| 1 | S&F in replacement red conventional Call Point with LED Resister 470 OHM Flush Mounting Flexi Element complete all as specified and directed. Make- System sensor,ceasefire or equivalent make as approved by GE |
| 2 | S&F in replacement Red Mini Horn Red UL certified India complete all as specified and directed. Make-System sensor,ceasefire or equivalent make as approved by GE |
| 3 | M&L for sub main wiring with 2 runs of 4sqmm FRLS PVC insulated copper conductor, singlecore cable and one run of 4Sqmm FRLS PVC insulated copper conductor, singlecore cable as earth wire in and including PVC casing and capping including taking down the unserviceable submain wiring complete all as specified and directed. Note:-2 runs of of main wire and one run of earth wire shall be measured and paid as unit length |
| 4 | S&F 2 Zone LCD Control panel non expandable 2x16 character LCD display panel resettable output for 4 wire connectivity Beam Sensors Common sounder Output 24V, 1AMP inbuilt One Fire Relay contact, 2 fault relay Contact 30V ACDC at 2Amp contact, mechanical voltage 150 265VAC complete all as specified and directed. Make:- RAVEL Part code-REFREE102 or euivalent make as approved by GE |
| 5 | S&F 2 Wire plug in detector base for series 300 detectors part code-SSFB401 complete all as specified and directed. Make:-System sensor or euivalent make as approved by GE |
| 6 | S&F in replacement two loop main control panel microprocessor based addressable type fire control panel with zonal indication with battery power pack and testing complete fire control panel complete all as specified and directed. .Make :-Argus ,Schrack, Esser of Honey well |
| 7 | S&F in replacement multi detector complying with and type certified to EN-45 with heat and smoke comination complete all as specified and directed. Make : Argus ,Schrack, Esser of Honey well |
| 8 | S&F in replacement SITXC on Detectors Complying with and type certified to EN - 45 Addressable type smoke detector Photoelectric /Optical with base with self built intelligence asper IS: 11360 complete all as specified and directed. .Make :-Argus ,Schrack, Esser of Honey well |
| 9 | S&F in replacement lead add battery 12 Volts, 7AH suitable for addressable fire alarm system complete all as specified and directed. |
| 10 | S&F in replacement PVC conduit of 20mm dia on the wall surface using clips of necessary size complete all as specified and directed. |
| 11 | S&F in replacement 2 core, 1.5 Sqmm PVC sheathed armoured copper conductor cable 1100 Volts grade FRLS cable complete all as specified and directed. |
| 12 | S&F electric sounder cum strobe suitable for addressable type alarm system complete all as specified and directed. |
| 13 | S&F in replacement respones indicator on wall or with the false ceiling with LED indicator lamp suitable for addressable type complete all as specified and directed. |
| 14 | S&F in replacement manual call point suitable for analgue addressable type fire alarm system complete all as specified and directed. |
| 15 | S&F in replacement fire exit route indicator board with inbuilt led luminaire complete set complete all as specified and directed. |
| 16 | M&L for 6 core, 1.5 Sqmm armoured, multistranded copper cable incldung taking down existing cable complete all as specified and directed. |
| 17 | S&F short circuit isolators complete all as specified and directed. |
| 18 | S&F in replacement RCCBs for earth leakage, short circuit, and over load protection of capacity 63Amps and leake current up to 300 mA complete all as specified and directed. . |
| 19 | Taking down carefully unserviceable main switches/DBs of any size including MCBs from their position and removing materials from site all as specified and as directed by Engr-in-Charge |
| 20 | S&F in replacement sub main wiring with 2 single core10 sqmm FRLSH multi-stranded PVC insulated cable unsheathed 1100 volts grade with one earth wire of 10 sqmm copper conductor cable to common earth dolly complete and including PVC conduit of minimum 25mm dia and making good to the disturbed surfaces of wall, floor, ceiling etc to match with exisiting surface complete all as specified and as directed Note:-Two runs of 10 sqmm and one run of 10 sqmm shall be measured as 1 RM. |
| 21 | S&F in replacement sheet metal enclosure Double Door factory made distribution board 240 volts SPN 12 way, 200 Amps rated bus bar complete all as specified and as directed. |
| 22 | S&F in replacement MCB SPN 6 to 32 Amps, C Curve, 240 volts, 50 Hz AC supply complete all as specified and directed. |
| 23 | S&F in replacement MCB SP 06 to 32 Amps, C Curve, 240 volts, 50 Hz AC supply complete all as specified and directed. |
| 24 | S&F in replacement sheet metal enclosure Double Door factory made distribution board 415 volts VTPN with mccb incomer 4 way, 200 Amps rated bus bar complete all as specified and as directed. |
| 25 | S&F in replacement MCCBs 415V, 16KA, 4 Pole capacity 63 Amp complete all as specified and as directed. |
| 26 | M&L for painting of old painted steel surfaces of meter box by scrapping rusted surface and applying one coat of aluminium paint inside and out side of box compelete all as specified and directed |
| 27 | M&L for earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 metre depth below normal ground level) with top edge of plate at a depth not less than 1.5 mtr below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to galvanized earth wire 04 mm dia with and including bolts, nuts, check nuts and washers of galvanised iron or steel and riveted to earth plate and one end and connecting to main switch board or metallic bodies of HT/LT equipments etc at the other end, GI wire encased in and including 15 mm bore GI light grade pipe with all fittings, from top of electrode to body of equipment fixed with and including flatiron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI light grade and including funnel, wire mesh, copper lugs etc from bottom of earth pit to top of electrode complete with earth pit in PCC 1:3:6, type C-2 (using 40mm graded crushed stone aggregates) and CI cover complete all specified and shown in electrical plate No 03 of SSR Pt-I connecting earth electrode to test point with and including earthing lead including neessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance n.exc 50m, material and labour complete all as specified and as directed by Engineer-in-Charge. (Notes 1. The rate quoted shall be deemed to include for all the above provisions. 2. PCC chamber shall be constructed at least 1.5 m away from the earth electrode and pipe for watering shall be provided in slanting maner) . Please Enable Macros to View BoQ information |