| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GARRISON ENGINEER (AF) BANGALORE NAME OF WORK : SPL REPAIR TO E&M SERVICES IN GE OFFICE COMPLEX AND ADJACENT LOCATIONS AT HQTC CA NO: GE(AF)/B/ OF 2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Description of Item of Work Item Code / Make Quantity Unit Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT (in Words) |
| 2 | Taking down carefully copper/aluminium point wiring (light, fan,socket or power) complete, including fittings & fixtures such as switches, sockets,ceiling rose, pendants, regulators, light fittings etc. Removing materials to store for keeping in safe custody for taking credit and making good to disturbed surfaces with plaster & matching with the existing colour of wall/floor etc complete all as specified & directed. |
| 3 | Taking down carefully ceiling fan from ceiling, dismantaling blades, and removing fan and painting of ceiling fans complete, with synthetic enamel paint by spraying including filling cavities with filler, one coat after cleaning all dust etc. and refixing of ceiling fan in same position in serviceable condition with greasing and oiling including provision of three core 1.5 sq mm cable from ceiling rose to fan connector complete all as specified & directed. |
| 4 | M&L for point wiring with 1.5 sqmm PVC insulated,unsheathed, FRLS multistranded copper conductor 1100 volts grade cable in and including heavy grade PVC Casing & Caping ISI marked broken white or of cream colour with all accessories such as tee,bend,joint cover etc, round/ square PVC blocks at junction for batten holders, ceiling rose etc ,screws, gutti / roul plugs PVC all as per site requirements including fixing on stone walls / brick masonary walls /ceilings /floors etc and including modular sunken boxes boxes for mounting of switches/ sockets/regulator etc and 1.5 sqmm PVC insulated,unsheathed, FRLS multistranded copper conductor 1100 volts grade cable as continuous earth lead connected to common earth dolly complete all as specified and colour coding of cables such as Phase- Red, Neutral-Black, and Earth-Green.and making good to disturbed surfaces/wall with plaster & matching with the existing colour of wall/floor etc complete all as specified & directed for the following:- |
| 5 | One light point controlled by one single pole 5 Amps switch. |
| 6 | One ceiling fan/wall point controlled by one single pole 5 Amps switch. |
| 7 | One exhaust fan point controlled by one single pole 5 Amps switch. |
| 8 | One 5 pin socket point 5 Amps on independent board. |
| 9 | One 5 pin socket point 5 Amps on same board with other switches. |
| 10 | All as per item No-3.00 here-in-before but for power point wiring with 2.5 Sqmm PVC insulated, unsheathed, FRLS multistranded copper conductor 1100 volt grade cable and 2.5 Sqmm PVC insulated, unsheathed, FRLS multistranded copper conductor 1100 volt grade cable as continuous earth lead for 6 pin 15 Amp modular switch socket outlet on independent board complete all as specified & directed. |
| 11 | S&F Modular switch , 1 Module single pole one way 10 Amps complete all as specified & directed. |
| 12 | S&F Modular socket , 2 Module 6 Amps, 5 pin, 230 volts AC complete all as specified & directed. |
| 13 | S&F Modular switch , 1 Module single pole one way 16 Amps complete all as specified & directed. |
| 14 | S&F Modular socket , 2 Module 6/16 Amps, 6 pin, 230 volts AC complete all as specified & directed. |
| 15 | S&F Modular type fan regulator upto 120 watts with 5 step speed control for fans any sweep 1200 mm/1400 mm complete all as specified & directed. |
| 16 | S&F PVC ceiling rose 65 x 50 mm surface type with 3 terminals 230 volt complete all as specified & directed. |
| 17 | S&F Modular white cover plate with frame, 3 module complete all as specified & directed. |
| 18 | S&F Modular white cover plate with frame, 4 module complete all as specified & directed. |
| 19 | S&F Modular white cover plate with frame, 6 module complete all as specified & directed. |
| 20 | S&F Modular white cover plate with frame, 8 module complete all as specified & directed. |
| 21 | S&F Modular metal flush box 3 module complete all as specified & directed. |
| 22 | S&F Modular metal flush box 4 module complete all as specified & directed. |
| 23 | S&F Modular metal flush box 6 module complete all as specified & directed. |
| 24 | S&F Modular metal flush box 8 module complete all as specified & directed. |
| 25 | S&F LED Light fitting, 4 feet 1x20 Watts, 220 volts, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of size 1.5 sqmm from ceiling rose to fitting complete all as specified & directed. |
| 26 | S&F LED mirror Light fitting 2 feet, 10 Watts, 220 volts, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of size 1.5 sqmm from ceiling rose to fitting complete all as specified & directed. |
| 27 | S&F LED light fitting of size 600 mm x 600 mm, 36 watt, white/warm white as per site requirement 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor wire of size 1.5 sqmm complete all as specified & directed. |
| 28 | S&F LED light fitting round shape 15 watt white/warm white as per site requirement 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of size 1.5 sqmm complete all as specified & directed. |
| 29 | S&F LED light fitting outdoor type 10 watt bulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of size 1.5 sqmm complete all as specified & directed. |
| 30 | S&F LED building security light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection including connecting up with three core flexible copper conductor cable of 1.5 sqmm size from ceiling rose to fitting including brackets made out of 50 mm dia light grade GI pipe 1.50 mtr long bent to shape and size as per site requirement for fixing of street light fitting on poles/ walls including Flat Iron clamps=02 Nos of size 30x5mm made to shape incl nuts,bolts & washers complete all as specified & directed. |
| 31 | S&F Sheet metal enclosure for DB's double door SPN, 8 ways when MCBs to be used single pole and neutral, deep drawn with 200 Amps rated copper bus bar 230 Volt, complete all as specified & directed. |
| 32 | S&F Sheet metal enclosure for DB's double door SPN,12 ways when MCBs to be used single pole and neutral, deep drawn with 200 Amps rated copper bus bar 230 Volt, complete all as specified & directed. |
| 33 | S&F MCB SP, 6-32 Amps, 230V, C- series with breaking capacity of 10KA complete all as specified & directed . |
| 34 | S&F MCB SPN, 40 Amps, 230 V, C- series with breaking capacity of 10 KA complete all as specified & directed. |
| 35 | S&F Sheet metal enclosure for DB's double door VTPN 04 ways including 01 No MCCB 125 Amp 4 pole to be used as incomer and outgoing as MCB single pole, deep drawn with 200 Amps rated copper bus bar 415 V, complete all as specified & directed. |
| 36 | S&F Exhaust fan steel body AC single phase 230 V of size 380 mm sweep, 900 RPM with blades, and frame and louvers including making holes in brick/stone wall of suitable size dia for fixing of exhaust fan and making good to disturbed surfaces/wall with plaster & matching with the existing colour of wall/floor etc complete all as specified & directed. |
| 37 | S&F BLDC ceiling fans complete with blades, down rods, electronic regulator and accessories, AC single phase 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) and remote to control all the function of fan complete all as specified & directed. |
| 38 | S&F Electric water heater, storage type steel body with copper inner tank and heating element upto 2 KW capacity 25 litre, BEE 5 Star rated complete with all accessories such as safety valve, thermostate, NRV, connection piece and including drilling holes in any type wall fixing four nos anchor bolts five inch size,nuts and washer and connected to water pipe line with two nos hot and cold 600 mm long connection pipe and electric connection testing complete all as specified & directed. |
| 39 | S&F Wall Mounted fan AC single phase 230 Volt of size 400 mm sweep in stone/ brick masonary or any type wall with four inch screws, gatti / PVC roul plugs all as per site requirement including making good to disturbed surfaces/wall with plaster & matching with the existing colour of wall/floor complete all as specified & directed. |
| 40 | S&F rigid PVC trunking white colour of 80 mm x 50mm with a long bodies & with flexible cover 65mm as per OEM, Legrand fixing on stone walls/ brick masonry walls/ceilings / floors etc. for running of all type of service/ miscellaneous cables complete with fitting such as joints/ Tee/ elbow / coupler etc, including taking down old PVC cable Trunking all as specified and directed. Make : Legrand, Cat No- 010452,( BODY) 010521 (COVER) or Techno-commerically equivalent in L&T, Schneider. |
| 41 | M&L for sub main wiring with two single core 2.5 sqmm PVC insulated ,unsheathed , FRLS multistranded copper conductor 1100 volts grade cable in and including heavy grade PVC Casing & Caping ISI marked broken white or of cream colour with all accessories such as tee,bend,joint cover etc, screws, gutti / roul plugs PVC all as per site requirements including fixing on surface on stone walls / brick masonary walls /ceilings /floors etc with 2.5 sqmm PVC insulated,unsheathed, FRLS multistranded copper conductor 1100 volts grade cable as a continuous earth wire and connected to common earth dolly complete and making good to disturbed surfaces/wall with plaster & matching with the existing colour of wall/floor etc all as specified and colour coding of cables such as Phase- Red, Neutral-Black, and Earth-Green complete all as specified & directed. Note-Two runs of 2.5 sqmm single core cable and one run of 2.5 sqmm earth wire including PVC casing & capping together shall be measured as one unit. |
| 42 | M&L for sub main wiring with two single core 4.00 sqmm PVC insulated ,unsheathed , FRLS multistranded copper conductor 1100 volts grade cable in and including heavy grade PVC Casing & Caping ISI marked broken white or of cream colour with all accessories such as tee,bend,joint cover etc, screws, gutti / roul plugs PVC all as per site requirements including fixing on surface on stone walls / brick masonary walls /ceilings /floors etc with 4.00 sqmm PVC insulated,unsheathed, FRLS multistranded copper conductor 1100 volts grade cable as a continuous earth wire and connected to common earth dolly complete and making good to disturbed surfaces/wall with plaster & matching with the existing colour of wall/floor etc all as specified and colour coding of cables such as Phase- Red, Neutral-Black, and Earth-Green complete all as specified & directed. Note-Two runs of 4.00 sqmm single core cable and one run of 4.00 sqmm earth wire including PVC casing & capping together shall be measured as one unit. |
| 43 | M&L for sub main wiring with two single core 6.00msqmm PVC insulated ,unsheathed , FRLS multistranded copper conductor 1100 volts grade cable in and including heavy grade PVC Casing & Caping ISI marked broken white or of cream colour with all accessories such as tee,bend,joint cover etc, screws, gutti / roul plugs PVC all as per site requirements including fixing on surface on stone walls / brick masonary walls /ceilings /floors etc with 6.00 sqmm PVC insulated,unsheathed, FRLS multistranded copper conductor 1100 volts grade cable as a continuous earth wire and connected to common earth dolly complete and making good to disturbed surfaces/wall with plaster & matching with the existing colour of wall/floor etc all as specified and colour coding of cables such as Phase- Red, Neutral-Black, and Earth-Green complete all as specified & directed. Note-Two runs of 6.00 sqmm single core cable and one run of 6.00 sqmm earth wire including PVC casing & capping together shall be measured as one unit. |
| 44 | M&L for Earthing complete with galvanised steel earth electrode plate of size 600x600x6mm thick, buried directly in ground(earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.50m below normal ground level, connected to galvanised iron wire 4 mm dia as earth lead up to test point with suitable size GI nuts/bolts, washers,check nut and brazed properly up to main board,LT panel etc and adequate quantity of charcoal and salt 15 cm around the earth plate including earth pit in cement concrete 1:2:4 type B-1 using 20mm graded stone aggregates,40mm thick precast RCC cover in 1:2:4 reinforced with 8mm dia TMT bars 3 Nos both way including CI cover 10 mm thick with hinged and frame of angle iron 25x25x6mm with 6mm dia MS bar handle made to shape, excavation and earth work in any type of soil and including medium grade GI watering pipe 20mm bore with funnel and wire mesh and medium grade GI protection pipe 15 mm bore up to main board complete all as shown in electrical plate no 3 of MES schedule Part-I , connected to earthing testing point and testing on completion complete all as specified and directed.Notes: (i) The unit rate includes 15 mm dia GI pipe up to 7.5m for protection of earth lead. (ii) The unit rate includes galvanised iron wire 4 mm dia from earth electrode to test point up to 7.5 meter (iii) In case measured value of earth resistance of each earthing is recorded more than 3 ohms then the earthing shall be re done by the contractor without any extra cost to the Govt till desired result is obtained (iv) After completion of work earthing shall be tested by the contractor in presence of Engineer-in-Charge / JE E/M and proper record shall be maintained duly signed by all concerned. (v) Earth resistance tester shall be provided by the contractor. It should be caliberated from authorised company/ lab. |
| 45 | S&F Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing 4 mm dia galvanised iron or steel wire complete all as specified & directed. |
| 46 | Excavation in trenches not exc 1.5m wide and not exc 1.5m deep and getting out in soft/loose soil complete all as specified and directed. |
| 47 | Returning, filling in,including spreading, levelling ,watering and well ramming in layers not exc 25cm thick in soft/loose soil complete all as specified and directed. |
| 48 | Removing surplus soil to a distance not exc 50m and depositing where directed at a level not exc. 1.5m above the starting point complete all as specified and directed. |
| 49 | M&L for sand cushioning to under ground cable with locally available dry sand for protection of cable 8cm thick before laying of cable and 15 cm thick after laying and stretching the cable below the bricks/PCC cover ,punning of sand using suitable T&P as per site requirement complete all as specified and directed. Note- Punned thickness of sand i.e 18 cm shall be considered for measurement purpose. |
| 50 | Supplying and laying un-reinforced precast concrets cable cover class LV, Type 1, flat, size 250x150x40 mm complete all as specified and directed. |
| 51 | M&L Plain cement concrete 1:2:4 type B1(using 20mm graded crushed stone aggregate) as in benching,coping including weathering slightly rounded or chamfered angles or as per site requirement with necessary plastering work complete all as specified and directed. |
| 52 | Supply and laying in trenches /laid in floor/duct/drawn through conduit XLPE insulated,screened, PVC bedded, galvanized steel strip or wire armoured heavy duty electric cable 1100V grade with aluminum conductor of cross sectional area 10 sqmm 2 core and connecting up incoming/out going cables connection with suitable size lugs and testing complete all as specified and directed. |
| 53 | All as per item No-46.00 here-in-before but of size 16 sqmm 4 core. |
| 54 | All as per item No-46.00 here-in-before but of size 35 sqmm 3.5core. |
| 55 | All as perNo-46.00 here-in-before but of size 50 sqmm 3.5core. |
| 56 | All as perNo-46.00 here-in-before but of size 70 sqmm 3.5core. |
| 57 | All as per No-46.00 here-in-before but of size 95 sqmm 3.5core. |
| 58 | S&F in replacement MCCB, 4 poles 415 Volts, 200 Amps, 36 kA, 50 Hz, AC, adjustable type in the existing LT panel /sheet metal enclosure/feeder pillar box or any place as directed including any addition, alteration in LT panel /sheet metal enclosure/feeder pillar box or in bus bar like drilling,cutting ,grinding or as per site requirement and connecting up incoming/out going cables connection with suitable size lugs and testing complete all as specified & directed. |
| 59 | Supply and Install on load Changeover switch 415 Volt in sheet metal enclosure 4 pole of capacity 200 Amp including connecting up incoming/out going cables connection with suitable lugs and testing complete all as specified & directed. |
| 60 | S&F LED street light fitting 90 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection including connecting up with three core flexible copper conductor cable of 2.5 sqmm size from ceiling rose to fitting including street light brackets made out of 50 mm dia light grade GI pipe 1.50 mtr long bent to shape and size as per site requirement for fixing of street light fitting on poles/ walls including Flat Iron clamps=02 Nos of size 30x5mm made to shape incl nuts,bolts & washers complete all as specified & directed. |
| 61 | S&F LED flood light 100 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete including connecting up with three core flexible copper conductor cable of 2.5 sqmm size from ceiling rose to fitting including street light brackets made out of 50 mm dia light grade GI pipe 1.50 mtr long bent to shape and size as per site requirement for fixing of street light fitting on poles/ walls including Flat Iron clamps=02 Nos of size 30x5mm made to shape incl nuts,bolts & washers complete all as specified & directed. |
| 62 | S&F street light brackets made out of 50 mm dia light grade GI pipe 1.50 mtr long bent to shape and size as per site requirement for fixing of street light fitting on poles/ walls including Flat Iron clamps=02 Nos of size 30x5mm made to shape incl nuts,bolts & washers complete all as specified & directed. |
| 63 | Disconnecting and taking out old rusted pipe and M&L for 40 mm dia galvanized iron tube light grade for cable protection, supporting to poles, plinth protections, road crossing, trenches, footpath etc, including new Flat Iron clamps=02 Nos of size 40x5mm, made to shape including nut bolt and washers complete all as specified & directed. |
| 64 | M&L for Earthing complete with galvanised steel earth electrode plate of size 600x600x6mm thick, buried directly in ground(earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.50m below normal ground level, connected to galvanised iron strip of size 32 x 6 mm as earth lead up to test point with suitable size GI nuts/bolts, washers,check nut and brazed properly up to main board,LT panel etc and adequate quantity of charcoal and salt 15 cm around the earth plate including earth pit in cement concrete 1:2:4 type B-1 using 20mm graded stone aggregates,40mm thick precast RCC cover in 1:2:4 reinforced with 8mm dia TMT bars 3 Nos both way including CI cover 10 mm thick with hinged and frame of angle iron 25x25x6mm with 6mm dia MS bar handle made to shape, excavation and earth work in any type of soil and including medium grade GI watering pipe 20mm bore with funnel and wire mesh and medium grade GI protection pipe 40mm bore up to main board complete all as shown in electrical plate no 3 of MES schedule Part-I , connected to earthing testing point and testing on completion complete all as specified and directed. Note: (i) The unit rate includes 40 mm dia GI pipe up to 7.5m for protection of earth lead. (ii) The unit rate includesGI main earthing lead/strip of size 32x6 mm from earth electrode to test point up to 7.5 meter (iii) In case measured value of earth resistance of each earthing is recorded more than 3 ohms then the earthing shall be re done by the contractor without any extra cost to the Govt till desired result is obtained (iv) After completion of work earthing shall be tested by the contractor in presence of Engineer-in-Charge / JE E/M and proper record shall be maintained duly signed by all concerned. (v) Earth resistance tester will be provided by the contractor. It should be caliberated from authorised company/ lab. |
| 65 | S&F GI strip 32 x 6 mm with saddles and fixing screws on poreceling insulator/ spacer fixed at every 1 mtr length on roof/wall of building/ connect to LT panel or main DB and joining the same with existing earth test point complete all as specified & directed. |
| 66 | M&L for Earthing complete with copper earth plate of size 600x600x3.15mm thick, buried directly in ground(earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.50m below normal ground level, connected to copper strip of size 20x3 mm as earth lead up to test point with suitable size copper coating nuts/bolts, washers,check nut and brazed properly up to main board,LT panel etc and adequate quantity of charcoal and salt 15 cm around the earth plate including earth pit in cement concrete 1:2:4 type B-1 using 20mm graded stone aggregates,40mm thick precast RCC cover in 1:2:4 reinforced with 8mm dia TMT bars 3 Nos both way including CI cover 10 mm thick with hinged and frame of angle iron 25x25x6mm with 6mm dia MS bar handle made to shape, excavation and earth work in any type of soil and including medium grade GI watering pipe 20mm bore with funnel and wire mesh and medium grade GI earth wire protection pipe 40mm bore up to main board complete all as shown in electrical plate no 3 of MES schedule Part-I , connected to earthing testing point and testing on completion complete all as specified and directed. Note: (i) The unit rate includes 40 mm dia GI pipe up to 7.5m for protection of earth lead. (ii) The unit rate includes copper main earthing lead/strip of size 20x3 mm from earth electrode to test point up to 7.5 meter (iii) In case measured value of earth resistance of each earthing is recorded more than 2 ohms then the earthing shall be re done by the contractor without any extra cost to the Govt till desired result is obtained .(iv) After completion of work earthing shall be tested by the contractor in presence of Engineer-in-Charge / JE E/M and proper record shall be maintained duly signed by all concerned. (v) Earth resistance tester will be provided by the contractor. It should be caliberated from authorised company/ lab. |
| 67 | S&F copper strip 20mm X 3mm with saddles and fixing screws on poreceling insulator/ spacer fixed at every 1 mtr length on roof/wall of building/ connect to LT panel or main DB and joining the same with existing earth test point complete all as specified & directed. Total in Figures 0.0 23 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |