| 1 | SITC of Radiator Cooled Silent DG Set (As per latest CPCB-IV+ emission norms) having specifications as per A, B, C, D, E, F & G : |
| 2 | A) Diesel Engine : Turbo charged Diesel Engine ( conforming to BS:649/5514), multi cylinder, dynamically balanced flywheel, electric start of suitable BHP at 1500 rpm capable of taking 10% over loading for one hour after 12 hours of continuous operation., Dry exhaust mainfold with silencer and Diesel oxidation catalyst & selective catalyst reduction system (isolated from main DG chamber), up to 1.50 M exhaust piping (with LRB insulation & Alum. cladding ) as required .Diesel engine should have Precise emission control by treatment with Diesel exhaust fluid (DEF)/Aqueous urea tank (above 82.5 KVA) as per CPCB 4+ norms |
| 3 | B) Alternator : AC Brush less SPDP Synchronous alternator rated of appropriate KVA, 415 volts at 1500 rpm, 3 phase, 50 Hz, ac supply with 0.8 lagging power factor. Alternator conforming to BS 5000 (part 99) or IS/IEC 60034-1. . Alternator shall be self regulated with standard Alternator Protection( Over voltage , over speed & under voltage, under speed warning & shutdown). |
| 4 | C) Canopy : CPCB / ARAI approved Standard canopy with Weatherproof, powder coated Accoustic enclosure for DG set for sound attenuation fabricated from CRCA sheet steel (structure) including sidewals & filled with glasswool (96Kg/m3) /PU Foam. as per IS8183 and the thickness of the doors should be 28/40/50/85 mm as per rating . All doors/opening are sealed with neoprene /EPDN gaskets. The DG Set has Inbuilt / External in fuel tank to run 6 to 8 Hrs along with DEF tank (as per OEM standards). There should be provision of protection and tripping of DG set for temperature greater than 50 degree centigrade. The enclosure should be suitable for following capacity DG sets and alternator. Noise level shall be less than 75 dB at a distance of 1 Mtrs. in open free field environment as per ISO 8528 part 10 duly certified by authorised agency etc. |
| 5 | D) Instruments : Electronic / Mechanical governor, Manual & electric Start ,Batteries with battery charger, Electronic fuel system, advanced after treatment system (ATS), Exhaust gas recirculation(EGR) System along with Diesel oxidation catalyst(DOC) and Selective catalytic reduction (SCR) , supply module and DCU to control and monitor DEF. Engine instruments panel should have microprocessor based Genset monitoring system capable of displaying Running Hour, RPM, lubbrication oil pressure indication, lubrication oil temperature, battery charging indication, overspeed indication, fuel level etc. The control Panel should equipped with MCCB/ACB of suitable rating. |
| 6 | E) Base frame and foundation : Both the engine and alternator shall be mounted on suitable base frame made of MS channel & coupled through a flexible coupling or close coupled which shall be installed on existing cement concrete foundation and vibration isolation arrangements as per recommendation of manufacturer. |
| 7 | F) First filling of the FUEL Tank and DEF tank shall be done by contractor. |
| 8 | G) DG set will be offered for Inspection and Testing at OEM's Works ( as per approved QAP ) in presence of Departmental Engineers .In case of 13 hour running testing at OEM's works, cost of actual consumables will be reimbursed. |
| 9 | Note: 1. During the DLP, the contractor shall arrange for servicing of the DG set through authorized dealer of OEM, as per the manufacturers guidelines. The actual cost of consumables used during servicing will be reimbursed to the contractor by the end user department.2. Manufacturer / OEM must have its authorized service dealer in Rajasthan. Which can provide service within 6 Hours of compalint registration. |
| 10 | 125 KVA at 0.8 pf 415V 50Hz 3-ǿ with 4 Cylinder Engine |
| 11 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 12 | 120.0 Sq. mm |
| 13 | 3.5 core |
| 14 | S&F following sizes of ISI marked ( IS:14927 P - II ) virgin material UPVC trunking along with accessories like coupler, inner, outer, elbow, square box, tee, end cap etc. on surface with screws, expansion fasteners as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 15 | 100 mm x 50 mm |
| 16 | Supply, Installation, testing and commissioning of BIS compliance Professional series Diagonal Screen size 43\\" LED with Resolution 3,840 x 2,160 (4K UHD) long with Static (Panel) Contrast Ratio (1300:1) or better with viewing angle 78/178 degree with response time of 8ms along with HDMI In 2.0 - 2 nos., USB 2 nos., RS 232- 1 nos., RJ 45- INos. with Built in Speaker(10W + 10W), with high speed processor and android or other reputated operationg system along with 4 GB RAM along with all audio and video decoder, Stand-by / sleep / off mode power 0.5 watt, - Al as per pre approved by Engineer in charge.For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 17 | Supply and installation of high tensile low carbon steel rod molecularly bonded with 99.9 % Copper thickness (250 microns) and confirming to UL 467, IS/IEC 62561-2 of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :- |
| 18 | (a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole |
| 19 | (b) filled with anti corrosive conductive compounds with the permanent sealings at both the ends, CPRI/ ERDA tested with RMS capacity of minimum 30 KA for withstanding 1 second .To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated lab for low resistivity ( less than 0.12 Ohm - meter ) & high conductivity in nature with carbon as a major content as per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts |
| 20 | © Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt |
| 21 | (d) Place Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. |
| 22 | (d) Testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book. |
| 23 | (e) Test certificates for confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 24 | 25 mm thick and 3 Mtr. Long |
| 25 | Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 26 | 25mm x 3mm G.I. ( Hot Dipped ) Strip |
| 27 | 25mm x 3mm tinned copper strip |
| 28 | SITC of PLC Based Auto main failure (AMF) Panel fabricated from CRCA sheet steel 2 mmThick , Powder coated finish , Engine Start & Stop commands, control Relays , Ammeter & Voltmeter with selector switches, Control & 2 nos 4 pole Power Contactors with 2 no. of required size 4 pole MCCB, Timers, Electronic Hooter ,Visual & Alarm indication for faults, UPS, operator interface panel complete in all respect suitable for following capacity DG sets: Appropriate Test Certificate/ report of product/accessories from OEM/Panel Manufecturer shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 29 | 100 to 140 KVA |
| 30 | Supply & Installation of D.P. Structure With AIR BREAK SWITCH having following specifications A, B, C, D, E. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 31 | A) Double pole structure on 2 no ISMB ( I beam ) of size 150 x 75 mm, 10 mtr length using 7 no MS channel each of size 100 mm x 50 mm x 2500 mm complete in all respect with nuts, springs washers, clamps as required. |
| 32 | B) Off load type gang operated 3-pole vertical flute type switch suitable for 11KV ; 400A ,3-ø, central post rotating double break isolator complete with MS hardware , copper moving & fixed contact ,assembly of 9 nos pin insulator ,GI pipe of suitable length for operation. |
| 33 | C) 3nos Vertical / Horizontal mounted 11kv horn gap fuse set /drop out 11kv barrel fuses mounted on 6no pin insulators |
| 34 | D) 3 piece non linear resistor type. lighting arrestor of approved make suitable for 3 wire, 11kv Overhead line with rated voltage of 9kv rms & nominal discharge current rating of 5 ka & complete with galvanized clamping arrangement GI bolts, nuts, washer etc as required. |
| 35 | E) 3 no 11kv ACSR conductors mounted on pin type insularors as required. 6.GENERAL:The go shall be operated by hand operated liver properly earthed with provision for locking mounted at 3’ |
| 36 | Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 37 | SITC of 11kV 630 Amps 21KA for 3 Sec. SF6 insulated, outdoor duty (IP54) , Extensible / Non extensible type Ring main unit (RMU) manually operated in combination of VCB modules and Load Break switch consisting of Copper busbar in SF6 insulated 304 (Non-Ferrite Non-Magnetic Grade) stainless steel enclosure of thickness 2.5mm with manometer. The HV switchgear and control gear should be confirming to IEC-62271-100, IEC-62271-200-2003 & IEC-60694-1996. The RMU should be internal arc tested for 21KA for 1Second with IAC-AFL classification for gas tank. Vacum Interrupter of VCB should be RMU Manufacturer’s own make. Each feeder of RMU should have voltage presence indicator. . and compring of followings:- 1 no. microprocessor based Self powered numerical relay with over Current/ earth fault & short circuit protection with each VCB feeder. - 3 Nos. Protection CT shall be of Burden 2.5VA, ratio 50/1A, Class of Accuracy class 5P10 for O/C and E/F protection for each VCB.- 1 No. Manometer for each tank,- 1 nos. Fault Passage indicator,-Right angle boots for all the feeder Modules All the type test certificates as per IEC from Third party NABL / CPRI / ERDA accrediated lab to be submitted. (Cost of RCC Foundation / Steel Structure to be paid Extra) All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR |
| 38 | Extensible 3 way RMU with 1 no. VCB & 2 No. Load Break Switch Please Enable Macros to View BoQ information |