| 1 | BoQ BOQ Represent (%) Percentage having Above/ Below ( + or - denomination) the Lump sum pre price inserted by MES BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority : GARRISON ENGINEER TEZPUR (NORTH) NAME OF WORK : REPAIR / REPLACEMENT AND DAY TO DAY MAINTENANCE OF INTERNAL WIRING, LIGHT FITTINGS, SWITCH GEARS, LED FITTINGS REPAIRS TO GEYSER, CEILING FANS AND OTHER ALLIED WORKS FOR ZONE 7 & 7A MD ACCN AT NAA UNDER GE (N) TEZPUR Contract No : GE(N)/TEZ/ OF 2026-2027 (File No. 8247) Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Description of items of works Item Code / Make Approx No. of quentity required. Units Pre Priced Rate (in. Rs.) as Defined by MES Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures to be entered by the Bidder Rs. P. Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT (In INR) TOTAL AMOUNT With Taxes TOTAL AMOUNT (In Words) |
| 2 | M&L for point wiring in replacement of with 1.5 Sqmm multi stranded copper conductor 1100 V grade, ISI marked , PVC insulated unsheathed cable (with approved colour code) FRLSH cable drawn in & including PVC casing caping of 25/32 mm wide, with double locking type, including all accessories casing caping as approved by EIC, with PVC 1.5 mm multi stranded insulated unsheathed copper wire, ISI marked of green colour for continous earth, PVC terminal box and PVC board making good disturbed surface to match with the existing surface for one light /fan/bell point controlled by one switch complete all as directed by Engineer-In-charge. |
| 3 | All as per item above but for One 3 pin socket outlet 5 Amps on same board complete all as specified and as directed. |
| 4 | All as per item above but for One 3 pin switch socket combination 5 Amps on indpendent board complete all as specified and as directed. |
| 5 | All as per item above but with 2.5 sqmm single core multistranded copper conductor FRLSH cable for 3/5 pin 15 Amp socket outlet on independent board complete all as specified and as directed. |
| 6 | All as per item above but for one light point controlled by two, two way switch with 1.5 sq mm copper conductor cable complete all as specified and directed. |
| 7 | M&L in replacement of point wiring in replacement with 1.5 sqmm FRLSH, PVC insulated stranded copper conductor single core including non metalic PVC conduit medium grade (MMS ISI) of size not less than 20 mm dia(or as site requirement) concealed in wall/over ceiling, pressed steel concealed terminal boxes of required size and with top cover 3 mm thick of plastic laminated sheet of reqd colour, painting terminal boxes inside and out side with one coat red oxide primer complete with all accessories and all as specified including 1.5 sqmm FRLSH PVC insulated sheathed multistranded copper earth conductor to common earth and connected to earth dolly for light / fan/ bell point controlled by one switch complete all as specified and as directed.Note:- (i) Cost of PVC conduit, steel terminal boxes, plastic laminated sheet cover etc; are deemed to be included in the quoted rate.(ii) M&L for cutting chases on walls / ceiling and making good disturbed surfaces including finishing with cement mortar (1:3) etc; are deemed to be included in the quoted rate. |
| 8 | All as per item above but for 3 pin 5 Amps switch socket combination on independent board with 1.5 sq mm copper cable complete all as specified and directed. |
| 9 | All as per item above but for 3 pin 16 Amps switch socket combination on independent board with 2.5 sq mm copper cable complete all as specified and directed. |
| 10 | All as per item above but for 5 Amps socket point on the same board controlled by one switch complete all as specified and directed. |
| 11 | All as per item above but for one light point controlled by two, two way switch with 1.5 sq mm copper conductor cable complete all as specified and directed. |
| 12 | S&F in repair Modular switch 1 way 10 A 1 module module complete all as specified and as directed. |
| 13 | S&F in replacement Modular switch 1 way 16 Amp SP, 1 module complete all as specified and as directed. |
| 14 | S&F in replacement Modular Fan step regulator, 120W - 2 module complete all as specified and as directed. |
| 15 | S&F in replacement Modular bell push 6 A 2 module complete all as specified and as directed. |
| 16 | S&F in replacement Modular Socket 6 A 2/3 pin combined 2 module complete all as specified and as directed. |
| 17 | S&F in replacement Modular Socket 6 A /16 A-2/3 pin combined 2 module complete all as specified and as directed. |
| 18 | S&F in replacement of switch piano (flush button type) single pole, one way, 5 Amps complete all as specified and directed. |
| 19 | S&F in replacement of switch socket combination 2 in one, 5 pin , 5/6 Amps, 240 Volts flush type,complete all as specified and directed. |
| 20 | S&F in replacement of switch socket combination 2 in one with box, 5 pin , 5/6 Amps, 240 Volts flush type,complete all as specified and directed. |
| 21 | S&F in replacement of switch socket combination 2 in One , 5/6 pin, 5/6/16 Amps flush type complete all as specified and directed. |
| 22 | S&F in replacement of socket out let, 5 pin 5 Amps flush type complete all as specified and directed. |
| 23 | S&F in replacement of call bell, Ding dong type, AC 230 Volts single pole complete all as specified and directed. |
| 24 | S&F in replacement of ceiling rose polycarbonate type three terminals complete all as specified and directed. |
| 25 | S&F in replacement of step type electronic fan regulator 120 watt single pole 240 Volts complete all as specified |
| 26 | S&F in replacement of Lamp holder PVC/Polycarbonate type with cord grip cap suitable for pendent fitting complete all as specified and directed |
| 27 | S&F in replacement for metal flush box 10/12 module complete all as specified and as directed. |
| 28 | S&F in replacement for metal flush box 8 module complete all as specified and as directed. |
| 29 | S&F in replacement for metal flush box 6 module complete all as specified and as directed. |
| 30 | S&F in replacement for metal flush box 3 module complete all as specified and as directed. |
| 31 | S&F in replacement for white cover plate with frame 10/12 module complete all as specified and as directed. |
| 32 | S&F in replacement for white cover plate with frame 8 module complete all as specified and as directed. |
| 33 | S&F in replacementfor white cover plate with frame 6 module complete all as specified and as directed. |
| 34 | S&F in replacement for white cover plate with frame 3 module complete all as specified and as directed. |
| 35 | S&F in replacement LED bulb of 7 W with Lumen output 950 lm B22 type fitted suitable for PVC /Poly Carbonate type complete all as specfied and directed. |
| 36 | S&F in replacement LED bulb of 9/10 W with Lumen output 950 lm B22 type fitted suitable for PVC /Poly Carbonate type complete all as specfied and directed. |
| 37 | S&F in replacement LED Tube light luminaires, 20-22 watts, lumen output not lessthan 2000 (4 feet), made of anodised extruded aluminium housng, with high transmissivity diffuser, high lumen output, with suitable integrated electronic driver, and operated in single phase, 230 volts, 50HZ, all accessories internally pre-wired and including connecting up with three core twisted flexible copper conductor cable of from connector and ceiling rose, complete all as specified and directed. |
| 38 | S&F in replacement mirror light batten type 10/11 W 230V AC, 50Hz, Pf >0.98, THD <10% on wall complete all as specified and directed by Engineer in charge. |
| 39 | S&F in replacement of LED bulk head wall light fixture 10 Watt , pressure die cast housing , IP 66 protection and IK 09 impact resistance suitable for surface and wall mounting complete all as specified and as directed. |
| 40 | Supply and fixing in replacement decorative wall light fixture metalic body single head wall light suitable for 20 watt maximun wattage complete all as specified and as directed. |
| 41 | S&F in replacement new generation energy saving and environmental friendly long life 25 W LED wall/building security light made up of pressure die cast aluminium housing with high efficient LED as lighting source and PC cover having top Opening seperate driver compartment with IP66 protection and impact resistance of IK07 complete all as specified and directed . |
| 42 | S&F in replacement new generation energy saving and environmental friendly long life 35W LED wall street light made up of pressure die cast aluminium housing with high efficient LED as lighting source and PC cover having top Opening seperate driver compartment with IP66 protection and impact resistance of IK07 complete all as specified and directed. |
| 43 | S&F in replacement air circulator(Brushless direct current motor) in lieu of old air circulator complete , 230 V, 1200 mm sweep, Five star rated with brushless direct current motor all complete.Note: Old air circulators to be deposited at AGE E/M store yard deemed to be included in the quoted rate complete all as specified and as directed. |
| 44 | Taking down exhaust fan any type/ size from wall and dismantling sealing cable and dismantling blades and bring in to contractor store for repair and fixing exhaust fan in position after repair, greasing etc. with existing flexible copper cable complete all as directed. (spare parts required shall be measured and paid separately) |
| 45 | S&F in replacement bearing suitable for ceiling fan 1200 mm to 1400 mm /exhaust fan of bearing No- 6201/6202 complete all as specified and directed. |
| 46 | S&F in replacement capacitor 2.5 MFD for ceiling fan. complete all as specified and directed. |
| 47 | S&F capacitor 3.15 MFD for ceiling fan complete all as specified and directed. |
| 48 | S&F rubber real with bolts, nuts and clamps of suitable for ceiling fan complete all as specified and directed. |
| 49 | S&F PCB Circuit for BLDC ceiling fan suitable of make Orient/Crompton/Havells or on site complete all as specified and directed. |
| 50 | S&F PVC insulated flexible copper cable 3 core of size 23/0.0076 complete all as specified and directed. |
| 51 | S&F in replacement old u/s element and fixing of new heating element of capacity 1.5/2 KW of any type (as per sample) complete all as specified and directed. |
| 52 | Supply and fixing in replacement old u/s thermostate for geyser and fixing of new thermostate adjustable between 30 degree to 90 degree celcius of any size /type as per existing (ISI marked) complete all as specified and directed. |
| 53 | S&F in replacement of insulation tape 25mm 18mtr roll suitable for 1100V all complete as specified and directed. |
| 54 | Supply and fixing in replacement of PVC connection pipe heavy duty 450mm long with 2 nuts brass at both ends suitable for hot water for GI pipe 15 mm dia complete all as specified and directed. |
| 55 | S&F in replacement MS anchor fastener heavy duty 12mm dia 10 cm long complete all as specified and as directed. |
| 56 | S&F in replacement plug top, AC 230 Volts, 6 Amps complete all as specified and directed. |
| 57 | S&F in replacement plug top, AC 230 Volts, 16 Amps complete all as specified and directed. |
| 58 | S&F in replacement hylam sheet cover 3 mm thick for fixing switches, sockets, regulators etc of suitable size as on site on existing metal box complete all as specified and directed. |
| 59 | S&F in replacement of PVC conduit medium grade (MMS) with fittings, ISI marked, 25 mm size complete all as specified and directed. |
| 60 | S&F in replacementt of PVC casing & capping medium grade with fittings, ISI marked, 25 mm size complete all as specified and directed. |
| 61 | S&F in replacement of PVC insulated Aluminium flat service cable 2 core , 1100 Volts, 6 Sq mm complete all as specified and directed. |
| 62 | Supply and draw submain wiring in replacement with two single core 6 sq mm FRLSH PVC insulated copper cable 1100 volts grade multi stranded, sheathed conductor in concealed PVC conduit including 6 sq mm multi-strand FRLSH PVC insulated copper wire for earth continuity conductor connected to common earth dolly complete and making good disturbed surface complete complete all as specified and as directed. Note:- Cost of PVC conduit, cutting chases on walls and making good disturbed wall surfaces including finishing with cement mortar (1:4) matching with the existing shade / tint are deemed to be included in the rates quoted. |
| 63 | All as per item no 61 above but on surface PVC casing caping medium grade of 25 mm wide, with double locking type, including all accessories complete all as specified and directed. |
| 64 | Supply and draw submain wiring in replacement with two single core 4 sq mm FRLSH PVC insulated copper cable 1100 volts grade multi stranded, sheathed conductor on wall surface PVC casing caping medium grade of 20-25 mm wide, with double locking type including 4 sq mm multi-strand FRLSH PVC insulated copper wire for earth continuity conductor connected to common earth dolly complete and making good disturbed surface complete all as specified and as directed.Note:- Cost of PVC casing caping on walls and making good disturbed wall surfaces matching with the existing shade / tint are deemed to be included in the rates quoted. |
| 65 | S&F in repair single pole and neutral enclouser with a two pin and earth plug and socket complete with one pole MCB 20 Amps complete all as spd and directed . |
| 66 | S&F in repair sheet metal enclosure double door for DBs SPN 4 way 240 V complete double door, flush mounted all as specified and as directed |
| 67 | S&F in repair sheet metal enclosure double door for MCB DBs SPN 8 way 240 V, complete flush mounted all as specified and as directed. |
| 68 | S&F in repair sheet metal enclosure double door for MCB DBs SPN 12 way 240 V, complete flush mounted all as specified and as directed. |
| 69 | S&F in repair sheet metal enclosure double door for MCB DBs TPN 04 way 415 V, suitable for 63/100 Amp MCCB as incomer complete flush mounted all as specified and as directed. |
| 70 | Supply and fixing in repair 415V 10KA 'C' curve miniature circuit breaker (MCB) 63Amp capacity in the DB complete with connection testing and commissioning all as directed. |
| 71 | S&F in repair MCB single pole (SP) 5 to 40 Amps, 240 volts , C curve , AC , 50 Hz ,10 kA complete all as specified and directed. |
| 72 | S&F in repair MCB Single pole & neutral (SPN) 32 Amps, 240 volts , C Curve, AC , 10 kA complete all as specified and directed. |
| 73 | S&F in replacement of Prepaid meters single phase 10-60 Amps 240Volt after taking down and depositing to AGE E/M yard Make- HPL cat part No. PSPB1523111000OC01 all complete all as specified and directed. |
| 74 | Supply & Fix in replacement of LT panel board \\"in-door wall mounting type\\" factory fabricated (CPRI type tested) with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-43 & general construction confirming to IS-13947, double door, front openable. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation & tinned copper bus-bar wrapped with coloured PVC tape/sleeves of rating in conformity to the Incoming MCCB rating. The panel board shall be fabricated out of 2.0 mm thick CRCA sheet duly pre-treated & powder coated, supporting frame made out of suitable size angle iron/channel etc. suitable for 3 Ph, 4 wire system 415/440 volts grade incl complete internal wiring with not less than 2.5 sqmm copper wire incl cable glands of suitable sizes incl arrangements for wall mounting complete all as specified & as directed with &incl the following accessories:- BUS-BAR & INTERNAL CONNECTIONS :The bus-bars shall be made up of 04 Nos Al 200 A rated, duly insulated with 1100 V grade standard colour coded PVC sleeves & rigidly mounted on suitable sized \\"F\\" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc.PROVISION FOR CABLE ENTRY :The provision for cable entry/exit shall be provided in the bottom for both incoming& out-going cables.INCOMING :MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting having breaking capacity 25 KA of rating 100 A incl electric connection complete.OUTGOINGS :(a) S&F MCB, DP, 10KA, 230V, \\"C\\" curve, 40 A, ISI Marked complete - 05 Nos (including one no. spare)(b) S&F MCB, DP, 10KA, 230V, \\"C\\" curve, 06 to 32 A, ISI Marked complete - 01 Nos.(c) Space for Single Phase prepaid KWH meter - 05 Nos.(d) Indicator lamp with integral circuit (230/240V) & cluster LED (Red, Orange, Blue) - 01 Set. |
| 75 | M&L for earthing complete with galvanised perforated steel pipe electrode, 40mm bore, medium grade, 2.5 metres length, buried directly and preferably vertically in ground with top edge of the pipe not less than 1.25 metres below ground level connected to GI earth wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 2 of SSR Part I connected to earth test point all as specified or indicated and connected earth work, in soft/loose soil, removing soil upto 50m, refilling agricultural soil if sandy soil, PCC 1:3:6 type C1 as in pit, 20mm dia GI pipe medium grade for watering pipe, 15 mm bore GI light grade earth lead protection pipe, 50mm thick RCC 1:2:4 type B1 cover slab of earth pit reinforced with 8 mm dia TMT Bars @ 10cm C/C both ways and with handle made out of 20mm dia bars, funnel, strainer, alternate layer of charcoal dust and common salt at 2.5Mtr depth and testing on completion , complete all as specified and directed. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |