| 1 | Item Rate BoQ BoQ_Ver4.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: HQ CWE (AF) NAGPUR Name of Work: PROVN OF AC POINT IN OMQs/SMQs INCLUDING B&R WORKS FOR MARKING DUCTS AND E&M WORKS BOR ELECTRICAL POINT AT MC (U) UNDER GE (AF) NAGPUR Contract No: CWE (AF) / NGP /NAG/ OF 2025-26 Name of the Bidder/ Bidding Firm / Company : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl. No. Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE inclusive of all taxes in Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Quoted Amount in Words Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | Material and labour for sub main wiring (concealed/surface) complete with two single core 4 Sqmm FRLSH PVC insulated unsheathed stranded copper conductor cable drawn through in and including 20 mm dia rigid non-metallic PVC conduit heavy grade and conduit accessories including 4 Sqmm FRLSH PVC insulated unsheated stranded copper earth cable connected to common earth dolly complete and including cutting chasing in walls for concealed wiring using machine cutting and making good the disturbed surface all as specified and directed. Make of cable : Polycab, Finolex, Havells. Note: 3 run of 4 sqmm&one run of PVC conduit shall be measured as single unit. |
| 3 | Supply and fix power unit with 20A SP MCB alongwith 20 A Plug for AC upto 2 ton, 3 module, 240 volts all as specified and directed. Make: Legrand , Seimens, Anchor Roma, Havells |
| 4 | Supply and fix MCB SP 6-32 Amps, breaking capacity 10 KA 'C' curve confirming to IS/IEC 60898-1 2002,integrated label holder, sliding bottom clamp , IP 20 protected terminal, sliding shutters, 240 volts, 50 HZ including making necessary incoming and outgoing electrical connection with suitable size of copper lugs etc, complete all as specified and directed.Make : Legrand or equivalent in ABB,Seimens |
| 5 | Supply and fix MCB TPN 40-100 Amps, breaking capacity 10 KA 'C' curve confirming to IS/IEC 60898-1 2002,integrated label holder, sliding bottom clamp , IP 20 protected terminal, sliding shutters, 240 volts, 50 HZ including making necessary incoming and outgoing electrical connection with suitable size of copper lugs etc, complete all as specified and directed. Make : Legrand , ABB , Seimens |
| 6 | Material and labour for laying & testing of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminum conductor of size 35 sqmm 4 Core all as per IS , complete all as specified and directed. |
| 7 | Material and labour for laying & testing of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminum conductor of size 50 sqmm 3.5 Core all as per IS , complete all as specified and directed. |
| 8 | Material and labour for laying & testing of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminum conductor of size 150 sqmm 3.5 Core all as per IS , complete all as specified and directed. |
| 9 | Material and labour for laying & testing of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminum conductor of size 120 sqmm 3.5 Core all as per IS , complete all as specified and directed. |
| 10 | Material and labour for laying & testing of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminum conductor of size 185 sqmm 3.5 Core all as per IS , complete all as specified and directed. |
| 11 | Material and labour for laying & testing of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminum conductor of size 240 sqmm 3.5 Core all as per IS , complete all as specified and directed. . |
| 12 | Excavation in trenches not exceeding 1.5 metre wide & not exceeding 1.5 meter in depth for foundation,laying of cable or pipe ( where provided for protection of cable or fixing with poles and stays) and getting out in any type of soil including trimming the sides and forming bottom surfaces to required levels complete all as specified and directed. |
| 13 | Removing surplus excavated soil to a distance n.exc. 50 metre and depositing where directed at a level n.exc.1.5 metre high from the starting point. |
| 14 | Returning, filling in trenches in soft/loose soil in layers n.exc. 25 cm after laying of cables including spreading, levelling, and well ramming complete all as specified and directed. |
| 15 | Boring of hole under road/pavement/hard standing or any other situation by mannual means and suitable for passing of HDPE pipe 40 to 100 mm bore and making good both ends all specified and directed |
| 16 | Material and labour for High density polyethylene pipes (HDPE) DWC duct pipe of size 50 mm inner dia laid in trenches for passing of LT cable complete all as specified and directed. |
| 17 | Material and labour for High density polyethylene pipes (HDPE) DWC duct pipe of size 90 mm inner dia laid in trenches for passing of LT cable complete all as specified and directed. |
| 18 | Material and labour for demolition of Hardstanding , road & concrete in floor for laying of LT cable and making good the disturbed surfaces of floor by applying cement plaster matching with the existing surfaces complete all as directed. |
| 19 | Material and labour for PCC 1:3:6 type C-2 (using 40 mm gradded aggregate) for foundation, filling and mass concrete etc complete all as specified and directed . |
| 20 | Note : The amount against Schedule of Credit on Page No. 23 shall be deducted from the total amount quoted against Sch 'A' while deriving lum Sum for Acceptance. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |