| 1 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed heavy class PVC conduit having wall thickness 2.0mm as required. |
| 2 | 2 X 1.5 sq. mm |
| 3 | 2 X 2.5 sq. mm |
| 4 | 2 X 4 sq. mm |
| 5 | 2 X 16 sq. mm |
| 6 | 4 X 4 sq. mm |
| 7 | 4 X 16 sq. mm |
| 8 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVCconduit as required. |
| 9 | S/D 3 X 1.5 sq. mm |
| 10 | Supplying and fixing following size/modules,G.I box alongwith modular base & cover for modular switches in recess etc.as required |
| 11 | 1 or 2 Module (75mmX75mm) |
| 12 | 3 Module (100mmX75mm) |
| 13 | 4 Module (125mmX75mm) |
| 14 | 6 Module (200mmX75mm) |
| 15 | Supplying and fixing two module stepped type electronic fan regulator on theexisting modular plate switch box including connections but excluding modularplate etc. as required. |
| 16 | Fan regulator |
| 17 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required |
| 18 | 5/6 amp Modular switch |
| 19 | 5/6 amp socket outlet |
| 20 | 15/16 amp Modular switch |
| 21 | 15/16 amp socket outlet |
| 22 | Supplying and fixing suitable size GI box with modular plate and cover in FRLS on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 23 | 32 Amp Switch socket |
| 24 | 1.32 Supplying and fixing suitable size GI box with modular plate and cover in FRLS on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 25 | Supplying and fixing 6 amps to 32 amps rating, 240/415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 26 | Single pole |
| 27 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 28 | 63 Amp |
| 29 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 30 | 63 Amp |
| 31 | Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 32 | 63 Amp |
| 33 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 34 | 63 Amp |
| 35 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 36 | 4 way, Double door |
| 37 | 8 way, Double door |
| 38 | 16 way, Double door |
| 39 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board with color coted wire set, insulated vertical phase bus bar, neutral bar with shroud, earth war, cable type blanking plate and circuit identification lebel with provision for MCCB as incomer and SP/TP MCB as outgoing as required. (but without MCCB incomer ) |
| 40 | 6 Way (6+6+6), TPN, Vertical type, MCB DB, double door |
| 41 | Providing & Laying of one number aluminium conductor, PVC insulated and PVC sheathed armoured/ XLPE power cable, 1.1 KV grade of following sizes on wall surface as required. |
| 42 | Armoured cable 50 sq. mm (3.5 core) |
| 43 | Providing and fixing following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 44 | 100 A - 125A , 18 KA |
| 45 | Providing and fixing of LED batten having minimum efficacy of 100 Im/W, P.F.>0.95 with THD<10%, CCT 6500 K,CRI 80, Surge Protection range 2 kV. The LED with useful life of 50000 Hrs. at L70 with five years warranty. The Input voltage shall be 150V to 270V, 50/60 HZ along with all accessories, including connections, testing etc. as required complete in all respects. |
| 46 | LED Batten 20 watt |
| 47 | Providing and fixing decorative LED mirror light having high quality design suitable for LED tube up to 10Watt (1000 lumen) 6500K and it should be compatible with specifications i.e. power factor ≥ 0.9, harmonic distortion ≤ 10% and efficacy ≥ 100 lumens per watt, CRI > 80, suitable for input voltage AC 220-240V, 50/60 Hz, complete with all accessories, connections, testing and commissioning etc. as required. |
| 48 | 10 Watt LED Mirror Light, 2 ft. |
| 49 | Acceptable Make |
| 50 | Copper Wire/Telephone Cable/UTP cable/ TV Cable:Finolex/KEI/ Polycab/ RR Kabel/ Havells/ Grandlay (duly ISI Marked) |
| 51 | Aluminium and copper XLPE Power Cables Armoured/Unarmoured:Finolex/KEI/ Polycab/ RR Kabel/ Havells/ Grandlay (duly ISI Marked) |
| 52 | Cat 6/ 6A Cable:Molex/ Digilink/ Schneider/ Belden/ Legrand |
| 53 | Modular Switch, Socket, Fan regulator, RJ-45, Cable TV socket, Data outlet socket, GI boxes etc. and accessories:Legrand : ARTEOR Honeywell : ORNA Panasonic : EUROPA Schinedier : ZENCELO |
| 54 | PVC Conduit with accessories:Finolex/ Supreme/ BEC/ NIC/ Polycab/ AKG (All shall be Min. 2mm thick and ISI marked) |
| 55 | MS Conduit with accessories:AKG/ NIC/ BEC/ RMCON (Note: The accessories shall be same that of conduit pipe and will comply to IS/ 4768 part 2 2003) |
| 56 | GI Pipe (for pipe pole and other items):Tata/ Jindal/ SAIL (All shall be ISI marked) |
| 57 | OFC cable and accessories:Belden/ D Link/ Tyco |
| 58 | Gland:Comet/ Dowells |
| 59 | HDPE/ DWC pipe:REX/ Duraline/ Duraplast/ Triputi |
| 60 | MCB/MCB DB/ Isolator/ RCCB/ Industrial Socket |
| 61 | MCCBs/ RCCBs/4 Pole Power contractor /Change Over:Legrand /Siemens/ Schneider/ L&T /ABB |
| 62 | 600 mm LED mirror light:L&T D Sine/ Schneider Compact NSX/ Legrand DPX3/ Siemens 2 VL/ ABB |
| 63 | LED bulk head fitting:Phillips/ Wipro/ Trilux/ Havells/ LT/ Panasonic |
| 64 | LED downlighter:Phillips/ Wipro/ LT/ Regent/ Panasonic |
| 65 | 36 watt 2'x2' panel light:Phillips/ Wipro/ LT/ Regent/ Panasonic |
| 66 | 36 watt LED batten light:Phillips/ Wipro/ LT/ Regent/ Panasonic |
| 67 | LED bed side light |
| 68 | Decorative wall light with E27 holder:Phillips/ Trilux/ Regent/ LT/ Lustre/ Panasonic/ wipro |
| 69 | 250/200 mm fresh air fan:USHA/ Khaitan/ Crompton/ Almonard |
| 70 | 300 mm sweep heavy duty exhaust fan:Usha/ Almonard/ Havells/ Orient/Bajaj/ Crompton |
| 71 | 3 /25 Ltrs. Geysers::Recold/ Bajaj/ Havells/ Crompton/ AO Smith/ Venus |
| 72 | 2 compartment energy meter board panel feeder pillar:Kalyani Switch Gear/ Power Associates/ Pristine/ Milestone/ ADLEC/ Tricolite/ ASPL/ CMKL |
| 73 | Ceiling fan:Usha/ Almonard/ Havells/ Orient/Bajaj/ Crompton |
| 74 | Or as per given against item or work and as per approval of Engineer-in-Charge Please Enable Macros to View BoQ information |