| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable of Polycab /Finolex /RR Kabels /Anchor /Salzer make in recessed medium class PVC conduit (25 mm dia PVC Conduits including cutting of walls /floors with hydraulic cutters and refacing to original position by way of cement plastering /pop / paiting etc complete job including cost of conduits and allied accessories like bends .lighting conceal deeps and fan deeps etc ) , with 6Amps modular switch, modular plate of Anti backteria series of Schneider /ABB /L&T /Legrand /Simens make , suitable GI box and earthing the point with 1.5 s q.mm FRLS PVC insulated copper conductor single core cable etc. as required. ( P+N+E for Normal and invertor points per room is to be provided seperately). |
| 2 | Point wiring for 10 Amp Socket out lets with 3x2.5 sq mm (P+N+E) FRLs PVC insulated 660/1100 volt grade flexible stranded (50 strands of 0.25 mm dia.) copper conductor wires of Polycab/Finolex/Anchor/RR Cabels /Salzer make, to be laid in recessed conducting system (25 mm dia medium class PVC Conduits including cutting of walls /floors with hydraulic cutters and refacing to original position by way of cement plastering /pop / paiting etc complete job including cost of conduits and its allied accessories ,seperate conduit for each point ).The Job further Includes supply and fixing modular grid plate mounted flush mounted 2 no 240 volts 6-16 Amp 5 pin socket out let along with 2 No's of 6-16 Amp control Switch to be housed in 6-Way heavy duty GI Modular Box with modular cover plate of Anti Bacterial of ABB /L&T / legrend /Simens make , complete as per specification and as required . The Job includes providing and laying of circuit wiring of same size from DB to first switch in sub circuit Complete as required Complete Job including conduits ,Switches ,Sockets and complete circuit from DB Box to switch-socket ( Seperate circuit for indiual points with out any looping and jointing ) |
| 3 | Point wiring for 16 Amp Socket out lets with 3x4 sq mm (P+N+E) FRLS PVC insulated 660/1100 volt grade flexible stranded copper conductor wires of Polycab/Finolex/Anchor/RR Cabels /Salzer make, to be laid in recess conducting system (25 mm dia medium class PVC Conduits including cutting of walls /floors with hydraulic cutters and refacing to original position by way of cement plastering /pop / paiting etc complete job including cost of conduits and its allied accessories ,seperate conduit for each point ) .The job further includes the cost of supplying and fixing modular grid plate mounted flush mounted 240 volts 16 amp 6 pin combined shuttered socket out let along with 240 volt 16 Amp control Switch of Anti fungal & Anti Bacterial of ABB /L&T / legrend /Simens make to be housed in heavy duty 4-Modular GI Box of same make as of switches /sockets with p/f of modular cover plate , complete as per specification and as required with inter connection complete as per specifications and as required. The Job includes providing and laying of circuit wiring of same size from DB to first switch in sub circuit Complete as required Complete Job including conduits ,Switches ,Sockets and complete circuit from DB Box toto switch-socket ( Seperate circuit for indiual points with out any looping and jointing ) |
| 4 | Wiring for submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in recessed medium class PVC conduit (25 mm dia PVC Conduits for housing of upto 4 Sq.mm wires and 32 mm dia for housing of above 4 Sq.mm wires including cutting of walls /floors with hydraulic cutters and refacing to original position by way of cement plastering /pop / paiting etc complete job ,seperate conduit for each point ) as required. of Polycab / Finolex /Anchor / RR Kabels /Salzer make. |
| 5 | 2 X4 sq. mm + 1 X4 sq. mm earth wire |
| 6 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire for sub main and AC Point |
| 7 | 2 X 10 sq. mm +1 X 6 sq. mm earth wire |
| 8 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 9 | Supply and fixing of Indicators (Modular type) fitted on modular grid plate and GI Boxes complete job |
| 10 | Supplying & fixing suitable size Gl box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 11 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, suitable for 230 V, 50 Hz, single phase ACSupply, earthing etc. complete as required.of Usha / Crompton Greaves / Orient /Helonix .The job includes p/f of Fan hook with fastners |
| 12 | Supply, Installation testing and commissioning of 200-250 mm sweep shutter type Exhaust Fans of Usha / Crompton Greaves /Orient /Helonix incl making of necessary connections and making of necessary space in walls / Windows as per site.The Job includes providing and fixing of hylum sheet to be fixed around exhaust fan (as per approved sample) |
| 13 | Supply ,installation ,Testing and Commissioning of 15 Watts ,Surface /recessed LED Downlighter having aluminium Body (Commercial type) of standard make dully isi marked ,incl ceiling rose and 2-core transparent wire for connections complete job.The luminaire should have Back lit techanology and not side lit and should have a LEDs with colour consistency SDCM ≤ 5, CRI ≥ 80 and CCT of 6500K. Luminaire shall be designed to emit initial system lumen output of 1400 lumens with minimum system efficacy of 120 lumen/watt. The luminaire shall comply to lifetime of 50000Hrs @ L70B50 with design ambient temp 45°C. The electronic driver used shall have a power factor ≥0.95 and THD ≤10%, suitable for an operating voltage range of 140-270V AC, THD≤10%, Current Ripple ≤5%, Internal surge protection should be minimum 4KV, electrical insulation class should be Class I. The luminaire should be of Class B serviceability. The luminaire should be at least IP20 & IK02 rated. . The luminaire driver shall be of the same make/manufacturer as that of LED luminaires. Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79, Type test as per IS10322, \\"FAT\\" before dispatch as per IS 10322 & IK Test. The successful bidder must submit the NABL accreditation certificate for Luminaire manufacturer before supply of material. The LED Luminaire & it's driver both should be BIS registered. Successful bidder shall submit the following reports before supply of material for approvals: LM79 issued by NABL accredited lab, LM80 issued by LED manufacturer, Type Test Certificate for luminaire as issued by NABL accredited lab, BIS certificate for LED Luminaire & Driver. Approved make Philips / Lighting techology / Trilux /wipro /Endo / Zumtobel / Ligman (to be approved before installation) The Agency / firm has to submit Techanical data sheet (TDS) along with above mentioned requisite certificates before supply of materials for approval from department not less than rank of SDO |
| 14 | Supply ,Installation ,Testing and Commissioning of IP66 , 50 Watt LED Flood light Luminaries (Commercial type) having Aluminium body of of standard make dully isi marked ,to be fitted on walls / poles with necessary cliffs /Clamps with nuts and bolts complete job.The system efficacy of the luminaire shall be ≥130lm/w. The LEDs used in the luminaire shall be from either Lumileds, Osram, Nichia, APT Electronics and CREE make, shall have CCT of 5700°K, CR≥70, SDCM≤5, Life of 50000Hrs @ L70B50. The luminaire shall have IP rating of IP66 & IK rating of IK07. The luminaire shall have lens made of polycarbonate & optical cover made of toughened glass. The LED driver shall have operating voltage range of 140V to 270V, PF≥0.95 @ full load, THD≤ 10% @ full load, In-built surge protection of 4KV, HV Cut off @ 325V (±15V). The luminaire shall have 10KV SPD in-built inside the luminaire. The maximum dimensions of the luminaire shall be, L: 264M, Depth: 52MM & height without cradle: 203MM. The nominal weight of the luminaire shall be maximum 2.4KGs. The luminaire driver & it’s SPD shall be of the same make/manufacturer as that of LED luminaires. Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79, Type test as per IS10322, \\"FAT\\" before dispatch as per IS 10322 & IK Test. The successful bidder must submit the NABL accreditation certificate for Luminaire manufacturer before supply of material for approval. The LED Luminaire & it's driver both should be BIS registered. Successful bidder shall submit the following reports before supply of material for approvals LM79 issued by NABL accredited lab, LM80 issued by LED manufacturer, Type Test Certificate for luminaire as issued by NABL accredited lab, BIS certificate for LED Luminaire & Driver. Approved make Philips / Lighting techology / Trilux /wipro /Endo / Zumtobel / Ligman (to be approved before installation) The Agency / firm has to submit Techanical data sheet (TDS) along with above mentioned requisite certificates before supply of materials for approval from department not less than rank of SDO. |
| 15 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/lsolator) of Legrend /L&T /ABB /Simens /Schinder make dully isi marked complete with connections.of Legrend /L&T /ABB /Simens /Schinder make dully isi marked complete with connections. |
| 16 | 4 way (4 + 12), Double door Separate for Heating and lighting |
| 17 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioninq etc. as required of legrand / ABB /Schneider /L&T /Simens make |
| 18 | Supplying and fixing of 32-40 Amps rating DP 240/415 volts (10KA) of Legrend /L&T /ABB /Simens /Schinder make dully isi marked complete with connections.of Legrand / ABB /Schneider /L&T /Simens make |
| 19 | Supplying and fixing of 63 Amps rating DP 240/415 volts (10KA) of Legrend /L&T /ABB /Simens /Schinder make dully isi marked complete with connections |
| 20 | Supply,Laying,Testing & Commissioning of 50 sq.mm 2 - core armored Al Cable XLPE/ PVC Insulated and Steel sheathed of Havells/paramount make, including cost thimbles on input aswell as output sides dully crimped with hydraulic crimping tool incl making of necessary connections |
| 21 | Earthing with G.l. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoall coke and salt as required.The job includes providing and fixing of main hole PVC Chamber with its cover complete job |
| 22 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 23 | Supply/ installation/testing and commissioning of OUT DOOR TYPE dOUBLE DOOR Wall mounted compartmentalized , 415 volts TPN MCCB Main Distribution panels ,fabricated out of sheet steel of 16 gauge dust protected, duly painted with powder coating ( not less than 80 microns ) incl earth terminal with all necessary accessories as required for panel (IP 54) with internal wiring of panel .The Panel is to provided and fitted with following adjustable type controlling /Protection switch gear devices (1) Normal Incoming (1A) 125 Amp DP MCB (10KA) of Legrend /Schinder /Simens / ABB make = 1 no (1B) 200 Amp PN Aluminium Bus bar having size of 20 x 10 mm colour coded = 1 Set One No. (1 No.) digital multifunctional meter 1 Set of phase indication lamps (2) Generator Incomer 63 Amp F.P Change over switch of Havels./HPL /Standard make = 1 no100 Amp PN Aluminium Bus bar having size of 20 x 10 mm colour coded = 1 Set One No. (1 No.) digital multifunctional meter 1 Set of phase indication lamps (3) Invertor Incommer 63 Amps DP MCB (10KA) of Legrend /Schinder /Simens / ABB make =1 No.100 Amp PN Bus bar Al Strips = 1 Set((4) Outgoing .63 Amps Double Pole MCB (10 KA) of Legrend /Schinder /Simens / ABB make = 3 No40 Amps Double Pole MCB (10 KA)of Legrend /Schinder /Simens / ABB make = 2 No 32 Amps Double Pole MCB (10 KA)of Legrend /Schinder /Simens / ABB make =4 No The Panel manufacturing unit should be CPRI Registered and the Contractor has to submit the test certificate of main switch gear's and Drawing's of panel (Showing claerly dimensions of panel with spacing of switchgear as per IE Standards ) & is to approved by Department not less than the rank of SDO before manufacturing of panel. |
| 24 | Supply, Installation, Testing & Commissioning of 1.5 Ton, D.C invertor Techonology Hot and Cold Air Conditioner of IFB/ LG /Blue Star make (to provide heating as well as cooling and dehumidification) . remote controlled suitable for operation on 220-240 volt single phase AC Supply alongwith all the features that are in vogue in latest model .The job includes fitting of indoor unit on wall by employing suitable clamps and outdoor units on angle iron Stand for holding of out door unit fitted with nuts and bolts,laying of refrigerant copper piping upto 3 mtrs whereever needed, insulating the copper pipeline with nitrilic foam, topping up with refrigerant for additional length of piping etc.complete. The job also includes p/f of pvc flexible drain pipe of length 12 mts alongwith fittings. The job further encompasses carrying out repairs to walls whereever the same are cut. |
| 25 | Supply, Installation, Testing & Commissioning of 4 KVA Relay type automatic Aluminium r wound voltage Stabilizer of Chinar suitable for 1.5 Ton AC with input voltage of 85-305 Volts thereby producing the desired output voltage with necessary dash fasteners incl making of necessary connections. of IFB /Blue star /V Guard make |
| 26 | Supply,Installation,Testing & Commissioning of 2 KVA Power Inverter (24 Volts) Sine wave type of make (Sukam / Luminous / Exide / Micro tec/Liv guard make ).The invertor shall have inbuilt display unit showing input and output voltage ,Charging voltage , output current etc with having inbuilt protection device of suitable capacity . The invertor should invertor and UPS mode of operation . The job further includes Supply , Installation , Testing & Commissioning of 2 No's of 180 AH /12 V Tall tubular Inverter Batteries of same make as of inverter ,the batteries are to be housed in pvc trolley incl cost of trolley . complete job.The job includes AMC of batteries and invertor for a period of three years ,which includes quarterly servicing of devices & as and when required. complete job. Please Enable Macros to View BoQ information |