| 1 | DSR Item no. 4.1 Supplying and installation following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastener etc. as required. |
| 2 | 450 mm width X 62.5 mm depth X 2.0 mm thickness |
| 3 | DSR Item no. 19.6 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : |
| 4 | 500 mm dia. R.C.C. pipe |
| 5 | DSR item No.5.2Earthing with G.I. earth pipe 4.5 Metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 6 | DSR item No.5.12 Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 7 | Supply and laying of XLPE insulated PVC sheathed Aluminum conductor cable of 1.1 KV grade as per IS 7098 (Part-I) 1988 (amended up to date) of the following sizes to be laid in existing on cable tray/open duct. The job include the cost of making connections with suitable size of Al. Lugs/ thimbles, (As per Complete Item No. 5 of the DNIT) |
| 8 | 400 sq.mm 3.5 core al. Conductor XLPE cable |
| 9 | 150 sq.mm 3.5 core al. Conductor XLPE cable |
| 10 | 70 sq.mm 3.5 core al. Conductor XLPE cable |
| 11 | Supply and laying of XLPE insulated PVC sheathed Aluminum conductor cable of 1.1 KV grade as per IS 7098 (Part-I) 1988 (amended up to date) of the following sizes to be laid in existing RCC/Hume/DWC/ Metal pipe., (As per Complete Item No. 6 of the DNIT) |
| 12 | 400 sq.mm 3.5 core al. Conductor XLPE cable |
| 13 | 70 sq.mm 3.5 core al. Conductor XLPE cable |
| 14 | Supply and erection of sheet metal cubical pedestal of suitable dimensions made from 50 mm X 50 mm X 6 mm thick M.S angle iron frame, covered with 1.6 mm thick M.S. sheet duly welded on five sides and front side hinged complete with locking arrangement with 4 Nos. switchgear supporting members each of M.S.,(As per Complete Item No. 7 of the DNIT) |
| 15 | Cubical size 1800mm x1500mm x500mm |
| 16 | Cubical size 1500mm x1500mm x500mm |
| 17 | DSR Item no. 2.2 Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. |
| 18 | 125 A,36KA,FPMCCB |
| 19 | 200 A,36KA,FPMCCB |
| 20 | 400 A,50KA,FPMCCB |
| 21 | Fabrication, Supply and Erection of 25mm x 25mm x 5mm MS angle iron Bracket (Clamp Type) of U–shape. The clamp should be approximate 400 mm Long fixed on surface/wall with the help of 2 nos. steel rawl plug for installation of existing cable tray.,(As per Complete Item No. 9 of the DNIT) |
| 22 | Making of Haudi of following size for drawing of underground cable etc constructed with bricks wall 4½” thick and plastered from the inner side with cement, sand, mixture 1:5. (As per Complete Item No. 10 of the DNIT) |
| 23 | Size 4’ x 4’ x 4’ deep |
| 24 | DSR item no.2.10.1.3Excavating trenches by mechanical/ manual means of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, for all depth, including getting out the excavated soil, and then returning the soil as required, (As per Complete Item No. 11 of the DNIT) |
| 25 | Pipes, cables etc. exceeding 300mm dia but not exceeding 600 mm Please Enable Macros to View BoQ information |