| 1 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains or laying of pipe/cables or for shafts, wells cesspits, man holes etc (not exceeding 1.5 m in width or 10 sqm on plan) and not exceeding 1.50m in depth in any kind of soil, including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m all as specified and directed. |
| 2 | Returning, filling in excavated material (soil) including spreading, levelling, watering and well ramming in layers not exc 25 cm all as specified and as directed. |
| 3 | Supply and laying Double Walled Corrugated (DWC) HDPE pipe of nominal bore 50mm including 90 degree bends with coupler and rubber ring, conforming to IS :16205 Part 24 Type 450N, laid in trenches for cable protection complete, all as specified and as directed. |
| 4 | Supply and laying Double Walled Corrugated (DWC) HDPE pipe of nominal bore 63mm including 90 degree bends with coupler and rubber ring, conforming to IS :16205 Part 24 Type 450N, laid in trenches for cable protection complete, all as specified and as directed. |
| 5 | Supply and laying Double Walled Corrugated (DWC) HDPE pipe of nominal bore 110mm including 90 degree bends with coupler and rubber ring, conforming to IS :16205 Part 24 Type 450N, laid in trenches for cable protection complete, all as specified and as directed. |
| 6 | Taking out existing LT UG XLPE cable of size 240 sqmm, 3.5 core from trenches/poles etc, alongwith protection covers all as specified and as directed. |
| 7 | All as per serial item No 6.00 but cross sectional area 150 sq mm, 3.5 core. |
| 8 | All as per serial item No 6.00 but cross sectional area 120 sq mm, 3.5 core. |
| 9 | All as per serial item No 6.00 but cross sectional area 95 sq mm, 3.5 core. |
| 10 | All as per serial item No 6.00 but cross sectional area 70 sq mm, 3.5 core. |
| 11 | All as per serial item No 6.00 but cross sectional area 50 sq mm, 3.5 core. |
| 12 | All as per serial item No 6.00 but cross sectional area 35 sq mm, 3.5 core. |
| 13 | All as per serial item No 6.00 but cross sectional area 25 sq mm, 3.5 core. |
| 14 | All as per serial item No 6.00 but cross sectional area 16 sq mm, 4 core. |
| 15 | All as per serial item No 6.00 but cross sectional area 10 sq mm, 2 core. |
| 16 | Supply and laying in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 240 Sqmm, 3.5 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete all as specified and as directed. |
| 17 | All as per serial item No 7.00 but cross sectional area 150 sq mm, 3.5 core. |
| 18 | All as per serial item No 7.00 but cross sectional area 120 sq mm, 3.5 core. |
| 19 | All as per serial item No 7.00 but cross sectional area 95 sq mm, 3.5 core. |
| 20 | All as per serial item No 7.00 but cross sectional area 70 sq mm, 3.5 core. |
| 21 | All as per serial item No 7.00 but cross sectional area 50 sq mm, 3.5 core. |
| 22 | All as per serial item No 7.00 but cross sectional area 35 sq mm, 3.5 core. |
| 23 | All as per serial item No 7.00 but cross sectional area 25 sq mm, 3.5 core. |
| 24 | All as per serial item No 7.00 but cross sectional area 16 sq mm, 4 core. |
| 25 | All as per serial item No 7.00 but cross sectional area 10 sq mm, 2 core. |
| 26 | M&L, in replacement, heat shrinkable straight through cable joint kit suitable for 10 to 16 Sqmm 4 core LT XLPE cable 1100 Volts grade complete with jointing material and accessories and testing including necessary excavation / earth work complete all as specified and as directed. |
| 27 | All as per serial item No 8.00 but 25 to 50 sqmm 3.5 core |
| 28 | All as per serial item No 8.00 but 70 to 120 sqmm 3.5 core |
| 29 | All as per serial item No 8.00 but 150 to 185 sqmm 3.5 core |
| 30 | All as per serial item No 8.00 but 240 sqmm 3.5 core |
| 31 | S&F in replacement 80 mm bore galvanised steel tubing, light grade, ISI marked, for protection of under ground cable on pole/wall/under road including clamps where reqd and taking out old unserviceable pipe complete all as specified and as directed. |
| 32 | M&L for cutting existing road/hard standing surfaces to a depth 60 cm and 50 cm width and getting out for laying underground pipe including returning filling in, watering well ramming in layers not exceeding 25cm in soil and filling the trench top with 15cm thick PCC 1:2:4, type B1 (using 20 mm graded stone aggregate) and making good the disturbed surface complete all as specified and as directed. |
| 33 | Dismantling of ACSR or AAC conductors of any size and any description from any height/ poles or any location complete all as specified and as directed by Engr in Charge. |
| 34 | Dismantling of Unserviceable LT insulators Pin/ shackle/ Disc & loop type from existing OH lines complete all as specified and directed by Engr in Charge. |
| 35 | Dismantling of unserviceable steel structure such as cross arms, bracings, supports, clamps etc from LT pole of any type/shape complete all as specified and directed. |
| 36 | Dismantling of GI wire cradles,earth wire guarding , fabricated with galvanised steel wire 4mm dia hexagonal / rectangular shape of any type complete all as specified and as directed . |
| 37 | Supply and fixing Cable route indicator made out cast iron and embedded LT Cable on the plate of size 80 mm dia 5 mm thick with angle iron support of 1.5m long including grouting lug of suitable size in PCC (1:3:6, C2) foundation of suitable size complete all as directed and directed by Engineer in Charge. |
| 38 | M&L in repairs/replacement earthing complete with galvanized steel earth plate electrode 60 cm X 60 cm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below ground level, connecting with GI strip of size 25mm x 4 mm, by means of nut bolts, check nuts and washer and the GI Earth strip connected upto main earth point/DBs alongwith 32mm dia GI medium grade protection pipe including provision of concrete pit in PCC (1:2:4) type B-1 using 20 mm graded stone aggregates with 40 mm thick RCC (1:2:4) cover with reinforced with XPM (weight not less than 4 Kg / Sqm) and frame of angle iron 25mm X 25 mm X 3mm with lugs 2 Nos and with 6 mm dia MS bar handle made to shape, |
| 39 | with GI light grade 20 mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling, test point made out of phosphorus bronze with fixing arrangement, funnel, wire mesh and earth work in hard/dense soil, returning filling in and removal of surplus soil to a distance not exceeding than 50 mtr, all as per electric plate No 3 of SSR Part I 2009 and connection to earth test point all as specified including testing on completion. Note : Rate of GI earthwire and GI protection pipe upto 7.5 mtr length shall be deemed to be included in this item. |
| 40 | Dismantling old existing LT stay assembly all as specified and as directed. |
| 41 | S&F in replacement FRP Junction box, light weight, weather proof, hinged door, with aluminium bus bar,240V, including MCB SP 6/10 amps, Box size not less than 250x200x100 mm including necessary connection for loop in and loop out cable connector and suitable size for cable glands and necessary fixing arrangement such as clamps, nut, bolts etc complete all as specified and directed . |
| 42 | S&F in replacement 40 mm bore galvanised steel tubing, light grade, ISI marked, for protection of under ground cable on pole/wall/under road including clamps where reqd and taking out old unserviceable pipe complete all as specified and as directed |
| 43 | S&F in replacement PVC insulated and over all PVC sheathed, stranded copper conductor wire 1.5 sqmm x 3 core, ISI marked complete from light fitting to pole junction box complete all as specified and as directed. |
| 44 | Supply, install, testing and commissioning in replacement, factory made and tested (including CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted, compartmantalised and IP-54 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber with insulated Aluminium bus bars 250 amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 50x50x6mm angle iron , powder coated, Front and rear opening type with aprons for cable entry with double door shutter and locking arrangement with including cable gland, lugs, jointing material etc and jointing, connecting, testing and commissioning and including following items. (Notes :The rate quoted shall include for Cost of dismantling/ taking down old unserviceable LT feeder piller, earth work & excavation for angle iron frame for foundation of panel board upto 0.50 m below GL in any type of soil & PCC (1:4:8), D2 filling in foundation the ground clearance of panel board shall be 0.40 m GL to the bottom of panel board). |
| 45 | Incoming: (a) MCCB 160 amps, 4 pole, 36 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 No. (b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 250 Amp, 4 pole, not less than 60cm long mounted on insulators for incoming supply-01 No.(c) Digital volt and ammeter with selector switch and CT's set - 01Set. (d) Neon indicating lamps (R, Y & B) -01 Set Outgoing: (a) MCCB 100 amps, 4 pole, 16 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 No. (b) MCCB 63 amps, 4 pole, 16 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 No.(c) MCCB 32 amps, 4 pole, 16 KA with adjustable thermal release, 50 Hz, 415 volts grade - 04 No. |
| 46 | Supply, install, testing and commissioning in replacement, factory made and tested (including CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted, compartmantalised and IP-54 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber with insulated Aluminium bus bars 150 amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 50x50x6mm angle iron , powder coated, Front and rear opening type with aprons for cable entry with double door shutter and locking arrangement with including cable gland, lugs, jointing material etc and jointing, connecting, testing and commissioning and including following items. (Notes :The rate quoted shall include for Cost of dismantling/ taking down old unserviceable LT feeder piller, earth work & excavation for angle iron frame for foundation of panel board upto 0.50 m below GL in any type of soil & PCC (1:4:8), D2 filling in foundation the ground clearance of panel board shall be 0.40 m GL to the bottom of panel board ). |
| 47 | Incoming: (a) MCCB 100 amps, 4 pole, 25 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 No. (b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 150 Amp, 4 pole, not less than 60cm long mounted on insulators for incoming supply-01 No.(c) Digital volt and ammeter with selector switch and CT's set - 01Set. (d) Neon indicating lamps (R, Y & B) -01 Set Outgoing: (a) MCCB 32 amps, 4 pole, 16 KA with adjustable thermal release, 50 Hz, 415 volts grade - 04 No. |
| 48 | Supply, install in replacement and testing out door wheather proof bus bar chamber of size 100 cm x 60cm x 30cm made out of 3.15mm CRCA MS sheet having one side openable hinged door shuter with locking arrangement/provn of two nos 80cm long 40x40x6mm anlge iron legs welded and 04 nos Aluminium bus bar of 200Amp rating provn of one MCCB TPN 100 Amp 25 KA for controlling Electric supply complete erected on ground with necessary PCC 1:3:6 type C2 foundation complete bus bar chamber painted with two coats of approved enamel paints over one coat of primer including making cable connection with necessary gland , lugs/thimbles complete all as specified and as directed. |
| 49 | M&L for PCC 1:2:4, type B1, using 20 mm graded stone aggregates as in coping of pole and similar work etc including necessary formwork and finishing even and smooth without using extra cement complete all as specified and as directed. Please Enable Macros to View BoQ information |