| 1 | 11/0.4 KV 250KVA Distribution Sub-Station |
| 2 | Prov.Distribution Transformer (Ordinary), 250 KVA, 11/0.4 kV |
| 3 | Prov.Steel Tubular Poles (9 m, Working Load > 200 kgf/m²) |
| 4 | Prov.Muffs with concerete filling |
| 5 | Prov.X-Arm: [Channel Iron (100x50x6 mm), Length : 2800 mm X 2 Nos] for incomer line |
| 6 | Prov.MS Angle Iron (50X50x6 mm), Length: (2800 mm) x1 Nos for LA's |
| 7 | Prov.X-Arm: [Channel Iron (75x40x6 mm), Length : (2800 mm X 4 Nos] for supporting DO fuse unit & GO switch |
| 8 | Transformer Bed, Belting & Knee Bracing |
| 9 | X-Arm:[Channel Iron (100x50x6 mm), Length : 2800 mm X 2 Nos]forTransformer Bed |
| 10 | X-Arm [Channel Iron (100x50x6 mm), Length : (460 mm) x 2 Nos for supporting Main Channel of Transformer] |
| 11 | MS Angle Iron (50X50x6 mm), Length : (2800 mm) x 2 Nos |
| 12 | MS Angle Iron (35X35x5 mm), Length : (460 ) x 2 Nos |
| 13 | MS Angle Iron (50X50x6 mm), Length : (950 mm) x 2 Nos for Bed Knee Bracing |
| 14 | Transformer LT Distribution Box and GO Switch fixing Assembly |
| 15 | MS Angle Iron (50X50x6 mm), Length : (2800 mm) x 2 Nos |
| 16 | MS Angle Iron (50X50x6 mm), Length : (450 mm) x 1 Nos |
| 17 | GO Switch Handle Supporting: [Channel Iron (75x40x6 mm), Length : 460 mm |
| 18 | GO AB Switch Unit (11kV, 400A, 25 KA ) Tripple pole O/D type |
| 19 | D.O Fuse Unit |
| 20 | Surge Arrester, 9 kV Station Class (Porcelain Type) |
| 21 | Discs insulator sets (comprising 1No.Disc(Porcelain, BS, 12 kV, 90 kN) including Dead End Clamps etc.) |
| 22 | Stay set complete |
| 23 | Stay Wire (7/3.15 mm) (7.0 kg Per Stay Set) |
| 24 | Pipe Earthing Set for 2 nos DTRs |
| 25 | LT Distribution Panel Box with MCCB(160A, 35 kA, 4P) |
| 26 | Half Clamp (M.S. Flat 50X6 mm) |
| 27 | Full Clamps (M.S. Flat 50X6 mm) |
| 28 | Nuts and Bolts of Various Sizes (with flat and spring washers)] |
| 29 | Copper Thimble 70 mm |
| 30 | Copper Thimble 300 mm |
| 31 | Danger Plate |
| 32 | Barbed Wire |
| 33 | LT Cable (3.5 Core) 500 mm² |
| 34 | 3-ɸ, 4 wire CT -PT operated Static Tri-Vector meter w(PT ratio -/110v,ct ratio -/5A) |
| 35 | Aluminium Paint. |
| 36 | CT-PT unit 11kv/110v |
| 37 | Prov.AAAC 7/3.15mm² Conductor for Earthing for 2 nos DTRs |
| 38 | Transformer Bed, |
| 39 | Prov. Chain link Fencing Plinth for double pole structure complete with digging, C.C. 1:6:12, R.R. masonary and plastering etc. size 10'x3'x2.5' |
| 40 | Prov. IT Peripheral for the scheme |
| 41 | Wood Cutter |
| 42 | Addl civil work for stengthening of existing line |
| 43 | Tong tester 1000A |
| 44 | Erection charges as per cost data 2025-26 complete in all respect |
| 45 | Erection charges for 2nd 250 KVA DTR |
| 46 | Transportation charges complete in all respect |
| 47 | 11 KV H.T Line |
| 48 | Prov. Conductor AAAC 7/3.81 (80mm2) |
| 49 | Prov. Steel Tubular Pole 11 Mtr. Long |
| 50 | Prov. Steel Tubular Pole 9 Mtr. Long |
| 51 | Prov. RCC Muff with Concerete Filling (1200 mm) |
| 52 | Prov. X-Arm (Horizontal) - MS Channel Iron: 100x50x5, Length [(1270)mm |
| 53 | MS A.I 50x50x6, Length [750 mm x 2 No.] |
| 54 | Prov. Discs insulator sets on Dead End structures (comprising 1 No. Disc: ^^(Porcelain, BS, 12 kV, 90 kN) including Dead End Clamps etc.) |
| 55 | Prov. 11 KV Pin insulator |
| 56 | Prov Stay set complete in all respect |
| 57 | Prov. Stay Wire (7/3.15 mm) (7.0 kg Per Stay Set) |
| 58 | Prov. HT Earthing set complete |
| 59 | Belt set-MS angle iron 50x50x6 mm L 1800mm x2 no. |
| 60 | X-bracing set-MS angle iron 50x50x6 mm L 2125mm x2 no. |
| 61 | X-arm Horizontal-MS channel 100x50x5mm L 2340mm x 2no. |
| 62 | Eye Hook for earth wire |
| 63 | M.S.A.I . 50x50x6mm L 2800mm for earth wire double pole structure |
| 64 | Trifor for sagging of line |
| 65 | Prov. Single Continous Earth wire (GI, 8 SWG) @ 0.102 kg/m |
| 66 | Prov. 11 KV Danger Plate (250X200X1.6 mm) |
| 67 | Prov. Nuts and Bolts of Various Sizes (Galvanised / Coated) [Preferably 16 mm Φ or more (with flat and spring washers)] |
| 68 | Prov. Barbed Wire |
| 69 | Prov. Aluminium Paint |
| 70 | Prov. Halfl clamp |
| 71 | Prov. Full clamp |
| 72 | Transportation charges complete in all respect |
| 73 | Erection Charges complete in all respect |
| 74 | LT Line |
| 75 | Cost of Conductor ( AAAC) (including Cutting & Sagging ) 7/3.15mm² |
| 76 | Steel Tubular Poles (8 m, Working Load > 200 kgf/m²) (with Ruling Span 67 m) |
| 77 | Muffs with concerete filling |
| 78 | Shackle Insulator (16 kN) |
| 79 | D-Iron (U- Clamps) |
| 80 | Earth Knob |
| 81 | LT ab cable Size 3Cx120+70+16 mm |
| 82 | LT Stay Set |
| 83 | Stay Wire (7/3.15 mm) (6.0 kg Per Stay Set) |
| 84 | Full Clamps [ 2 No for A.I + 1 No for Stay Set] |
| 85 | Earth wire (GI, 8 SWG) Road Crossing Gaurding |
| 86 | Spool Tie |
| 87 | Nuts and Bolts of Various Sizes (Galvanised / Coated) [Preferably 16 mm Φ or more (with flat and spring washers)] |
| 88 | Aluminium Paint |
| 89 | Spiral PVC Spacer |
| 90 | Erection Charges of cable complete in all respect |
| 91 | Erection Charges for cond complete in all respect |
| 92 | Transportation Charges complete in all respect |
| 93 | 4-Pole Structure |
| 94 | Prov.Steel Tubular Poles (11 m, Working Load > 200 kgf/m²) |
| 95 | Prov.Muffs with concerete filling |
| 96 | Prov.X-Arm: [Channel Iron (100x50x5 mm), Length : 2800 mm X 2 Nos] for incomer line |
| 97 | Prov.MS Angle Iron (50X50x6 mm), Length: (2800 mm) x1 Nos for LA's |
| 98 | Prov.X-Arm: [Channel Iron (75x40x6 mm), Length : (2800 mm X 4 Nos] for supporting DO fuse unit & GO switch |
| 99 | MS Angle Iron (50X50x6 mm), Length : (2800 mm) x 2 Nos |
| 100 | MS Angle Iron (35X35x6 mm), Length : (460 ) x 2 Nos |
| 101 | MS Angle Iron (50X50x6 mm), Length : (950 mm) x 2 Nos |
| 102 | MS Angle Iron (50X50x6 mm), Length : (2800 mm) x 2 Nos |
| 103 | MS Angle Iron (50X50x6 mm), Length : (450 mm) x 1 Nos |
| 104 | GO Switch Handle Supporting: [Channel Iron (75x40x6 mm), Length : 460 mm |
| 105 | GO AB Switch Unit (11kV, 400A, 25 KA ) Tripple pole O/D type |
| 106 | D.O Fuse Unit |
| 107 | Surge Arrester, 9 kV Station Class (Porcelain Type) |
| 108 | 11 kV Pin Insulators (Porcelain, 12 kV, 10 kN): |
| 109 | Discs insulator sets (comprising 1No.Disc(Porcelain, BS, 12 kV, 90 kN) including Dead End Clamps etc.) |
| 110 | Stay set complete |
| 111 | Stay Wire (7/3.15 mm) (9.0 kg Per Stay Set) |
| 112 | Prov HT Earthing set complete |
| 113 | Half Clamp (M.S. Flat 50X6 mm) |
| 114 | Full Clamps (M.S. Flat 50X6 mm) |
| 115 | Nuts and Bolts of Various Sizes (with flat and spring washers)] |
| 116 | Danger Plate |
| 117 | Barbed Wire |
| 118 | Aluminium Paint. |
| 119 | Prov.AAAC 7/3.81mm² Conductor for Earthing |
| 120 | Erection charges of 4-pole str |
| 121 | Erection charges of HT stay set |
| 122 | Erection charges of HT Earthing set |
| 123 | Transportation charges complete in all respect Quantities are mentioned above are tentative and Actual Quantity shall be worked out after Check Survey to be carried out by the successful Tender and detailed Engineering and finalization of Tower location Chart.Payment shall be made as per Approved Bill of Material/Actual Quantities measured at site. Please Enable Macros to View BoQ information |