| 1 | Earth work in excavation in foundation, trenches etc. including dressing of sides and ramming of bottoms, including getting out the excavated material, refilling after laying pipe/ foundation and disposal of surplus excavated material at a lead upto 50m suitable site as per direction of Engineer for following depths, below natural ground / Road top level.In all types soils/ saturated soil such as moorum, sand, sandy silt, clay, black cotton soil, kankar, etc.Depth upto 1.5 mSGNR RUB PUMP HOUSE TO 13MLD STP |
| 2 | JODKIYNA PHATAK PUMP HOUSE TO 13MLD STP |
| 3 | Providing, lowering, laying in trenches, aligning, fixing in position and jointing Ductile Iron (DI) ISI marked K-7 grade S&S pipes as per IS:8329-2000 (amended up to date), with internal High Alumina Cement (HAC) mortar lining for gravity sewer network with rubber ring (EPDM) joints as per IS: 5382-1985 (excluding special accessories) complete including all material, labour, hydraulic testing and commissioning as per technical specifications and as per direction of Engineer. Note : E/w to be measured and paid separately.350 mm |
| 4 | 600mm |
| 5 | Constructing masonry Chamber 120x120x100 cm, inside with 75 class designation brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100 mm. top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement :2 coarse sand : 4 graded stone aggregate 20 mm nominal size) necessary excavation foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick finished with a floating coat of neat cement complete as per standard design :With F.P.S. bricks |
| 6 | Providing, lowering, laying, aligning, fixing in position in pipe line, Resilient Seated D/F DI Sluice valves of approved make & design standard of following dia complete (including jointing & jointing material ) including all material, labour, testing and commissioning along with pipe line as per Technical Specification & as per direction of Engineer.Manually operated class PN 1.0. 350 mm dia |
| 7 | Providing, lowering, laying, aligning, fixing in position and jointing in pipe line CI Kinetic Double Air Valves as per IS:14845 of following dia (including jointing and jointing material), including all material, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer. 200 mm dia |
| 8 | Providing, lowering, aligning, fixing in position in pipe line, DI D/F resilient seated (soft seated) Swing type Non Return Valve of approved make of following Pressure rating & dia complete, generally confirming to IS: 5312 (part -1)/ 2004 (amended up to date) and of following specifications: Body, Bonnet & disc of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequent revisions, Face to face dimensions as per IS 5312 (part -1):2004 Drilled as per IS:1538. Electrostatic Epoxy Powder(EP-P) / Fusion Bonded Epoxy (Non-Toxic & suitable for drinking water) coated with minimum thickness of 250 micron applied on body, cover and disc inside and outside . Disc seal ring of EPDM/ Neoprene (food grade quality) and disc seal retaining ring of SS/CS. Shaft of SS- AISI- 410, Hinge SS AISI 316/410 ,Bonnet Gasket EPDM ,Bush- Brass with EPDM/NBR \\"O \\"ring seal Nut-Bolt confirming to IS:1363 and IS: 1367 (galvanised steel) Insertion rubber of black EPDM 6mm thick. Suitable support structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work.Class PN 1.6, 350 mm dia |
| 9 | Providing and laying lean cement concrete 1:4:8 in Sub- base over a prepared sub-grade with coarse and fine aggregate conforming to IS: 383, the size of coarse aggregate not exceeding 25 mm, aggregate cement ratio not to exceed 15:1, aggregate gradation after blending to be as per table 600-1, cement content not to be less than 150 kg/ cum, optimum moisture content to be determined during trial length construction, concrete strength not to be less than 10 Mpa at 7 days, mixed in concrete mixer, laid manually, compacted with surface vibrator, finishing and curing complete as per clause 601, 112 of MoRT&H specification including all material, labour, machinery, lighting, guarding and maintenance of diversion |
| 10 | Providing and laying un-reinforced, plain cement concrete mix with Concrete Mixer & vibrator pavement over a prepared sub base with 43 grade cement , coarse and fine aggregate conforming to IS: 383, maximum size of coarse aggregate not exceeding 25 mm, mixed as per approved mix design, laid, spread, compacted and finished in a continuous operation including provision of contraction, expansion, construction and longitudinal joints etc including all material, labour, machinery, lighting, guarding and maintenance of diversion. PCC M-20 |
| 11 | Providing, lowering, laying, aligning, fixing in position at and jointing at all level/ depths DI K-12 standard specials with rubber ring (EPDM/SBR) joints as per IS: 5382-1985 such as tees, bends, tapers, caps etc. within trenches in DI pipe line complete including all material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer. Note : E/w to be measured and paid separately. Specials S&S DI K-12 Above 300mm dia and upto 600mm dia |
| 12 | Fabrication, supply of flanged/ plain ended MS pipe made from MS sheet strips of relevant IS specification of approved thickness by welding, lowering, laying, aligning, fixing in position at all level/ depths in trenches complete (excluding flanged jointing wherever required) including all material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer. Note : E/w to be measured and paid separately. MS pipe specials upto 600mm dia (with minimum 5mm thickness sheet) |
| 13 | Construction of boundary wall of Brick/ stone masonry as per enclosed GA drawing, scope of work and technical specifications complete work in all respect. Brief details of boundary wall parameter is as below:1. Depth of foundation- 900 mm.2. PCC in M-10, width -900 mm and thickness 100 mm,3. Stone/Brick masonry in CM: 1:6 section of foundation above PCC, 600 mm (W )x 450 mm (D) and 450 mm (W) x 450 mm (D)4. Superstructure work: Stone masonry in CM: 1:6, W-300, height-1650 mm,/ Brick work in CM: 1:6 W-230 mm, height- 1650 mm.5. Cement mortar pointing on Stone masonry and cement mortar plaster 20 mm thick on brick masonry in CM 1:6.6. Expansion joint shall be on every 30 mtr.7. On top of wall there shall be CC Coping 75 mm thick (1:2:4) shall be provided.8. Pillar for main gate 350x350 mm in size is part of boundary wall.9. Cement paint of approved colour in 3 coat shall be done. Please Enable Macros to View BoQ information |