| 1 | Supplying & Laying following size XLPE insulated and PVC sheathed Aluminium conductor armoured power cable of 1.1 KV grade in existing DWC/GI/pipe/on surface / ground or loose for connection and testing etc as reqd. |
| 2 | 4 x 25 sq mm |
| 3 | 3.5 x 35 sq mm |
| 4 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 5 | Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 6 | 200 watt |
| 7 | Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 8 | 200 watt |
| 9 | Supplying and erection of galvanised 'D' iron clamps complete with shackle insulator (100 mm X 110 mm), G.I. bolts, nuts and washers, coach screws etc. as required. |
| 10 | Supplying and Drawing i/c connections & interconnections of following sizes of PVC Insulated and PVC Round Sheathed Multi Core Flexible Aluminium Conductor Heavy Duty Industrial Cables for Voltage Grade 1100 Volts as per IS: 694:2010 for interconnection from window to fitting of street light pole and high mast pole height of upto 30 mtrs.etc complete as reqd. |
| 11 | 3 x 4 sq.mm |
| 12 | Dismantling of Existing High mast accessories at a height of upto 16 mtrs and Supplying Installation testing and commissioning of winch assembly of upto 16 Mtr high mast, SS Wire rope, Lantern carriage ring, suitable Junction box for cable terminations, winch stand , window cover duly welded to the pole, handle, the double drum winch should be made of minimum 3 MM thick Hot dip galvanized HT steel plate having suitable arrangement of holding minimum 12 Nos flood light fitting of upto 250W i/c fixing, testing etc as reqd. including dismantling and reinstallation ,connections & inter connections of existing flood lights/Street light fitting to the new winch assembly at a height of upto 16 mtrs etc complete as required.(old Dismantling materials are property of Contractor) |
| 13 | Supplying, Installation, Testing and commissioning of Astronomical time switch of following configuration to be mounted in feeder pillars / Lighting DBs for automatic switching On & OFF of street lights at sun set & sun rise or twilight(Auto ON, Auto OFF, Auto modes) with manual override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete as required. |
| 14 | 1 output per phase and suitable for single phase supply |
| 15 | Fabrication, supply, installation, testing and commissioning of MV compartmentalized type outdoor type double door cubical feeder pillar panel, having front area not less than 1.6 sqmtr. having 300 mm depth, made out of 2 mm thick CRCA sheet with 300 Amps rated 4 strip aluminium busbar, free standing totally enclosed dust and vermin proof, suitable for operation on 3 phase 415 V, 4 wire AC supply system, having suitable cable entry arrangement with detachable gland plates, duly powder coated, interconnection with suitable size aluminium strips / bars connections, earthing labelling, quarter turn knobs, etc. with cable chamber, busbar chamber conforming to section-4 of CPWD specification for Electrical works part IV Substation 2013 etc., complete with fixing of panel on MS stand of size 50 mm x 50 mm x 6 mm thick and 1000 mm height angle iron framework grouted 500 mm deep in CC foundation i/c painting of MS frame work with synthetic enamel paint etc. as reqd. (a) Incomer = 250A 4P MCCB, 415V, 36 kA (Icu=Ics), with Thermal Magnetic release (b) Metering compartment: Digital Multifunction meter (having basic parameters: Amps, Volts, W/VA, KWh /KVAh ) set of CTs - 1 Set b) Phase indicating lamps(LED type) with toggle switches, control fuses etc. - 1 set (c) Outgoings: ) 250 A Power contactor three pole with 415 volt AC supply - 1 Nos. |
| 16 | b)125 A TP MCCB, 415 V, 25 kA (Ics = Icu), with adjustable thermomagnetic release - 3 Nos. c) 63 A TP MCCB, 415 V, 25 kA (Ics = Icu), with adjustable thermomagnetic release - 3 Nos. d) Astronomical time switch capable of automatic switching On & OFF of street lights at sun set & sun rise or twilight (Auto ON, Auto OFF) in feeder pillars / Lighting DBs for three phase supply - 1 No. e) GI earth strip of suitable size to full width of cubicle panel with two earth studs at the ends as required - 1set f) Anodised aluminium MV danger notice plates and phenolic labeling as required - 1set |
| 17 | Supplying, installation, Testing & commissioning of 110 Amp. power contractor with connection complete etc. as required. |
| 18 | Supplying, Installation, Testing & Commissioning of SMC pole Box of size 250mm x 200mm x 105mm with hinged cover on surface/ recess/pole complete with aluminum connector strip - 2 Nos, MS Clamp - 2 Nos., 6-32amp. C series SPMCB- 1 No., having IP: 66 protection connection etc. as reqd. |
| 19 | Credit for old dismantle items |
| 20 | Assorted size LED Fittings 150/180/200 watt |
| 21 | Feeder pillar |
| 22 | contactor Please Enable Macros to View BoQ information |