| 1 | Supply, Installation, Testing and Commissioning of air cooled ducted split type air conditioning machine with each having a capacity and details as mentioned below suitable for operation on R 32/R-410A /R-407 Green refrigerant comprising of Scroll type compressor hermetically sealed complete with automatic capacity, safety switches, lubrication system with min 5 year(OEM) warranty for both compressor and Printed Circuit Board (PCB), Suitable capacity squirrel cage induction motor having class 'B' insulation suitable for operation on 415 + 10% volts, 50Hz, A.C. supply for Blower motor, Necessary drive arrangement for blower motor, Matching Air cooled condenser with necessary fittings for refrigerant piping connections, necessary structural support for mounting condensers, Microprocessor based control panel complete with accessories, machine Isolation /disconnect switch, valves and accessories to inter connect compressor and condenser including pressure testing, vacuum. Necessary starters suitable for Indoor & outdoor unit complete with O/L, U/V, phase reversal protection, single phase preventor i/c copper conductor control and power cable and drain pipe of suitable size and length etc. complete as required. The total cooling capacity/heating capacity of tested unit shall have a capacity as per relevant IS code. The lab testing reports as per IS: 8148 shall be submitted from National Accreditation Board for Testing and Calibration Laboratories (NABL)accredited as per ISO/International Electro technical Commission (IEC) 17025 standards/ Central Power Research Institute (CPRI)/ Electrical Research and Development Association (ERDA) with Original Equipment Manufacturer (OEM) etc. complete as per CPWD specification as required. |
| 2 | 5.5 TR (3.2 EER) |
| 3 | SUB HEAD - II [Associated items] Providing/Fabricating and fixing M S Stand of suitable size for outdoor unit made out of 40x40x5 mm MS angle iron i/c cutting welding, painting, grouting etc complete with necessary MS angle support from the walls for Outdoor Unit mountings as required. |
| 4 | 40 X 40 X 5 mm MS angle iron |
| 5 | 40 X 5 mm MS flat strip |
| 6 | Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft drawn copper refrigerant piping for AC system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications complete as required. (The item shall be measured from outside connection of indoor unit to outside of condenser unit). |
| 7 | 9.5 mm dia with tube thickness 0.8 mm with insulation of suitable thickness |
| 8 | 15.87mm dia with tube thickness 0.8 mm with insulation of suitable thickness |
| 9 | Providing and fixing following size dia (nominal bore) FRLS, HMS (High Mechanical Stress), uPVC pipe from outlet socket of AC unit complete with uPVC fittings and clamps including cutting and making good the walls etc. complete as required. |
| 10 | 40 mm dia. |
| 11 | 25 mm dia. |
| 12 | Supply & fixing of control cum transmission wiring and AC power supply cable of shielded Copper conductor for looping between indoor & outdoor units complete as manufacturers standard compete as required. |
| 13 | 5c X 4 sq.mm PVC insulated copper conductor cable |
| 14 | S/F of PVC insulated PVC sheathed copper conductor armoured cable of 4c X 6 Sq.mm size of 1.1Kv grade on surface/ recess of wall with MS saddle complete as reqd. |
| 15 | Supplying and fixing FP sheet steel enclosure on surface/ recess along with 25/32 A 415 V \\"C\\" curve FP MCB complete with connections, testing and commissioning etc. as required. (Havells/Legrand) |
| 16 | Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. |
| 17 | Thickness 0.63 mm sheet |
| 18 | Thickness 0.80 mm sheet |
| 19 | Providing & Fixing supply air grills of Powder coated Aluminum construction having a free area of not less than 70% without volume control dampers in the supply air system as per site requirements complete as per detailed specifications. |
| 20 | Supplying and installing following nominal size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. |
| 21 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 22 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 23 | Note:- 1. The Agency has to submit police verification record & ID proof of each staff.2. The firm shall provide each staff with working cell phone.3. The staff may be deputed for duty as per instruction of concerned SDE (E)/JTO (E).4. Penalty shall be imposed in case of absence of any staff as per T & C of contract.5. The Estimated Rates are inclusive of GST / other Input Tax Credit (ITC) taxes as applicable & Freight Charges (Unloading & Stacking) etc., the contractor shall quote accordingly.6. The contractor shall provide correct tariff heads & other details to enable BSNL claim Input Tax Credit.7. The bidder who submits the offer with concessional Goods and Service Tax (GST) shall submit the proof of applicable concessional GST. In case the Concessional GST is not creditable to BSNL it should be included in the price of the goods/services.8. The FF & packing amount quoted shall not be subject to change after bid evaluation /ordering on account of change of copper, lead base price, change in duties & taxes of item etc.9. Bidder must mandatorily mention HSN & SAC numbers.10. Evaluation of bids: - The evaluation and comparison of responsive bids shall be done on the basis of Net cost to BSNL on the prices of the goods & Services (i.e. complete work) offered along with all applicable Taxes, packing Forwarding Freight & Insurance charges etc. exclusive of GST.Declaration by Bidder1. We hereby declare that in quoting the above prices, we have taken into account the entire credit on inputs available under the GST Act introduced w.e.f. 1 July 2017 and further extended on more items till date.2. We hereby certify that HSN/SAC shown in column 17 are correct & credit of GST for the amount shown in column 10 above are admissible as per GST Laws.Name of bidder:Seal of Company: GST No./(s) Please Enable Macros to View BoQ information |