| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GE Utilities Udhampur Name of Work: Repair /Maint of service main cables, voltage stabilizer, UPS earthing and other allied works in the AOR of MPH under GE (Utilities) Udhampur Contract No: GE/U-04/2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | Earthing complete with galvanised steel earth plate electrode 60 cm x 60cmx 6 mm thick buried directly in ground vertically to a depth not less than 2.25 mtrs below ground level with top edge of earth plate at a depth not less than 1.5 mtr below ground level connected to galvanised iron strips 32 x 6 mm by means of nuts both check nuts and washers made of galvanised iron or steel earth strip protected by galvanised iron pipe 40 mm bore medium grade upto ground level as directed and including concrete pit in PCC ( 1 : 3 : 6) type C1 pre cast RCC cover slab 30 cm x 30 cm x 10 cm thick including reinforcement with 8 mm dia steel deformed bars at the rate of 10 cm both ways with one lifting handle made of 8 mm dia MS bar funnel, wire mesh 20 mm bore galvanised iron or steel pipe medium grade for watering charcoal on coke and salt in alternate layers, necessary excavation and earth work in any type of soil complete all as shown in electrical plate No 5 of MES schedule Pt-I and testing on completion, complete all as specified and directed by Engineer-in-Charge. |
| 3 | Earthing complete with galvanised steel earth plate electrode 60 cm x 60cmx 6 mm thick buried directly in ground vertically to a depth not less than 2.25 mtrs below ground level with top edge of earth plate at a depth not less than 1.5 mtr below ground level connected to earthing lead of 4 mm dia galvanised iron by means of nuts both check nuts and washers made of galvanised iron or steel earth strip protected by galvanised iron pipe 40 mm bore medium grade upto ground level as directed and including concrete pit in PCC ( 1 : 3 : 6) type C1 pre cast RCC cover slab 30 cm x 30 cm x 10 cm thick including reinforcement with 8 mm dia steel deformed bars at the rate of 10 cm both ways with one lifting handle made of 8 mm dia MS bar funnel, wire mesh 20 mm bore galvanised iron or steel pipe medium grade for watering charcoal on coke and salt in alternate layers, necessary excavation and earth work in any type of soil complete all as shown in electrical plate No 5 of MES schedule Pt-I and testing on completion, complete all as specified and directed by Engineer-in-Charge. |
| 4 | Earthing complete with copper earth plate electrode 60 cm x 60cmx 3.15 mm thick buried directly in ground vertically to a depth not less than 2.25 mtrs below ground level with top edge of earth plate at a depth not less than 1.5 mtr below ground level connected to copper strips 20x3 mm by means of nuts both check nuts and washers made of galvanised iron or steel earth strip protected by galvanised iron pipe 40 mm bore medium grade upto ground level as directed and including concrete pit in PCC ( 1 : 3 : 6) type C1 pre cast RCC cover slab 30 cm x 30 cm x 10 cm thick including reinforcement with 8 mm dia steel deformed bars at the rate of 10 cm both ways with one lifting handle made of 8 mm dia MS bar funnel, wire mesh 20 mm bore galvanised iron or steel pipe medium grade for watering charcoal on coke and salt in alternate layers, necessary excavation and earth work in any type of soil complete all as shown in electrical plate No 5 of MES schedule Pt-I and testing on completion, complete all as specified and directed by Engineer-in-Charge. |
| 5 | Supply and fix earth pit chamber board of 3.15 mm thick mild steel sheet sheet of size min 45cmx30cm fixed with 12 mm thick MS rod two nos upto 90 cm height by nuts/bolts including spray painting with two coats of synthetic enamel black paint complete MS sheet both side including writing letter min 6 cm height i.e Earth pit No . Location Earthing test value and date and other letters, complete all as specified and directed by Engineer-in-Charge. |
| 6 | Supply and fix in repair Earth continuity conductor or main earthing lead fixed to wal on batten or recess or chasses or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation of 25x4 mm galvanised iron strip, complete all as specified and directed by Engineer-in-Charge. |
| 7 | Supply and fix in repair Earth continuity conductor or main earthing lead fixed to wal on batten or recess or chasses or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation of earthing lead of 4 mm dia galvanised, complete all as specified and directed by Engineer-in-Charge. |
| 8 | S&F double walled corrugated (DWC) pipe of size 50 mm including snap fit coupler conforming to IS14930 (Pt-II)/IS16205 Pt-II for protection of LT cable in under ground, complete all as specified and directed by Engineer-in-Charge. Make: REX/Tirupati Plastomatics Pvt Ltd |
| 9 | Excavation in trenches n.exc 1.5 mtr wide and n.exc 1.5 mtr in depth and getting out soft/loose soil complete all as specified and directed by Engineer-in-Charge for foundation of stay, laying of cable etc. |
| 10 | Returning filling in soil including spreading, levelling, watering and well ramming in layers not exc 25 cm, complete all as specified and directed by Engineer-in-Charge. |
| 11 | Removing excavated material soil n.exc 50 m and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-Charge. |
| 12 | Taking up old serviceable/unserviceable UG cable from trench for replacement , repair and re-laying or re-routing of size 10 Sqmm to 35 Sqmm 3.5 core and make good the disturbed surface to the existing complete all as specified and directed by Engineer-in-Charge. Earth work shall be measured and paid separately under appropriate items of Sch-'A') |
| 13 | Supply, laying, testing and commissioning LT UG armoured, XLPE insulated, inner and outer sheathed,PVC insulated with multi stranded aluminium conductor cable of 1100 volts grade, of size 16 Sqmm 4 Core ISI marked with IS-7098, laid in trenches/floor/duct/wall including aluminium lugs of suitable sizes complete all as specified and directed by Engineer-in-Charge. - |
| 14 | Supply, laying, testing and commissioning LT UG armoured, XLPE insulated, inner and outer sheathed,PVC insulated with multi stranded aluminium conductor cable of 1100 volts grade, of size 25 Sqmm 4 Coree ISI marked with IS-7098, laid in trenches/floor/duct/wall including aluminium lugs of suitable sizes complete all as specified and directed by Engineer-in-Charge. |
| 15 | M&L for dehydration & filtration of voltage stabilizer and E&M equiptment by dehydration plant (bringing plant at site) including testing of sample before and after dehydration and filtration to achieved 40 KV at 2.5 mm gap complete all as specified and directed by Engineer-in-Charge :-Note : (i) The filtration of the voltage stabilizer oil shall be carried out at different locations of GE (U) Udhampur(ii) The report before filtration & after filtration to be submitted by contractor .(iii) Oil for topping up will be measured and paid separately.(iv) Centrifuging Machine with all T&P & testing eqpt required for dehydration to be arranged by contractor. |
| 16 | Supply & toping up of new voltage stabilizer oil (in sealed barrel) conforming to IS 335 std having dielectric strength 40 KV at 2.5 mm gap after initial dehydration complete all as specified and directed by Engineer-in-Charge. Make : Savita/Castrol/Power True/Truoil. |
| 17 | M & L for rewinding 433 Volts LV coils of voltage stabilizer and other E&M equipment of using proper size super enameled copper wire of existing gauge and proper number of turns alongwith insulating material i.e leatheroid, paper insulation, cotton tapes, empire tapes, wooden block packings, PVC sleeves, soldering and varnishing with insulating varnish , colding/drying etc complete suitable for working voltage 1.1 KV including three layer insulated material as per existing size of core including testing and commissioning complete all as specified and directed by Engineer-in-Charge. NOTE :-i). Oil filtration, supply of new oil will be measured separately.ii). All petty parts including nut, bolts, gasket minor weldings are deemed to be included the rate quoted.iii). The rate for taking out,refixing after repair, both side transportation, lifting /unloading of voltage stabilizer by crane /manual should be deemed to include in the rate quoted. |
| 18 | Supply and fixing in repair digital voltmeter, ranging from 0 to 500 Volts as per existing make and model, including providing necessary electrical connections (to accommodate in panel board) complete all as specified and directed by Engineer-in-Charge. |
| 19 | Supply and fixing in repair digital ammeter, ranging from 0 to 400 Amps (with CT of suitable ratio), as per existing make and model, including providing necessary electrical connections (to accommodate in panel board) complete all as directed by the Engr-in-Charge. |
| 20 | Supply and fix in repairs Indicator Lamps (LED type) as per existing make and model, including providing necessary electrical connections (to accommodate in panel board) complete all as specified and directed by Engineer-in-Charge. |
| 21 | Dismantling and taking out old worn out reversible synchronous motor from the voltage stabilizer and supply and fix reversible servo motor (3 Kgs.) with RC, single phase 230 Volts as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 22 | Dismantling and taking out old worn out reversible synchronous motor from the voltage stabilizer and supply and fix reversible servo motor (10 Kgs.) with RC, single phase 230 Volts as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 23 | Dismantling and taking out old worn out reversible synchronous motor from the voltage stabilizer and supply and fix reversible servo motor (20 Kgs.) with RC, single phase 230 Volts as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 24 | Supply and fix in replacement of Transformer suitable for 10 to 30 KVA Servo voltage stabilizer as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 25 | Supply and fix in replacement of Transformer suitable for 60 to 75 KVA Servo voltage stabilizer as per existing make and model complete all as specified and directed. |
| 26 | Supply and fix in replacement of Transformer suitable for 100 KVA Servo voltage stabilizer as per existing make and model complete all as specified and directed. |
| 27 | Supply and fix in replacement of Transformer suitable for 200 KVA Servo voltage stabilizer as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 28 | Supply and fix in replacement of Dimmer suitable for 10 to 30 KVA Servo voltage stabilizer as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 29 | Supply and fix in replacement of Dimmer suitable for 60 to 75 KVA Servo voltage stabilizer as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 30 | Supply and fix in replacement of Dimmer suitable for 100 KVA Servo voltage stabilizer as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 31 | Supply and fix in replacement of Dimmer suitable for 200 KVA Servo voltage stabilizer as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 32 | Dismantling and taking out old worn out Push Button/ Auto manual switch/Micro Switch/ Potentio Meter/ Limit Switch/ Lever Switch from the voltage stabilizer and supply and fix new Push Button/ Auto manual switch/Micro Switch/ Potentio Meter/ Limit Switch/ Lever Switch suitable for voltage stabilizer capacity up to 400 KVA and testing as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 33 | Dismantling and taking out old worn out Trigger Transformer 9V/18V from the voltage stabilizer and supply and fix new Trigger Transformer 9V/18V suitable for voltage stabilizer capacity up to 400 KVA complete all as specified and directed by Engineer-in-Charge. |
| 34 | Dismantling and taking out old worn out servo control panel from the voltage stabilizer and supply and fix new Servo Control panel suitable for voltage stabilizer capacity up to 400 KVA as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 35 | Dismantling and taking out old worn out servo control box from the voltage stabilizer and supply and fix new Servo Control Box suitable for voltage stabilizer capacity up to 400 KVA as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 36 | Dismantling and taking out defected PCB from the voltage stabilizer and supply and fix new Servo circuit card (PCB) suitable for voltage stabilizer capacity up to 200 KVA as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 37 | Supply and fix in repairs carbon brush of voltage stabilizer of capacity up to 400 KVA complete all as specified and directed by Engineer-in-Charge. |
| 38 | M&L for spray painting of servo voltage stabilizer/isolation Transformer, preparation of old painted surfaces of steel body by brushing/cleaning stain, greasy spots with thinner outside of voltage stabilizer/Isolation transformer indoor/outdoor type capacity 10 KVA to 30 KVA to match with existing colour complete all as specified and directed by Engineer-in-Charge. |
| 39 | Description all as per Ser item No 37.00 here-in-before, but capacity of 50 KVA to 75 KVA |
| 40 | Description all as per Ser item No 37.00 here-in-before, but capacity of 100 KVA to 200 KVA |
| 41 | Supply and fix in repair top cover gasket/cock sheet suitable for 10 KVA to 30 KVA Voltage Stabilizer/Isolation transformer complete all as specified and directed by Engineer-in-Charge. |
| 42 | Description all as per Ser item No 40.00 here-in-before, but capacity of 50/75 KVA |
| 43 | Description all as per Ser item No 40.00 here-in-before, but capacity of 100 KVA to 200 KVA |
| 44 | S & F in repairs control wiring of voltage stabilizer of capacity up to 200 KVA complete including disconnection from main cables and refixing the connectiong back after repair complete all as specified and directed by Engineer-in-Charge. |
| 45 | Supply and fix in repairs high low voltage cut off circuit of voltage stabilizer as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 46 | Routine periodical maintenance/servicing as and when required and testing of voltage stabilizer/Isolation Transformer of capacity up to 200 KVA complete including all consumables items like cotton, waste cloth, kerosene oil etc.Maintenance will be carried out complete all as specified and directed by Engineer-in-Charge. and comprising of the following :-(a) Greasing of all points.(b) Checking of servo(c) Checking of relays, selector switch, control switch, micro switch, carbon brush.(d) Checking of sensing trigger transformer, main transformer and dimmer.(e) Checking of ammeter, voltmeter contactor.(f) Checking and repairing of all internal wiring and connection of voltage stabilizer complete.(g) Checking of any leakage of oil.h) Repair/rewiring of broken/damaged control panel connection including measuring instruments, indicators, etc. |
| 47 | Comprehensive monthly maintence of 2 X 5 KVA UPS system installed in the AOR of MPH, complete all as specified and directed by Engineer-in-Charge. The detail scope of work consists of the following :-(i) Execute diagnostics and physical checks.(ii) Examine, clean, test, all equipment as required and repair parts as and when required.(iii) Measurement of UPS parameters like input/output voltage, frequency, current, frequency, room temperature etc.(iv) Battery Parameters like voltage, current and other relevant parameters.(v) Ensure dust free and controlled temperature conditions.(vi) The corrective maintenance may require multiple visits to site (vii) Check all Equipment LED LCD display board if any fault found to be rectified in the same cost.(viii) Checking of servicibility of MCB/MCCB if found unserviceagle to be replace without any extra cost. (ix) Checking of UPS fuse. if found us to be replace.(x) Keeping of servicibility of UPS is the responsibility of the contractor for the entire contract period.Note : Response time should be not more than 24 hours from the time of receipt of complaint on any working day between 9 AM to 6 PM. |
| 48 | Supply and fix inreplacement of Batteries (VRLA / Li-ion / Tubular, depending on model) of capacity (12V, 25Ah–65 Ah) as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 49 | Supply and fix in replacement of Batteries (VRLA / Li-ion / Tubular, depending on model) of capacity 12 Volt 150/180Ah as per existing make and model complete all as specified and directed. |
| 50 | Supply and fix in replacement of Battery fuses / battery breaker (DC MCB/MCCB) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 51 | Supply and fix in replacement of Battery connectors, links, and cables suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 52 | Supply and fix in replacement of IGBT modules (in inverter & rectifier sections) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 53 | Supply and fix in replacement of Power diodes / rectifier bridges as per existing make and model suitable for 05 to 10 KVA UPS complete all as specified and directed by Engineer-in-Charge. |
| 54 | Supply and fix in replacement of Snubber circuits (resistor + capacitor assemblies) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 55 | Supply and fix in replacement of DC bus capacitors (electrolytic, high voltage) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 56 | Supply and fix in replacement of inverter driver boards / gate driver cards suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 57 | Supply and fix in replacement of Control PCB / DSP board (system logic) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 58 | Supply and fix in replacement of input & output contactors / relays suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed. |
| 59 | Supply and fix in replacement of Static switch module (SCRs / Triacs) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed. |
| 60 | Supply and fix in replacement of input & output MCBs / MCCBs suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 61 | Supply and fix in replacement of Surge protection devices (SPDs) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 62 | Supply and fix in replacement of Current transformers (CTs) & voltage sensors suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 63 | Supply and fix in replacement of Cooling fans / blowers (fail quite often, need spares) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 64 | Supply and fix in replacement of Air filters (if used) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 65 | Supply and fix in replacement of Heat sink compound / thermal pads suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 66 | Supply and fix in replacement of LCD / HMI display unit suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 67 | Supply and fix in replacement of Communication cards (SNMP, Modbus, RS-485, etc.) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed. |
| 68 | Supply and fix in replacement of Control fuses (low-rating, PCB type) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 69 | Supply and fix in replacement of Cables and connectors (signal & power) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 70 | S & F in replacement on load change over switch 415 V, 4 pole, 100 A as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 71 | S&F in replacement on load change over switch 415 V, 4 pole, 125 A as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 72 | S&F in replacement on load change over switch 415 V, 4 pole, 160 A as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 73 | S&F in replacement on load change over switch 415 V, 4 pole,200 A open execution as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 74 | S&F in replacement on load change over switch 415 V, 4 pole, 250 A open execution as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 75 | S&F in replacement on load changeover switch 415 V, 4 pole, 320A open execution as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 76 | S&F in replacement on load changeover switch 415 V, 4 pole, 400A open execution as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 77 | Attending breakdown for Servo Voltage stabilizer/ UPS detect fault related to breakdown by a service Engineer complete all as specified and directed by Engineer-in-Charge. Note:- (a) Spares will be measured and paid separately under relevant items.(b) The break down complaint should be attended within 8 hours by the intimation of Engr-in-charge or concern JE E/M by telephonically / verbally. (c) Not attended of complaint within eight hours will lead to recovery from subsequent payment in the following manner :- (i) Not attending within 0 to 8 Hours - Rs. 2000.00 (ii) Not attending within 8 to 16 Hours- Rs. 2000.00 (iii) Not attending within 16 to 24 Hours- Rs. 2000.00 (iv) Not attending after24 Hours - Rs. 5,000.00 (v) The maximum recovery will be Rs. 50,000.00 plus the expenditure incurred for rectification of the same by any other means. |
| 78 | Supply, Install, Test and Commissioning of LT feeder pillar box outdoor type fabricated out of 3.15 mm thick CRCA sheet double door, CPRI approved complete with powder coating with seven tank process mounted on M.S angle Iron frame of size 40x40x6mm, duly grouted with PCC reqd, complete all as specified and directed by Engineer-in-Charge with the following:-(a) S & F copper bus bar 600 Amp with cloured heat shrinkable insulated sleeve 415 Volts as per IS of suitable size mounted on DMC/epoxy insulator (not less than 50mmx50mm conical type at a maximum interval of 500 mm- 01 Set.(b) S&F MCCB FP 400 Amps 35 KA - 01 No |
| 79 | Supply, Install, Test and Commissioning of LT feeder pillar box outdoor type fabricated out of 3.15 mm thick CRCA sheet double door, CPRI approved complete with powder coating with seven tank process mounted on M.S angle Iron frame of size 40x40x6mm, duly grouted with PCC reqd. with the following:-(a) S & F copper bus bar 400 Amp with cloured heat shrinkable insulated sleeve 415 Volts as per IS of suitable size mounted on DMC/epoxy insulator (not less than 50mmx50mm conical type at a maximum interval of 500 mm- 01 Set.(b) S&F MCCB FP 250 Amps 35 KA - 01 No |
| 80 | Supply and fix battery charger of capacity 24 V/110 Volt, 100 Amp single phase 3 feeder BATTERY CHARGER and D.C distribution board in common cubicle . The charger is schedule for 230V+/-10%, AC input and the output is suitable to charge of 24V DC 100Ah batteries and also supply load, The output voltage remains constant within +/-2% for AC input voltage variation 230V +/- 10% and load variation 0-100%, current ratings 100 A, over charging, overvoltage, undervoltage, over load and current limit protection complete all as specified and directed. |
| 81 | M & L for replacement of battery brass terminal with nuts and bolts complete all as specified and directed by Engineer-in-Charge. |
| 82 | M&L in replacement of Battery lead complete of size 16 Sqmm as per site complete all as specified and as directed by Engineer-in-Charge. |
| 83 | Taking down/dismantling and refixing of any capacity of stabilizer/LT equipments by using Hydra mechine/suitable crane complete and including tranportation shifting to approved manufacturer/Workshop including testing and commissioning complete all as specified and directed by Engineer-in-Charge. (Note- Dismantling and disconnecting HT cable and LT cables and refixing after rewinding and Transportation from Udhampur Army cantt to Workshop and workshop to Udhampur will be paid as one job) |
| 84 | Taking down/dismantling of any capacity of em equipment /stabilizer/LT equipments by using Hydra mechine/suitable crane complete and including tranportation shifting to MPH and placed at safer place complete all as specified and directed by Engineer-in-Charge. (Note- Dismantling and disconnecting HT cable and LT cables from E/M equipment and Transportation from Udhampur Army cantt to MPH and other store as directed by engr-in-charge will will be paid as one job) Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |