| 1 | Providing and installation of lifts wirh power operated center opening doors and AC variable voltage and variable frequency controls for 13 passangers (884 kg) with speed 1.0m/sec. and ACV VVF control complete all work as per derection of engineer in charge. (PAS2023 No 3.1.3) |
| 2 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. (DSR 2025 No. 5.6) |
| 3 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) (DSR 2025 No. 5.8) |
| 4 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. (DSR 2025 No. 5.10) |
| 5 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. (DSR 2025 No. 5.14) |
| 6 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. (10 x 6 sq. mm) (DSR 2025 No. 1.17.37) |
| 7 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. (Group C) (DSR 2025 No. 1.54.3) |
| 8 | Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required. 315A TP&N (DSR 2025 No. 2.1.7) |
| 9 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. 315 A, 35 KA TPMCCB (DSR 2025 No. 2.2.8) |
| 10 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as equired. (But without MCB/RCCB/Isolator) 6 Way Double Door (DSR 2025 No. 2.3.1) |
| 11 | Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32 A 415 V \\"C\\" curve TP MCB complete with connections, testing and commissioning etc. as required. (DSR 2025 No. 2.17) |
| 12 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top along with 20 A \\"C\\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.(DSR 2025 No. 2.18) Please Enable Macros to View BoQ information |