required shade : |
| 390 | New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm) |
| 391 | Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gram/litre, of approved manufacturer and of requiredshade and colour all complete to achieve even shade and colour : |
| 392 | New work (two or more coats) over and including water thinnable priming coat with cement primer having VOC contentless than 50 gram/litre |
| 393 | Providing and applying white cement based putty of average thickness1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 394 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications : |
| 395 | Painting wood work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and manufacture |
| 396 | Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and manufacture |
| 397 | Providing and fixing aluminium sliding door bolts, ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, withnuts and screws etc. complete |
| 398 | 300x16 mm |
| 399 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, withnecessary screws etc. complete : |
| 400 | 300x10 mm |
| 401 | Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less thangrade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessaryscrews etc. complete |
| 402 | 125 mm |
| 403 | Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete. |
| 404 | Single rubber stopper |
| 405 | Providing & fixing glass panes with putty and glazing clips in steel doors, windows, clerestory windows,all complete with |
| 406 | With float glass panes of 4.0 mm thickness (weight not less than 10kg/sqm) |
| 407 | Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. |
| 408 | Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: (a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofingcompound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment.(b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS: 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm heightincluding rounding of junctions of walls and slabs.(c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm ofcement admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-incharge.(d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement :4 coarse sand)admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep.(e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks forcuring and for final test.“All above operations to be done in order and as directed and specified by the |
| 409 | (e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. * All above operations to be done in order and as directed and specified by the Engineer-In-charge: |
| 410 | With average thickness of 120 mm and minimum thickness at khurra as 65 mm. |
| 411 | Providing and fixing unplasticised-PVC pipe clips of approved design to unplasticised-PVC pipes by means of 50x50x50 mm hard wood plugs, screwed with MS screws of required length including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. |
| 412 | 110mm |
| 413 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion,(i) Single socketed pipes. |
| 414 | 110 mm diameter |
| 415 | Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete. |
| 416 | Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. |
| 417 | Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories forunplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion. |
| 418 | Bend 87.5° |
| 419 | 110 mm bend |
| 420 | Shoe (Plain) |
| 421 | 110 mm Shoe |
| 422 | ELECTRICAL WORK |
| 423 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FR PVC insulated copper conductor single core cable etc as required. |
| 424 | Group C |
| 425 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 426 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 427 | Supplying and fixing stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 428 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings). |
| 429 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 430 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FR PVC insulated, copper conductor, single core cable etc. as required. |
| 431 | Numbering of ceiling fan/ exhaust fan/ fluorescent fittings as required. |
| 432 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. |
| 433 | Upto 450 mm sweep |
| 434 | MCCB, MCB & DB'S |
| 435 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 436 | 40 amps |
| 437 | Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 438 | E A R T H I N G |
| 439 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as required. |
| 440 | Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required. |
| 441 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 442 | Supply and wiring of 4 number 25 sq. mm. PVC insulated 1100 V grade single core copper conductor cable in 50 mm dia PVC conduit partly concealed in wall and partly laid in slab alongwith reinforcement before concreting with two number 16sq mm single core copper conductor cable as earth continuity wire drawn in coudit including matching colour wash etc, complete in all respect. |
| 443 | LED LUMINAIRES |
| 444 | Supply & fixing of LED Tube Light with batten suitable for up to 1x22 watt Led tube light fitting including tube Suraface complete in all respect. |
| 445 | Cat. AAA |
| 446 | Supply and fixing of LED Street light Fitting having die cast aluminium body and diffuser with driver set suitable for 45 watt to 50 Watt. Confirming to IP 66protection complete in all respect. |
| 447 | Cat. AAA |
| 448 | Supply and erection of AC 230/250 Volts, 50 Hz exhaust fans including providing nuts, bolts, mounting frame and other accessories including connections etc. complete as required |
| 449 | Exhaust Fan |
| 450 | LIFTING AND SHIFTING WORK (Details AS per TS Estimate |
| 451 | GST Extra As per Applicable Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy