| 1 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed heavy class PVC conduit having wall thickness 2.0mm as required |
| 2 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 3 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 4 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 5 | Make:-finolex,Anchor,Plaza |
| 6 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 7 | S/D 3 X 1.5 sq. mm |
| 8 | Make:-finolex,Anchor,Plaza |
| 9 | Supplying and fixing 6 amps to 32 amps rating, 240/415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 10 | Single pole |
| 11 | Make:-L&T/Havells/schenider |
| 12 | Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 13 | 63 Amps |
| 14 | Make:-L&T/Havells/schenider |
| 15 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 16 | 6 way, Double door |
| 17 | 16 way, Double door |
| 18 | Make:-L&T/Havells/schenider |
| 19 | Providing & Laying of one number aluminium conductor, PVC insulated and PVC sheathed armoured/ XLPE power cable, 1.1 KV grade of following sizes on wall surface as required. |
| 20 | Armoured cable 6 sq. mm (Twin Core) |
| 21 | Armoured cable 10 sq. mm (Twin Core) |
| 22 | Makes:-Wipro/ Bajaj/Havells |
| 23 | Supplying and fixing of LED street light luminaire with the use of the latest technology 70 Watt (7000 lumens), 6500K made of CRCA housing and it should be compatible with specifications i.e. power factor ≥ 0.95, harmonic distortion ≤ 10% and efficacy ≥ 80 lumens per watt, CRI > 70, suitable for input voltage AC 150-270V, 50/60 Hz complete with all accessories, connections, testing and commissioning etc.as required. |
| 24 | LED 70 Watt Street light |
| 25 | Makes:-Wipro/Havells/ Bajaj |
| 26 | Supplying and erection of 7000mm (7 Mtrs.) Galvanized iron (GI) pole to be mounted on a 1:2:4 cement concrete base (pedestal) of 220 mm dia and 375 mm foundation bolt depth in a hole of excavation about 300 mm dia. and of suitable depth, to be filled with 1:3:6 cement concrete up to a height of 450 mm from bottom and then fitted with M.S. bolts / nuts of 12.5 mm dia; 375 mm length. complete in all respects as required:- |
| 27 | 7 Mtrs. Galvanized iron (G.I.) Pole |
| 28 | Supplying and fixing of 40 mm dia. M.S. pipe (medium class) bracket for mounting of fluorescent / HPMV / HPSV/ LED street light fitting on pole including bending the pipe to the required shape, bolts and washer, painting the flat iron with primer and finish paint etc. as required. |
| 29 | 40mm dia, MS Street light bracket |
| 30 | Excavation around the pole 600mm x 600mm to be filled with 1:3:6 cement concrete up to the depth of 600mm from bottom including paint of the pole as require complete in all respects. |
| 31 | Providing & fixing of G.I. box along with space for MCB and incomer/outcomer hols for cables properly fixed/ welding with the pole as required complete in all respects. |
| 32 | Dismental credit of useful materials@ 2500/- Please Enable Macros to View BoQ information |