| 1 | Taking down care fully copper/aluminium point wiring from wooden batten or conduits (light, fan, socket or power) complete incl fittings such as switches, sockets, ceiling roses, pendents, regulators, light fittings any type etc to be measured seperately) and making good disturbed surfaces of walls, floors etc complete all as specified and directed by Engineer in charge. |
| 2 | M & L for Point wiring complete with 1.5 sqmm single core PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor drawn through and including non-metalic rigid PVC conduit medium grade ISI Marked and all conduit accessories concealed in wall/ceiling/fixed to roof/truss/columns etc and including provision of 1.5 sqmm PVC insulated copper cable FRLS as earth continuty, fabricated branded modular metal flush box / M S steel terminal boxes, concealed in walls with suitable modular inner and outer plate / 3 mm thick laminated top sheet cover for housing switches , socket out let and fan regulators etc. all as specified and as directed for the followings:- |
| 3 | One light/exhaust fan point controlled by one way switch |
| 4 | One bell/buzzer point controlled by one bell push |
| 5 | One light point controlled by two Nos two way switches |
| 6 | One 3 pin 5 Amps socket outlet point controlled by one way switch on independent board. |
| 7 | One 3 pin 5 Amps socket outlet point controlled by one way switch on same board |
| 8 | All as per item No 2 but point wiring with 4 Sqmm single core copper cable and earth continuity wire with 4 Sqmm single core stranded copper cable for one three pin 15 socket outlet point on independent board complete all as specified and directed by Engineer in charge |
| 9 | M & L for Point wiring complete with 1.5 sqmm single core PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor drawn through existing PVC conduit, including provision of 1.5 sqmm PVC insulated copper cable FRLS as earth continuty and fabricated branded modular metal flush box/M S Steel terminal boxes, concealed in walls with suitable modular inner and outer plate/3 mm thick laminated top sheet cover for housing switches , socket out let and fan regulators etc. all as specified and as directed for the followings:- |
| 10 | One light/fan point controlled by one way switch |
| 11 | One bell /buzzer point controlled by one bell push |
| 12 | One light point controlled by two Nos two way switches |
| 13 | One 3 pin 5 Amps socket outlet point controlled by one way switch on independent board. |
| 14 | One 3 pin 5 Amps socket outlet point controlled by one way switch on same board |
| 15 | All as per item No 4 but point wiring with 4 Sqmm single core copper cable and earth continuity wire with 4 Sqmm single core stranded copper cable for one three pin 15 socket outlet point on independent board complete all as specified and directed by Engineer in charge. |
| 16 | Taking down old unserviceable MS Steel terminal boxes from wall and supply and fixing fabricated branded modular metal flush box 1module/2 module concealed in walls with suitable modular inner and outer plate for housing switches, socket out let and fan regulators etc including make good of disturbed surface complete all as specified and directed by Engineer in charge. Note-Switch,socket, regulator will be paid separately |
| 17 | Taking down old unserviceable MS Steel terminal boxes from wall and supply and fixing fabricated branded modular metal flush box 3 module/4 module concealed in walls with suitable modular inner and outer plate for housing switches, socket out let and fan regulators etc including make good of disturbed surface complete all as specified and directed by Engineer in charge. Note-Switch,socket, regulator will be paid separately |
| 18 | Taking down old unserviceable MS Steel terminal boxes from wall and supply and fixing fabricated branded modular metal flush box 6 module concealed in walls with suitable modular inner and outer plate for housing switches , socket out let and fan regulators etc. including make good of disturbed surface complete all as specified and directed by Engineer in charge. Note-Switch,socket, regulator will be paid separately |
| 19 | Taking down old unserviceable MS Steel terminal boxes from wall and supply and fixing fabricated branded modular metal flush box 8 module concealed in walls with suitable modular inner and outer plate for housing switches , socket out let and fan regulators etc including make good of disturbed surface complete all as specified and directed by Engineer in charge. Note-Switch,socket, regulator will be paid separately |
| 20 | M&L in replacement switch Modular type 6 Amps 1 Way,1 module, 230V AC complete all as specified and directed by Engineer in charge. |
| 21 | M&L in replacement switch modular type 6 amp SP two way, 1 module complete all as specified and directed by Engineer in charge. |
| 22 | M&L in replacement Modular Bell push button SP, 6 Amps, 1 module 230V AC complete all as specified and directed by Engineer in charge. |
| 23 | M&L in replacement Modular socket outlet 2/3 pin 6 Amp socket 2 module complete all as specified and directed by Engineer in charge. |
| 24 | M&L in replacement switch Modular type 16 Amps 1 way, 1 module with modular plate 230V AC complete all as specified and directed by Engineer in charge. |
| 25 | M&L in replacement Modular socket outlet 2/3 pin 6/16 Amp universal socket 2 module complete all as specified and directed by Engineer in charge. |
| 26 | M&L in replacement modular stepped type electronic fan regulator 120W, 2 module all as specified and directed by Engineer in charge. |
| 27 | M&L in replacement switch piano flush button type single pole one way 6 Amps complete all as specified and directed by Engineer in charge. |
| 28 | M&L in replacement switch piano flush button type single pole two way 6 Amps complete all as specified and directed by Engineer in charge. |
| 29 | M&L in replacement bell push single pole 6 Amps complete all as specified and directed by Engineer in charge. |
| 30 | M&L in replacement switch piano flush button type single pole 16 Amps complete all as specified and directed by Engineer in charge . |
| 31 | M&L in replacement socket outlet, 2 in 1, 3 pin 6 and 16 Amp single pole complete all as specified and directed by Engineer in charge. |
| 32 | M&L in replacement socket outlet 5 pin 6 Amp flush button type complete all as specified and directed by Engineer in charge. |
| 33 | M&L in replacement regulator electronic switch/socket type 5 steps suitable for 1200/1400 mm sweep 230 volts all as specified and directed. |
| 34 | M&L in replacement bell electric (ding dong) 230 volt, SP all complete all as specified and directed by Engineer in charge . |
| 35 | M/L in replacement insulated body, angle holder (metal ring) with back plate complete all as specified and directed by Engineer in charge. |
| 36 | S&F ceiling rose PVC/Polycarbonate type with three terminals complete all as specified and directed by Engineer in charge . |
| 37 | M&L in replacement sheet metal enclosure, single pole and neutral with a two pin and earth plug and socket 240 Volts grade 20Amps complete with one single pole MCB 'C' series 10/20 A capacity complete all as specified and directed by Engineer in charge. |
| 38 | Supply and fix LED batten luminaire surface mounted, 4 feet system wattage of 20 Watts, > 2000 systems lumen outputwith lifetime of 25000 burning hours with 70% of its initial lumen maintained. CRI>70, Power Factor >0.90, THD< 10%, colour temperature-6500K, surge protection 2.5 KV in CM, IP-20 protected, Class-1, short circuit and over circuit protection, voltage range-180 to 270 Volts AC, temperature range 0 to 45 Degree C minimum and including connecting up with PVC sheathed 1.5 sqmm 3 core copper conductor flexible wire from ceiling rose to fitting fixed complete all as specified and directed. |
| 39 | Supply and fix LED batten luminaire surface mounted 2 feet system wattage of 10 watts and not less than 1000 lm with life time of 25000 burning hours with 70% of its initial lumen maintained, CRI >70, power factor > 0.90, THD < 10%, color temperature >6500 K , surge protection 2.5 KV in CM IP- 20 protected,voltage range - 180 to 270 volts AC, temperature range 0 to 45 Degree C minimum, system efficiancy at luminarie level ≥100 Lumens/watt and including connecting up with PVC sheathed 1.5 sqmm 3 core copper conductor flexible wire fixed complete all as specified and directed. |
| 40 | S&F LED 2 X 2 ft backlite surface mounted fitting 36/40 Watts not less than 3600lm with Metallic CRCA powder coated body with high efficiency opal/PMMA diffuser with system efficacy>100 lm/W, CRI>70, color temperature >5700k, IP 20, Power factor<0.90, THD<10%, 25000 burning hours , Ambient temperature 0 to 50 Deg C, Driver should meet IEC complaint for safety, with voltage variation range of 180-270 V and surge protection of 2.5 KV including necessary fixing arrangementsfixed complete all as specified and directed. |
| 41 | Supply and fix LED 9/10 watts bulkhead fitting with powder coated die cast aluminium housing with glass/ non yellowing polycarbonate cover, IP65 Protection, System level efficacy of the Luminary is > 100 lm/W with a life class of 25,000 burning hours at L70 criteria, Power Factor >0.90, driver with Voltage range 180-270V, Temperature range 0 to 45 Deg minimum, Driver efficiency >85%, THD<10%, CRI>70, Color Temperature-6000K, surge protection of 2.5 KV, including connecting up with necessary PVC sheathed 3 core 1.5Sqmm copper conductor flexible wire complete all as specified and directed. |
| 42 | S&F in replacement of decorative type wall mounted luminaire (Comet) with unbreakable poly carbonate materials suitable for 1x14 watt LED bulb B22 base complete all as specified and directed by Engineer in charge. |
| 43 | Supply and fix surface ceiling mounted, LED down light fitting 12 watts with die cast aluminium housing and system wattage of 12W, system efficacy at luminary level ≥ 100 Lumens/watt, 25000 burning hours, 6500K color temperature with CRI >70, Power Factor > 0.90, with multi stage high Isolate CC-CV operated driver with voltage variation range - 180 to 270 Volts AC, and surge protection of 2.5 KV, and including connecting up with PVC sheathed 3 core 1.5Sqmm copper conductor flexible wire complete all as specified and directed. |
| 44 | S&F 35W high efficient LED street light fitting with pressure die cast Aluminum housing and has lenses specially designed for street lighting with polycarbonate cover, system level efficacy of the luminarie should more than 110 lm/W. Color temperature is around 6500 K with a color rendering index of 70. The luminaire is IP-65 protected. It has an electronic driver with a power factor>.0.90, voltage variation range 180-270V, THD<10%, High and low protection along with a surge protection of 4 KV including provision of suitable dia GI light grade pipe1.5 meter length bend to shape and necessary clamps etc for fixing the light fittings on wall fixed complete as specified and directed. |
| 45 | M & L for opening up the winding of ceiling fan 1200/1400 mm sweep any make any type and rewinding with super enamelled copper winding wire after inserting super enamelled insulating material binding it with insulating tape etc completely and varnishing well including drying completely. Replacement of worn out / unserviceable capacitor bearing , bush , safety pins, nuts, bolts, washers , rubber bush with ceiling fan clamp, cable PVC flexible 23/0076 and testing the ceiling fan after re-fixing of the blades to the entire satisfaction of Engineer-in-Charge. |
| 46 | Supply and Fixing LED bulb 9 watts, 900 lumens output, 6500K suitable for B-22 base complete all as specified and directed by Engineer in charge . |
| 47 | Supply and Fixing LED bulb 14 watts, 900 lumens output, 6500K suitable for B-22 base complete all as specified and directed by Engineer in charge . |
| 48 | Supply and fix in repair MCB SPN 63 Amps 240 volts 10 KA 50 HZ 'C' curve complete all as specified and directed by Engineer in charge. |
| 49 | Supply and fix in repair MCB SPN 40 Amps 240 volts 10 KA 50 HZ 'C' curve complete all as specified and directed by Engineer in charge. |
| 50 | Supply and fix in repair MCB SPN 32 Amps 240 volts 10 KA 50 HZ 'C' curve complete all as specified and directed by Engineer in charge. |
| 51 | Supply and fix in repair MCB SP 6-32 Amps 240 volts 10 KA 50 HZ 'C' curve complete all as specified and directed by Engineer in charge. |
| 52 | Supply and fixing ventilating fan 250 mm sweep, 1250 RPM, non metallic resin body, single phase 240 volts AC 50 Hz and connecting up complete including louvers and provision of copper cable 3 core of size 0.5 sqmm for connection from ceiling rose to fan complete all as specified and as directed. |
| 53 | Supply and fixing ventilating fan 200 mm sweep, 1250 RPM, non metallic resin body, single phase 240 volts AC 50 Hz and connecting up complete including louvers and provision of copper cable 3 core of size 0.5 sqmm for connection from ceiling rose to fan complete all as specified and as directed. |
| 54 | Supply and fixing exhaust fan 300 mm sweep (steel Body), 1250 RPM, non metallic resin body, single phase 240 volts AC 50 Hz and connecting up complete including louvers and provision of copper cable 3 core of size 0.5 sqmm for connection from ceiling rose to fan complete all as specified and as directed. |
| 55 | Supply and fix wall mounted fan 400mm, 230 volts, 50 Hz 1420 RPM with 90 degree oscillation and having speed control by pull cord system all as specified and directed. |
| 56 | S & F water heater storage type (Geyser) steel body, vertical type with suitable size of fastner and including provision and connecting up of SS braided pipe with adopter for inlet and outlet water connection, having adjustable knob for temperature control and inner tank material of superior glass lined tank and outer body material ABS with high pressure with standing capacity upto 8 bar pressure complete all as specified of capacity 25 ltr having heating element 2 KW and not less than 5 star rating with minimum two year warrant on product. Note : old unservicable geyser will be deposoted in MES yard. conversion against low rating to 5 star rating. |
| 57 | Supply and fixing wall mounted angular electric chimney black colour of suction power not less than not less than 1050 cum/Hr,Al casette with stainless steel outer layer, touch control panel,3 speed motor with 250 watt with decorative smart cooker hood SS and glass, energy efficent LED light with digital display, including ducting not less than 12 feet as per site required complete all as specified and as directed by Engr-in-Charge. |
| 58 | Supply and fixing ceiling fans complete with blade, down rods, with remote and accessories rated speed not less than 330 RPM, 230 V, 1200 mm sweep, air delivery not less than 220 CMM, BEE five star rated voltage range 180 - 270 volts with brushess direct current motor (BLDC) all as specified and directed by Engr in Charge. (Against BLDC converson). Old fan shall be deposited to MES store yard. |
| 59 | S&F in repair sub main wiring with two runs of 4 Sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable with one run of 2.5 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable as earth continuity conductor, drawn through and including 25 mm dia non metallic rigid PVC conduit and conduit accessories on surface of walls complete all as specified and directed. |
| 60 | M&L for fan motor of ventilating fan 250/300mm sweep plastic body operated on single phase 230 volts 50Hz electric supply as per sample complete including making necessary electrical connections and testing on site after replacement all as specified and directed by Engr-in-Charge at site. |
| 61 | Supply and fix in repair sub main wiring complete with two runs of 4 Sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable with one run of 2.5 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable as earth continuity conductor, drawn through existing metallic/ non metallic conduit in walls all as specified and as directed. |
| 62 | Supply and fix in repair sub main wiring complete with two runs of 6 Sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable with one run of 6 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable as earth continuity conductor, drawn through existing metallic/ non metallic conduit in walls all as specified and as directed. |
| 63 | Supply and fix in repair sub main wiring complete with two runs of 10 Sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable with one run of 10 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable as earth continuity conductor, drawn through existing metallic/ non metallic conduit in walls all as specified and as directed. |
| 64 | S&F plug top, 3 pin, 20 amp earth metal clad (ISI marked) complete all as specified and directed by Engineer in charge. |
| 65 | S&F socket 3 pin 20 amp earth metal clad (ISI marked) complete all as specified and directed by Engineer in charge . |
| 66 | S & F PVC Gang box surface type heavy duty suitable for single switch & socket 5 Amps complete all as specified and directed by Engineer in charge . |
| 67 | S & F PVC Gang box surface type heavy duty suitable for two switch & two socket 5 Amps complete all as specified and directed by Engineer in charge . |
| 68 | S & F Gang box surface type heavy duty suitasble for 15 Amps switch and socket complete all as specified and directed by Engineer in charge. |
| 69 | M & L for in replacement only single core PVC insulated cable 1.5 Sqmm FRLS 1100 Volts with copper multi stranded conductor and drawing in existing concealed conduits, all as specified and directed by Engr-in-Charge. |
| 70 | M & L in replacement for only single core PVC insulated cable 2.5 Sqmm FRLS 1100 Volts with copper multi stranded conductor and drawing in existing concealed conduits , all as specified and directed by Engr-in-Charge. |
| 71 | M & L in replacement for only single core PVC insulated cable 4 Sqmm FRLS 1100 Volts with copper multi stranded conductor and drawing in existing concealed conduits , all as specified and directed by Engr-in-Charge. |
| 72 | M & L in replacement for only single core PVC insulated cable 6 Sqmm FRLS 1100 Volts with copper multi stranded conductor and drawing in existing concealed conduits , all as specified and directed by Engr-in-Charge. |
| 73 | M & L in replacement for only single core PVC insulated cable 10 Sqmm FRLS 1100 Volts with copper multi stranded conductor and drawing in existing concealed conduits , all as specified and directed by Engr-in-Charge. |
| 74 | M&L in replacement copper cable flexible 2 core PVC insulated of size 23/.0076 ll as specified and directed by Engr-in-Charge. |
| 75 | Supply and fixing LED Bollard integral decorative with PMMA diffuser 10 watt of height not less than 0.6 meter with IP 65 protection suitable for single phase 230 volts 50 HZ AC Supply including LED bulb , Poles, service wire and cement work complete all as specified and directed by Engineer-in-Charge. |
| 76 | Supply and fixing new generation, post top energy saving environmently friendly 15W , long life aesthetically designed with symmetrical light distribuiton spun aluminium landscape luminaire with high power LED as light sources. |
| 77 | Supply,installation,testing and commissioning of self priming regenerative pump 0.5/0.37 HP/KW, single Phase 220 volt+18%, discharge range 1950-450 LPH, head range 6-21 mtr insulation class ‘F’ of size 25x25mm complete including mounting bracket of angle iron of suitable size with necessary nuts, bolts and washer etc and making electrical connection with suitable size copper multi stranded cable of suitable length and connecting with GI/ uPVC/cPVC water supply line of any dia/size alongwith accessories such as tee,bend, elbow and socket etc including making bypass arrangement for any fault in pump in future to provide uniterrupted water supply to building all as specified and directed at site by Engr-in-Charge. |
| 78 | Supply,installation, testing and commissioning instant electric water heater with heating element of capacity 3 ltrs complete with all accessories such as safety valve, thermostat, NRV, connection piece etc and connecting with water mixture complete with all other accessories reqd for making water connections all as specified and directed. |
| 79 | Supply installation testing and commissioning of prepaid meter single phase, 2 wire 5-60A capacity,240 volts,50Hz, class-1.0 rating,IS 15884:2024, encased meter of protective class-II,load switching utilization category UC3 with key pad based token carrier interface including freedom device complete all as specified and directed. Model: Liberty 170 of make Secure. |
| 80 | Supply and fixing in replacement motor suitable for electric chimney not less than 250 watt single phase 230 volts 50 Hz of existing model including making necessary electrical connections all as specified and directed. |
| 81 | Supply and fixing in replacement PCB suitable for automatic electric chimney of existing model including making necessary electrical connections all as specified and directed. |
| 82 | Supply only SS braided pipe of 12 mm ((internal) suitable for hot/cold water, 60 cm long with brass nuts and rubber washers complete all as specified and directed. |
| 83 | Supply only heating element of 2 KW any type with nut bolt washer complete all as directed. |
| 84 | Supply only replacement of capacitor 3.15 Mfd, 240 V complete all as specified and directed. |
| 85 | Supply only replacement of capacitor 1.5/2.5 Mfd, 240 V complete all as specified and directed. |
| 86 | Supply and fix in repair MCCB 160 Amps, FP 415 volts 16 KA 50 HZ with thermal magnetic setting complete all as specified and directed by Engineer in charge. |
| 87 | Taking down of old/existing electric chimney of any make & model including exhaust pipe of any dia and length,strip opening of chimney after dismantling and unbolting all moveable/immoveable parts,cleaning of all complete chimney with suiatble cleaning agent upto entire satisfaction of Engineer-in-Charge, replacement of rusted nuts bolts& washers and defective parts as per existing make and model, reassembling all parts and refxing of chimney to its original position including exhaust pipe and testing on completion all as directed at site. Note: Parts shall be measured and paid separately. |
| 88 | Supply & fix in repair factory made epoxy powder coated Load line Distribution Board TPN-4 ways with double door (IP-43 protection) fabricated from minimum 1.6mm thick CRCA sheet and fixed flush to wall and suitable for universal mounting and including insulated 200 Amp copper bus bar, Isolated neutral bar, standard DIN rail, Earth bar and cable ties for cable management, top and bottom removeable gland plates with knockouts and suitable for one TPN- MCCB 125/160 Amp as incomer and 32 to 63 Amp SP MCBs outgoing complete all as specified and conforming to IS : 8623. |
| 89 | Supply and fix MCB DB SPN 12 way Horizontal, IP - 43 Protection double door 240 V AC 50Hz with for MCB SPN as incomer and DP/SP MCBs as out going with tinned copper bus bar ,neutral link earth link complete all as directed by Engineer -in- Charge. |
| 90 | Supply and fix MCB DB SPN 8 way Horizontal, IP - 43 Protection double door 240 V AC 50Hz with for MCB SPN as incomer and DP/SP MCBs as out going with tinned copper bus bar ,neutral link earth link complete all as directed by Engineer -in- Charge. |
| 91 | S&F wall mounted angular Electric chimney black colour of suction power not less than 1200Cum/Hr,Al casette with stainless steel outer layer ,touch sensor control panel, Auto off function, Brush-less DC motor and variation in speed control, oil collector Tray with decorative smart cooker hood SS and glass ,energy efficent Led light with digital display , including ducting not less than 12 feet as per site required complete all as specified and as directed by Engr-in-Charge. |
| 92 | S&F in replacement of ducting hose of wall mounted angular Electric chimney not less than 12 feet as per site required complete all as specified and as directed by Engr-in-Charge |
| 93 | M & L for in replacement only single core PVC insulated cable 1.5 Sqmm FRLS 1100 Volts with copper multi stranded conductor and drawing in existing concealed conduits, all as specified and directed by Engr-in-Charge. |
| 94 | Schedule of Credit Please Enable Macros to View BoQ information |