| 1 | S/F of 16mtr high mast shaft of approved make with rising system, hot dip Galvanized inside & outside dip having pole sheet thickness 4mm top dia minimum 150mm bottom dia minimum 360mm base plate 32mm. thick suitable for wind velocity as per IS 875 part 3 & having no circumferential weld with accessories for high mast such as head frame suitable for 6 to 12 luminaries & its control gear boxes, 1.5 HP power tool motor, 3 point suspension with steel wire roop 6mm dia double drum winch. including making suitable foundation as per manufacture drawing & site reqirement along with foundation bolts nuts washers, anchors plates etc. complete in all respect as per direction and satisfaction to the Engineer in charge. 21.3.1 |
| 2 | S/F of twin unit aviation obstruction light (GEC–ZH 750) / Bajaj BJAOL –1 with transformer and neon spiral etc. complete in all respect, at the top of the building complete in all respect. CAT-AA 409 |
| 3 | S/F of following capacity of automatic street light cubical control panel paintd with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 series with contractor, HRC fuse,isolating switch metering instrument & instrument box with CTs etc.in case of TPN,complete in all respect. 25A TPN 807 e ii |
| 4 | Supply and burring of Safe Earthing Electrode T-19 (Hot Dip Galvanized), Length up to 2000mm, outer pipe 50mm, inner pipe 25, terminal Dia 12 mm, outer GI pipe of 16 swg and inner GI pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame with hinged cover & masonry husing (from electrode terminal to switch board, cost of 25 x 3 G.I . strip will be extra) 725 A |
| 5 | S&L of 25mm x 3mm G.I. Strip from earth electrodedirectly in the ground as requried complete in all respact 716 |
| 6 | Supplying installation, testing and commissioning of flood light powder coated pressure die cast aluminium body with built-in or separate driver as per the requirement with driver efficiency > 85% input voltage 140-270 volt, AC frequency 50/60 hz, operating temperature range -5°C to 50°C, internal surge protection of 5KV L,N,E as per IEC 61000-4-5, driver efficiency is >85%, THD <10% as per IEC 61000-3-2, P.F >0.95, IP-66, IK-10, CRI is > 70, under voltage and over voltage protection, EMI - EMC as per CISPR-15, lenses for beam angle 30 DEG, 120 DEG as per the application and the project requirement, suitable till able fitting, lifetime LED, driver, electrical. Circuitry) TV, of minimum 50000 burning hours with 70% initial lumen maintain till life end as per LM80, extrapolation as per ASTM 2111 report CCT 3000 Kelvin/ 4000 Kelvin/ 5700 Kelvin/ 6500 Kelvin as per ANSI bin, SDCM, standard deviation color matching is <5, maximum powder composition should not more than the specified rating and fixture shall be of relevant BIS standard complete in all respect, I/C, external connection with 1.5mm FRLSH/ HFFR PVC insulated copper conductor single core cable and earthing ETC as required with minimum 5 year OEM warranty system lumen efficiency >135 LM/ watt output LM79 and LM80 test report and all testing required for LEDs fixture as per BIS shall be submitted, safe size and CCT shall be as. Approved by Engineer-in-Charge, as per requirement, thermal management, heat sink of aluminium housing such that LED junction temperature shall not rise above 90 degree Celsius. 8.17.5 |
| 7 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cable 1100 volts grade in existing masonary open duck as directed by Engineer- In charge complete in all respect inculding axcavation and rifling . The armouring of the cable shall be properly connected with the earth conductor by clamps etc. (a) 16sq mm 4 core 20e.1.9 |
| 8 | S/F of 63 AMP. 415 volts metal clad TPN HRC type switch fuse unit complete with HRC fuse on angle irorn bracket in all respact 327 cat B |
| 9 | S/F of 100 Dia G.I. Pipe DSR 15.13.3 2025 Please Enable Macros to View BoQ information |