| 1 | Design, Engineering, Manfacture, Shop Testing, Supply including packing and forwarding, Transportation and delivery at site as per Technical Specifications and approved drawings |
| 2 | 20 MVA, 132/33 kV Three Phase Power Transformer with OLTC, HV and LV connectors and other required accessories and fittings with online DGA monitoring kit, online dehydration kit and maintenance-free automatic breathers as per detailed Technical specs as per SBD incliding other related works/accessories & Civil works required for its complete commissioning. (Current density for HV/LV winding not more than 2.4 A/sq mm. Core Flux density not more than 1.5T) alongwith spares strictly as per the details contained in the Standard Bidding Document. The Transformer supplied is without NIFPS & SCADA Compatible RTCC |
| 3 | 36kV, 50c/s , 2500 Amp, 31.5 kA for one second, Ac motor operated horizontal double break, outdoor type Two pole Isolators without Earthing Switches. COPPER FIXED AND MOVING CONTACTS/ COPPER CURRENT CARRYING PARTS, GALVANISED IRON MECHANISM BOX |
| 4 | 36kV, 50c/s , 2500 Amp, 31.5 kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with One Earthing Switch. COPPER FIXED AND MOVING CONTACTS/ COPPER CURRENT CARRYING PARTS, GALVANISED IRON MECHANISM BOX. |
| 5 | Single phase, 50 c/s 36KV Current Transformers1200-600-300 /1-1-1-1 A , 31.5KA for one second, rateddynamic current 31.5 KA(peak), Class Ainsulation, Burden 20 VA, 2 NO PS CORE, 1 NO5P20, 1 NO 0.2s class, Galvanised tank,including first fill of transformer oil plus 20%extra and all accessories, auxiliariesetc. |
| 6 | 33KV VCB (36 KV, 2000 Amps of 3 phase, 50 c/s and 31.5 KA for 3 sec) outdoor type with all accessories and auxiliaries along withsupporting structures etc. complete in allRespects SS BODY, UNIVERSAL SPRING CHARGING MOTOR WITH MANDATORY SPARES |
| 7 | 33kV 400Sq. mm ,Aluminum ,single core XLPE cable,FRLS( in four lengths) including Indoor & Outdoor Heat Shrinkable Cable Kits |
| 8 | Galvanised steel structure of Sizes & Sorts including Nuts and Bolts as per instructions of Engineer Incharge |
| 9 | 16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 10 | 8 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 11 | Handling, Storage, Preservation, Erection, Testing and commissioning of equipments and material including all comsumables required for 20 MVA Power Transformers etc including Ferrules, Lugs, Printed sleeves, cable ties, cable glands, Tags, minor cutting, wielding works etc. complete in all respects |
| 12 | 20 MVA, 132/33 kV Three Phase Power Transformer with OLTC, HV and LV connectors and other required accessories and fittings with online DGA monitoring kit, online dehydration kit and maintenance-free automatic breathers as per detailed Technical specs as per SBD incliding other related works/accessories & Civil works required for its complete commissioning. (Current density for HV/LV winding not more than 2.4 A/sq mm. Core Flux density not more than 1.5T) |
| 13 | 36kV, 50c/s , 2500 Amp, 31.5 kA for one second, Ac motor operated horizontal double break, outdoor type Two pole Isolators without Earthing Switches. COPPER FIXED AND MOVING CONTACTS/ COPPER CURRENT CARRYING PARTS, GALVANISED IRON MECHANISM BOX |
| 14 | 36kV, 50c/s , 2500 Amp, 31.5 kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with One Earthing Switch. COPPER FIXED AND MOVING CONTACTS/ COPPER CURRENT CARRYING PARTS, GALVANISED IRON MECHANISM BOX. |
| 15 | Single phase, 50 c/s 36KV Current Transformers1200-600-300 /1-1-1-1 A , 31.5KA for one second, rateddynamic current 31.5 KA(peak), Class Ainsulation, Burden 20 VA, 2 NO PS CORE, 1 NO5P20, 1 NO 0.2s class, Galvanised tank,including first fill of transformer oil plus 20%extra and all accessories, auxiliariesetc. |
| 16 | 33KV VCB (36 KV, 2000 Amps of 3 phase, 50 c/s and 31.5 KA for 3 sec) outdoor type with all accessories and auxiliaries along withsupporting structures etc. complete in allRespects SS BODY, UNIVERSAL SPRING CHARGING MOTOR |
| 17 | 33kV 400Sq. mm ,Aluminum ,single core XLPE cable,FRLS( in four lengths) including Indoor & Outdoor Heat Shrinkable Cable Kits |
| 18 | Galvanised steel structure of Sizes & Sorts including Nuts and Bolts as per instructions of Engineer Incharge |
| 19 | 16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 20 | 8 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 21 | Civil Works |
| 22 | Construction of 20 MVA Power Transformer Foundations in 1:1.5:3 Mix( Min Qty 21.204 Cum) including Earth Work= 32 Cum, 1:3:6 Mix= 1.2 Cum, Reinforcement=2969 Kg, Form work=54.72 Sq m, 15mm plaster=55 Sqm including P/F of Rail Assembly (10 RM) & Carriage etc COMPLETE JOB as per instructions of Site Engineer. Please Enable Macros to View BoQ information |