| 1 | Taking down carefully copper/ aluminium point wiring (light/fan/bell/ holder/socket or power point) inclusive of all fittings such as switches, ceiling roses, pendants, regulators, sockets, fittings etc. removing materials from site and making good to the disturbed surfaces of floors/walls/ceiling etc, complete all as specified and as directed by Engr-in-Charge. |
| 2 | Taking down carefully aluminium sub main wiring of any type and size including fittings and fixtures, removing materials from site , complete all as specified and as directed by Engr-in-Charge. |
| 3 | Disconnecting from electric circuit and taking out existing unserviceable MCB DB SPN of any number of ways including MCB etc removing materials from site, complete all as specified and as directed by Engr-in-Charge. |
| 4 | Taking down ceiling fan, ceiling cable end, dismantling blades, removing fan and blades, re-fixing, complete all as specified and as directed by Engr-in-Charge. |
| 5 | Disconnecting from electric circuit and taking out electric meter from the existing sheet metal enclosure and deposited to MES for re-fixing , complete all as specified and as directed by Engr-in-Charge. |
| 6 | Materials and labour for concealed point wiring with 1.5 Sqmm PVC insulated and unsheathed multi-stranded FRLSH copper conductor cable 1100 volts grade, single core, drawn through and including PVC concealed conduit (medium grade) not less than 20mm size with all fittings and accessories suitable for one light / one fan/ bell point controlled by one switch including unsheathed single core stranded copper cable of size 1.5 Sqmm as earth continuity conductor connected to common earth and earthy dolly and to be terminated to sunken/pressed flush box readily available covered with outer plates/inner plates etc as per site requirement and making good to the disturbed surfaces of walls,floors etc, complete all as specified and as directed. Note:- 1. Metal box shall be measured and paid separaely as ''Supply'' only for mounting modular switches sockets, fan regulators including testing on completeion complete all as specified and as directed. 2. Modular plate with frame shall be measured and paid for separately. |
| 7 | All as per Item No.6 here-in-before but for one 3 Pin 5 Amps socket outlet on same board with other switch, complete all as specified and as directed. |
| 8 | All as per Item No.6 here-in-before but for one 3 pin 5 amps switch socket out let on independent board, complete all as specified and as directed. |
| 9 | All as per Item No.6 here-in-before but wiring with 2.5 Sqmm , PVC insulated unsheathed multistranded FRLS copper conductor cable 1100 volts grade, single core earth continuity conductor connected to common earth dolly for one 3/5 pin 15 amps switch socket out let on independent board, complete all as specified and as directed. |
| 10 | Materials and labour for concealed point wiring with 1.5 Sqmm PVC insulated and unsheathed multistranded FRLSH copper conductor cable 1100 volts grade, single core, drawn through and including PVC concealed conduit (medium grade) not less than 20mm size complete with all fittings and accessories suitable for one light controlled by two way switch including unsheathed single core stranded copper cable of size 1.5 Sqmm as earth continuity conductor connected to common earth and earth dolly and to be terminated to sunken/pressed flush box readily available covered with outer plates/inner plates etc as per site requirement and making good to the disturbed surfaces of walls,floors etc, complete all as specified and as directed. Notes -1. Metal box shall be measured and paid separaely as ''Supply'' only for mounting modular switches sockets, fan regulators etc. 2. Modular plate with frame shall be measured and paid for separately. |
| 11 | Supply and fix modular switch 6 Amps, 230 V, single pole, one way, 1 module, complete all as specified and as directed. |
| 12 | Supply and fix modular switch 16 Amps, 230 V, single pole, one way, 1 module, complete all as specified and as directed. |
| 13 | Supply and fix modular 2 way switch 6 Amps, 230 V, single pole, one way, 1 module, complete all as specified and as directed. |
| 14 | Supply and fix modular bell push 6 Amps 230V, single pole, one way, 1 module, complete all as specified and as directed. |
| 15 | Supply and fix bell multi music type, AC 230 V, single pole, complete all as specified and as directed. |
| 16 | Supply and fix modular step type fan regulator suitable for ceiling fan of 1200mm sweep, 120 watts, 2 module, complete all as specified and as directed. |
| 17 | Supply and fix socket, modular type 2/3 pin combined, 2 module, 6 Amps, 230V, complete all as specified and as directed. |
| 18 | Supply and fix socket, modular type 2/3 pin combined, 2 module, 6 Amps/16 Amps, complete all as specified and as directed. |
| 19 | Supply and fix ceiling rose, surface bakelite, 65mm x 50mm, three terminals, complete all as specified and as directed. |
| 20 | Supply only modular metal flush box of 02/01 module, complete all as specified and as directed. |
| 21 | Supply only modular metal flush box of 03 module, complete all as specified and as directed. |
| 22 | Supply only modular metal flush box of 04 module, complete all as specified and as directed. |
| 23 | Supply only modular metal flush box of 08 module, complete all as specified and as directed. |
| 24 | Supply and fix modular cover plate with frame 02/01 module, complete all as specified and as directed. |
| 25 | Supply and fix modular cover plate with frame 03 module, complete all as specified and as directed. |
| 26 | Supply and fix modular cover plate with frame 04 module, complete all as specified and as directed. |
| 27 | Supply and fix modular cover plate with frame 08 module, complete all as specified and as directed. |
| 28 | Material and labour for two single core PVC insulated unsheathed cable 6.0 sqmm (Nominal area) two run with multistranded copper conductor cable, 1100 volts grade, drawn through and including PVC concealled conduit with accessories and continious earth wire of single core PVC insulated, unsheathed cable 6.00 sqmm (Nominal area) with ultistranded copper conductor (green)one run 1100 volts grade for sub main wiring and making good to the disturbed surfaces, complete all as specified and as directed. Note:-(i) Two run of wiring cable, one run of earth wire shall be measured as one unit. (ii) 270 Rm qty including for AC wiring. |
| 29 | Material and labour for two single core PVC insulated unsheathed cable 4.0 sqmm (Nominal area) two run with multistranded copper conductor cable, 1100 volts grade, drawn through and including PVC concealled conduit with accessories and continious earth wire of single core PVC insulated, unsheathed cable 2.5 sqmm (Nominal area) with ultistranded copper conductor (green)one run 1100 volts grade for sub main wiring and making good to the disturbed surfaces, complete all as specified and as directed. Note:- 1. Two run of wiring cable, one run of earth wire shall be measured as one unit. 2. Metal box shall be measured and paid separaely as ''Supply'' only for mounting modular switches sockets, etc. 3. Modular plate with frame shall be measured and paid for separately. |
| 30 | Supply and fix LED light fitting 1x 20W, 220V, AC decorative box type, rechargeable inverter type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose, complete all as specified and as directed. |
| 31 | Supply and fix LED light fitting mirror type with high out put diffuser 2 feet, 10 watt, 220 V, AC decorative rechargeable inverter type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size from ceiling rose, complete all as specified and as directed. |
| 32 | Supply and fix LED building security light fitting, 35 Watt, 230 V AC, outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection, complete all as specified and as directed. |
| 33 | Supply and Fix Lamp holder, PVC/Polycarbonate type, with back plate suitable for batten fittings, complete all as specified and as directed. |
| 34 | Supply and fix retrofit LED Bulb rechargeable inverter type 15W, complete all as specified and as directed. |
| 35 | Supply and fix sheet metal enclosures MCB DB 4 way TPN, Vertical type , double door, IP54 Protection with 200 Amp rated bus bar including earth & neutral link, complete fixing acessoreies, complete all as specified and as directed. |
| 36 | Supply and fix sheet metal enclosures MCB DB 8 way SPN, Vertical type , double door, IP54 Protection with 200 Amp rated bus bar including earth & neutral link, complete fixing acessoreies, complete all as specified and as directed. |
| 37 | Supply and fix Miniature circuit breaker (MCB) Single Pole, 240 Volts, 10KA, 6 to 32 Amps, 'C' curve, complete all as specified and as directed. |
| 38 | Supply and fix MCB SPN 6 to 32 Amps 10KA ‘C’ curve, 240 volts, complete all as specified and as directed. Note:-(i) 16 Nos qty including for AC wiring. |
| 39 | Supply and fix Miniature circuit breaker (MCB) Triple Pole and Neutral, 415 Volts, 63A, breaking capacity, 'C' curve, complete all as specified and as directed. |
| 40 | Hanging only ceiling fan (M.D. supply) and connecting up including provision of 1.5m down rod not less than 12mm , with necessary clamps , nuts , bolts and welding work if required including cutting of existing false ceiling board and provision of 1.5 Sqmm PVC insulated unsheathed multistranded (green colour) copper conductor cable 1100 volts grade, single core, earth continuity conductor cable from ceiling rose or connector to fan, complete all as specified and as directed. |
| 41 | Taking down Ceiling fan, dismantling blades and removing fan and blades deposited to E/M store, complete all as specified and as directed. |
| 42 | Supply and fix ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) and including provision of PVC insulated sheathed round flexible wire with multistranded copper condictor of size 1.50 Sqmm 3 core 1100 volts, complete all as specified and as directed. |
| 43 | Supply and fix exhaust fan of size 300m sweep, steel body AC single Phase, 230V, with blades, frame and louvers, complete all as specified and as directed. |
| 44 | Fixing only and connecting electric meters upto 25 amps obtained from item No 5 here-in-before, ccomplete all as specified and as directed. |
| 45 | Supply and fix energy meter enclosure of size 110cm x 85 cm x 25 cm fabricated out of 1.2mm thick MS sheet front openable with lock and key arrangement including weather, dust and vermin proof suitable for fixing single phase electric energy meter and fixed over the wall with necessary grouting arrangement and refixing electric meters/circuits as per site condition including one coat of synthetic enamel paint over a coat of red oxide primerincluding taking down carefully the existing unserviceable energy meter enclosure of any size and making good to the disturbed surfaces of walls, complete all as specified and as directed. |
| 46 | Supply and fix sheet metal enclosures MCCB DB 4 way VTPN, double door, vertical type, with 200 Amp rated bus bar including earth & neutral link, IP 43 protection, complete fixing accessories and taking out existing unserviceable cutout any type etc any number of ways including MCB etc and making good to the disturbed surfaces of floors/walls/ceiling etc., complete all as specified and as directed. |
| 47 | Supply and fix Moulded case circuit breaker (MCCBs) Triple pole and Nuetral, 415 Volts, adjustable type 100 Amps, 16KA with current carrying capacity in the DB including taking down old MCB 63Amps, complete all as specified and as directed. |
| 48 | M&L for earthing complete with galvanized steel earth plate electrode 600mmx600mmx6mm thick buried directly in gournd (earth pit not less than 2.25 Mtr deep below normal ground level) with top edge of plate not less than 1.5 Mtr below normal ground level connected to galvanized 4 mm dia earth wire as earthing lead upto 7.5 mtrs from testing point fixed by means of steel bolts, nuts, check nuts and washer, of galvanized earth wire protected by 25mm bore medium grade galvanised iron pipe and other end connected to earthing test point including funnel with watering pipe of 20mm bore light grade galvanised iron, wire mesh, charcoal or coke and common salt in alternate layer of 15cm (Compacted thickness) all around earth electrode with concrete earth pit in PCC (1:3:6) type C-1 50mm thick precast RCC M-20 nominal mix cover slab of size 450mm x 450mm reinforced with 8mm dia TMT bar 10 cm C/C and suitable handle of 10mm dia round bar including necessary execavation, earth work in soft / loose soil and deposited soil to a distance n.exc 50 M and necessary testing complete all as shown in electrical plate No. 3 of MES shedule of SSR Part-I, complete all as specified and as directed.Note:-(i) 4 nos qty including for AC wiring. |
| 49 | Supply and fix GI wire dia 4 mm size, complete all as specified and as directed. |
| 50 | Supply and fixing single pole and neutral sheet metal enclosure with two pin earth plug and socket complete including one Single pole MCB 20 Amps cappacity, complete all as specified and as directed. |
| 51 | Supply and fix sheet metal enclosure, double door, vertical type DBs for mounting of MCB for 415 Volts, 6 way, with 200 Amps rated bus bar with provision for 160 Amps MCCB as incommer and SP/ TP MCB as outgoing and electrically connected up, complete all as specified and as directed. |
| 52 | Supply and fix 415V, 25 KA 'C' curve moulded case circuit breaker (MCCB) of Three poles and Neutral current carrying capacity 100 AMP, in the DB Complete with connection testing and commissioning, complete all as specified and as directed. |
| 53 | Supply and fix 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single poles and current carrying capacity 6 to 32 AMP, in the MCB DB Complete with connection testing and commissioning, complete all as specified and as directed. |
| 54 | Excavating in trenches not exc. 1.50 m wide and not exc. 1.50 m in depth for laying of Cables and getting out in Soft/ Loose Soil, complete all as specified and as directed. |
| 55 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 250mm in Soft/Loose Soil, complete all as specified and as directed. |
| 56 | Removing excavated Materials (Soils) not exc. 50.00 m and depositing where directed at a level not exc. 1.50 m above the starting point , complete all as specified and as directed. |
| 57 | Horizontal boring for passing GI protection pipe up to 100 mm bore (dia), under road / foot path, not exc. 10.00 metre in a single length, complete all as specified and as directed. |
| 58 | M&L for Sand cushioning (dry) in trenches for protection of UG cables (below, above and around the UG cable laid in trenches) of 230mm spread thick -ness and consolidated (punned) upto 180mm thickness, complete all as specified and as directed.NOTE :-(i) For the purpose of Payment, Punned thick-ness of Sand Cushioning only shall be Measured and Paid for. |
| 59 | Supply and fix Sub-Class B brick, well burnt, laid breadth-wise along the axis of Cable laid in Trenches over Sand Cushion laid for UG Cable Protection, complete all as specified and as directed. |
| 60 | Supply & Laying or Fixing or Passing through Pipe XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70sqmm 3.5 core and Testing, including brass compression cable gland, terminal Lug, etc., complete all as specified and as directed. Materials and Labour for rendering 8 mm thick, cement plaster, in cement mortar (1:4) mixed with water proofing compound as per manufactures instructions over and including 12 mm thick backing coat in cement mortar (1:4) on fair faces of brick work or concrete surface in walls, complete all as specified and directed.Note: - (Water proofing compound will be measured and paid separately) Please Enable Macros to View BoQ information |