| 1 | Maintenance, servicing, cleaning of Busbur chamber of each VCB including conneting busbar from CT to Busbar, spout, support insulator, opening of covers, using CTC and clean cloth and hot air blower, checking for any loose contact, tigtening of all nuts & bolts, refixing all covers complete all as specified and as directed |
| 2 | Maintenance, servicing, cleaning of vacuum circuit breaker unit of 11 KV VCB panel of capacity 400 Amps to 2500 Amps, taking out from panel, cleaning of all parts with CTC and clean cloth, removal of carbon deposited inside the moving contacts, greasing of all moving parts of the VCB, checking of complete operating mechanism for proper functioning, reporting for any defective parts, complete all as specified and as directedNote: Replacement of defective parts of the VCB shall be measured and paid separately |
| 3 | M&L for rectification of fault of electrical circuit of 11 KV VCB by checking, repair from CT/PT and programming of multifunctional meters and replacement of defective wiring with FRLSH multistranded PVC insulated copper conductor 1100 volts grade as per existing size of wire complete all as specified and as directed |
| 4 | M&L for rectification of fault of control circuit of 11 KV VCB by checking, repair of close / trip / spring charging circuit replacement of defective wiring with FRLSH multistranded PVC insulated copper conductor 1100 volts grade as per existing size of wire complete all as specified and directed |
| 5 | M&L for rectification of fault of indication circuit of 11 KV VCB by checking, repair of indicating LED lamp circuit, annuciation system replacement of defective wiring with FRLSH multistranded PVC insulated copper conductor 1100 volts grade as per existing size of wire complete all as specified and as directed |
| 6 | M&L for rectification of fault of heater circuit of 11 KV VCB by checking, repair of thermostat / heater circuit system replacement of defective wiring with FRLSH multistranded PVC insulated copper conductor 1100 volts grade as per existing size of wire complete all as specified and as directed |
| 7 | M&L for rectification of fault of AC light circuit of 11 KV VCB by checking, repair of door switch , B-22 polycarbonate holder and replacement of defective wiring with FRLSH multistranded PVC insulated copper conductor 1100 volts grade as per existing size of wire, Lamp holder, door switch complete all as specified and directed |
| 8 | M&L for rectification of fault of DC 110V circuit of 11 KV VCB by checking, repair from battery charger to VCB and and internal distribution to other components /system and replacement of defective wiring with FRLSH multistranded PVC insulated copper conductor 1100 volts grade as per existing size of wire complete all as specified and as directed |
| 9 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 M deep for taking out / laying cable and getting out in soft/loose soil complete all as specified and as directed |
| 10 | Excavation in trenches n.exc 1.5m wide and n.exc 1.5m in depth and getting out in soft disintegrated rock (considered for road cutting) complete all as specified and directed. |
| 11 | Returning, filling in soil including spreading, levelling, watering and well ramming in layers not exceeding 25 cm complete all as specified and as directed |
| 12 | Removing excavated soil to a distance not exceeding 50M and depositing where directed at level not exceeding 1.5 m above starting point complete all as specified and as directed |
| 13 | M&L for dry sand cushioning for under ground cable provided with layer and sand 8cm deep before laying the cable and 15cm after laying the cable complete all as specified and directed. |
| 14 | Supplying and laying un-reiforced precast concrete cable cover, class LV, Type 1, flat, size 250mm x 150mm x 40mm all as specified and directed. |
| 15 | M&L for PCC type B1 1:2:4, using 20mm graded stone aggregate for pole coping / road / drain / path against damage due to excuvation/laying of cable complete all as specified and directed. |
| 16 | S&F GI pipe 100 mm dia medium grade for cable protection laid in floor including taking out old unserviceable GI Pipe complete all as specified and directed. |
| 17 | Supply and laying in trenches XLPE insulated, armoured, heavy duty electric cable with stranded aluminium conductor, 1100 Volts grade cross section area 400 Sqmm 3.5 core and connection complete with aluminium cable lugs incl dismantling taking down unsv one all as specified and directed. |
| 18 | S&F Cable joining kit for 1.1 KV grade cable for straight through heat shrink type joint complete with joining material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 240 sqmm including dismantling / taking down unserviceable one complete all as specified and directed. |
| 19 | All as per item No. 18.00 above, but for size 300 Sqmm, 3.5 Core |
| 20 | All as per item No. 18.00 above, but for size 400 Sqmm, 3.5 Core Please Enable Macros to View BoQ information |
| 21 | All as per item No. 18.00 above, but for size 400 Sqmm, 3.5 Core Please Enable Macros to View BoQ information |