| 1 | Excavation in trenches, not exceeding 1.5 meter wide and not exceeding 1.5 meter in depth for foundation of poles, stays or for taking out/laying of cables and getting out in soft/loose soil complete all as specified and directed by Engr-in-Charge. |
| 2 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25cm in soft/loose soil complete all as specified and directed by Engr-in-Charge. |
| 3 | Removing excavated materials (soil) n. exc 50 m and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and directed by Engr-in-Charge. |
| 4 | M&L for crushed stone sand cushioning to UG cable, provide with the layer 8 cm before and 15 cm after laying and stretching jointing and testing the cable, complete all as specified and as directed by Engr-in-Charge.Note : Only punned thickness shall be measured. |
| 5 | Supply and laying of factory made, machine pressed, unreinforced, pre-cast concrete cable cover class LV type-1 flate size 250mm x 150mm x 40mm, complete all as specified and as directed by Engr-in-Charge. |
| 6 | M & L for steel tubular swaged poles type 410 SP-31 (9mtr long) complete with cast iron base plate, final taper plug, bolts, nuts & screws including two coats of aluminium paint over one coat of red oxide zinc chromet primer including portion above coping shall be painted in altermative bands of black and yellow colour starting with yellow colour (each band of 20 cm wide) by two coat of super enamelled paint upto 1.5m height all as specified complete in all respect conforming to IS-2713, including dismantling steel tubular pole, complete all as specified and as directed by Engr-in-Charge..Note : Excavation and earth work, cement concrete etc shall be measured and paid separately under respective item. |
| 7 | M&L for stay assy using stay rod 20 mm dia complete with accessories as shown in elect plate No 1,of SSR 2009 Part-I, incl. galvanized steel wire stranded of size 7/4mm including dismaintling of the existing complete all as specified and directed by Engr in Charge. |
| 8 | M & L for, Over head, aluminium conductor, steel reinforced, weasel, including making connections and fixing on poles with all necessary arrangements, including dismantling of ACSR or AAC conductors, complete all as specified and as directed by Engineer-In-Charge.Note: Weight of ACSR or all aluminium conductors drawn for overhead lines is to be determined by measuring taut horizontal distance between centers of two adjacent poles and compounding the weight of conductors of that size and length and 3% extra added for sag, jointing, jumpers, etc. |
| 9 | Re-Straining tightening of existing ACSR conductor of any size on LT/HT poles including necessary aluminium binding wire, connectors, PVC sleeves for jumpers etccomplete all as specified and directed by Engr-in-Charge. |
| 10 | M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint, including dismaintling of the existing cross-arms of M.S. channel or angle sections etc, complete all as specified and as directed by Engineer-In-Charge. |
| 11 | M&L for replacement of Pin type, porcelain,vitreous, white, green & brown insulator including one galvanised iron steel spindle, two galvanized iron washer and one galvanised iron nut, working pressure 1100 Volts and of size 65 mm dia and 100 mm height ISI marked complete all as specified and directed by Engr in charge. |
| 12 | M&L for replacement of shackle type, porcelain,vitreous, white, green & brown insulator including one galvanised iron steel spindle, two galvanized iron washer and one galvanised iron nut, working pressure 1100 Volts and of size 115 mm dia and 100 mm height ISI marked complete all as specified and directed by Engr in charge. |
| 13 | M & L for plain cement concrete (1:4:8) type D-2 (using 40mm graded stone aggregate) as in foundation of poles complete all as specified and as directed |
| 14 | M&L for PCC (1:3:6) type C-1 with 20 mm gradded stone aggregate for copping of poles Pedestal (PCC) or mass filling (CM 1:4) complete all as specified and directed by Engr in Charge. |
| 15 | Supply, laying & testing of heavy duty, XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables with stranded aluminium conductor, 1100 volts grade, of size 400 sqmm 3.5 core in trences or passing through pipes, ducts or fixed to walls/poles, including taking down old unserviceale cable, complete all as specified and as directed by Engr-in-Charge.Note :- Excavation and earth work shall be measured and paid separately under respective item. |
| 16 | Supply, laying & testing of heavy duty, XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables with stranded aluminium conductor, 1100 volts grade, of size 300 sqmm 3.5 core in trences or passing through pipes, ducts or fixed to walls/poles, including taking down old unserviceale cable, complete all as specified and as directed by Engr-in-Charge.Note :- Excavation and earth work shall be measured and paid separately under respective item. |
| 17 | Supply, laying & testing of heavy duty, XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables with stranded aluminium conductor, 1100 volts grade, of size 185 sqmm 3.5 core in trences or passing through pipes, ducts or fixed to walls/poles, including taking down old unserviceale cable, complete all as specified and as directed by Engr-in-Charge.Note :- Excavation and earth work shall be measured and paid separately under respective item. |
| 18 | Supply, laying & testing of heavy duty, XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables with stranded aluminium conductor, 1100 volts grade, of size 150 sqmm 3.5 core in trences or passing through pipes, ducts or fixed to walls/poles, including taking down old unserviceale cable, complete all as specified and as directed by Engr-in-Charge.Note :- Excavation and earth work shall be measured and paid separately under respective item. |
| 19 | Supply, laying & testing of heavy duty, XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables with stranded aluminium conductor, 1100 volts grade, of size 95 sqmm 3.5 core in trences or passing through pipes, ducts or fixed to walls/poles, including taking down old unserviceale cable, complete all as specified and as directed by Engr-in-Charge.Note :- Excavation and earth work shall be measured and paid separately under respective item. |
| 20 | Supply, laying & testing of heavy duty, XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables with stranded aluminium conductor, 1100 volts grade, of size 70 sqmm 3.5 core in trences or passing through pipes, ducts or fixed to walls/poles, including taking down old unserviceale cable, complete all as specified and as directed by Engr-in-Charge.Note :- Excavation and earth work shall be measured and paid separately under respective item. |
| 21 | Supply, laying & testing of heavy duty, XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables with stranded aluminium conductor, 1100 volts grade, of size 50 sqmm 3.5 core in trences or passing through pipes, ducts or fixed to walls/poles, including taking down old unserviceale cable, complete all as specified and as directed by Engr-in-Charge.Note :- Excavation and earth work shall be measured and paid separately under respective item. |
| 22 | Supply, laying & testing of heavy duty, XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables with stranded aluminium conductor, 1100 volts grade, of size 35 sqmm 3.5 core in trences or passing through pipes, ducts or fixed to walls/poles, including taking down old unserviceale cable, complete all as specified and as directed by Engr-in-Charge.Note :- Excavation and earth work shall be measured and paid separately under respective item. |
| 23 | Supply, laying & testing of heavy duty, XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables with stranded aluminium conductor, 1100 volts grade, of size 25 sqmm 3.5 core in trences or passing through pipes, ducts or fixed to walls/poles, including taking down old unserviceale cable, complete all as specified and as directed by Engr-in-Charge.Note :- Excavation and earth work shall be measured and paid separately under respective item. |
| 24 | Supply, laying & testing of heavy duty, XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables with stranded aluminium conductor, 1100 volts grade, of size 16 sqmm 4core in trences or passing through pipes, ducts or fixed to walls/poles, including taking down old unserviceale cable, complete all as specified and as directed by Engr-in-Charge.Note :- Excavation and earth work shall be measured and paid separately under respective item. |
| 25 | Supply, laying & testing of heavy duty, XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables with stranded aluminium conductor, 1100 volts grade, of size 10 sqmm 2core in trences or passing through pipes, ducts or fixed to walls/poles, including taking down old unserviceale cable, complete all as specified and as directed by Engr-in-Charge.Note :- Excavation and earth work shall be measured and paid separately under respective item. |
| 26 | M& L for replacement of GI Pipe light grade for cable protecton in road crossing and making good surface road to filling with PCC of size 80 mm dia complete all as specified and directed by Engr in Charge. |
| 27 | M& L for replacement of GI Pipe light grade for cable protecton in road crossing and making good surface road to filling with PCC of size 50 mm dia complete all as specified and directed by Engr in Charge. |
| 28 | M& L for replacement of GI Pipe light grade for cable protecton in road crossing and making good surface road to filling with PCC of size 40 mm dia complete all as specified and directed by Engr in Charge. |
| 29 | Supply Installation , Commissioning ,in replacement of of factory made cubical out door LT panel pedestal mounting type Confirming to IP-54 , CPRI approved fabricated from 3.15 mm thick CRCA sheet powder coated, Aluminium bus bar 600 Amp rating capacity, Three Phase and 400 Amp for Neutral with minimum clearance 75 mm , all as per IS shall be available inside for easy access and working condition, Markings should be made to identify incoming and outgoing circuits and earthing bolts at two points, including taking down of old existing panel complete. The panel should housing the following accessories :-(I) MCCB 4 pole 400 Amp 36 kA,-01 Nos ( As incomer)(ii) Change over switch 250 Amp capacity -01 No(iii) MCCB 4 pole 250 Amp 25 kA, -02 No(iv) MCCB 4 pole 200 Amp 25 kA, - 02 No.(v) MCCB 4 pole 63 Amp 25 kA, L&T, -02 Nos(vi) LED Voltmeter, L&T, -01 No(vii) LED Ammeter, L&T, -01 No(viii) Voltmeter Selector Switch, L&T, -01 No(ix)Ammeter Selector Switch, L&T, -01 No(x) CT 200/5, 5VA, Matrix tape wound ring type bar primary(xi) LED Indicating lamps Red/ Yellow, (xii) LED Indicating lamps Blue,(xiii) MCB SPN 20A, 10 kA, 'C' curve, -01 No(xiv) Aluminium Bus bar 450 Amp 4 strip. |
| 30 | Supply Installation , Commissioning ,in replacement of of factory made cubical out door LT panel pedestal mounting type Confirming to IP-54 , CPRI approved fabricated from 3.15 mm thick CRCA sheet powder coated, Aluminium bus bar 600 Amp rating capacity, Three Phase and 300 Amp for Neutral with minimum clearance 75 mm , all as per IS shall be available inside for easy access and working condition, Markings should be made to identify incoming and outgoing circuits and earthing bolts at two points. including taking down of old existing panel complete. The panel should housing the following accessories :-(I) MCCB 4 pole 350 Amp 36 kA, -01 No.(ii) MCCB 4 pole 160 Amp 25 kA, - 01 No.(iii) MCCB 4 pole 100 Amp 25 kA, -04 Nos.(iv) LED Voltmeter, L&T, -01 No (v) LED Ammeter, L&T, - 01 No(vi) Voltmeter Selector Switch-01 No(vii) Ammeter Selector Switch-01 No(viii) CT 250/5, 5VA, Matrix tape wound ring type bar primary(ix) LED Indicating lamps Red/ Yellow, (x) LED Indicating lamps Blue, (xi) MCB SPN 20A, 10 kA, 'C' curve, - 01 No.(xii) Aluminium Bus bar 300 Amp 4 strip. |
| 31 | Supply Installation , Commissioning ,in replacement of of factory made cubical out door LT panel pedestal mounting type Confirming to IP-54 , CPRI approved fabricated from 3.15 mm thick CRCA sheet powder coated, Aluminium bus bar 400 Amp rating capacity, Three Phase and 200 Amp for Neutral with minimum clearance 75 mm , all as per IS shall be available inside for easy access and working condition, Markings should be made to identify incoming and outgoing circuits and earthing bolts at two points. including taking down of old existing panel complete. The panel should housing the following accessories :-(I) MCCB 4 pole 200 Amp 36 kA, -01 No.(ii) MCCB 4 pole 100 Amp 25 kA, - 01 No.(iii) MCCB 4 pole 63 Amp 25 kA, -03 Nos.(iv) LED Voltmeter,-01 No (v) LED Ammeter, - 01 No (vi) Voltmeter Selector Switch, - 01 No(vii) Ammeter Selector Switch, -01 No(viii) CT 250/5, 5VA, Matrix tape wound ring type bar primary(ix) LED Indicating lamps Red/ Yellow, (x) LED Indicating lamps Blue, (xi) MCB SPN 20A, 10 kA, 'C' curve, - 01 No.(xii) Aluminium Bus bar 300 Amp 4 strip. |
| 32 | Supply Installation, Commissioning, in replacement of factory made cubical out door LT panel pedestal mounting type Confirming to IP-54 , CPRI approved fabricated from 3.15 mm thick CRCA sheet powder coated, Aluminium bus bar 800 Amp rating capacity, Three Phase and 400 Amp for Neutral with minimum clearance 75 mm , all as per IS shall be available inside for easy access and working condition, Markings should be made to identify incoming and outgoing circuits and earthing bolts at two points, including taking down of old existing panel complete. The panel should housing the following accessories :-(I) MCCB 4 pole 400 Amp 36 kA, -01 Nos (ii) Change over switch 250 Amp capacity , -01 No(iii) MCCB 4 pole 200 Amp 25 kA, - 02 No.(iv) MCCB 4 pole 63 Amp 25 kA, -01 Nos(v) LED Voltmeter, L&T, -01 No(vi) LED Ammeter, L&T, 01 No(vii) Voltmeter Selector Switch,-01 No(viii)Ammeter Selector Switch,-01 No(ix) CT 200/5, 5VA, Matrix tape wound ring type bar primary(x) LED Indicating lamps Red/ Yellow,(xi) LED Indicating lamps Blue, (xii) MCB SPN 20A, 10 kA, 'C' curve, -01 No (xiii) Aluminium Bus bar 450 Amp 4 strip. |
| 33 | Supply & Fix in replacement of twin core flat or round sheathed stranded copper conductor cable 1.5 Sqmm all as specified and directed by Engr-in-Charge. |
| 34 | Supply and fixing in replacement of junction box made of mild steel 1.6 mm thick of size 250mmx200mmx105mm incl 4 Nos aluminium bus bar of 2 mm thick duly fitted on the suitable insulator with fixing with 35x6mm ms flate iron with nut bolt and washer and incl one MCB SP 6 amp with rail fitted in ms box incl suitable size cable hole,gland duly painted with one coat of aluminium paint over a coat of red oxide etc complete all as specified and directed by Engr-in-Charge. |
| 35 | Supply and fixing in replacement of LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete. and all as specified and directed by Engr-In-Charge. |
| 36 | Supply & Fixing in replacement of Pole Street light bracket fabricated out of GI Tubing light grade 40/50 mm bore bend to the shape as directed and not less than length 1.0 Mtr complete with Mounting MS Clamp of Flat Iron size 40x5mm of suitable length of 02 Nos incl nut bolts etc of suitable size complete all as specified and directed by Engineer-In-Charge. |
| 37 | M & Lfor installing, testing and commissioning of factory made bus bar chanber with 160 Amps MCCB comprising of 4 Nos aluminium bus bar of 200 Amp rating supported on insulator and enclosed with sheet steel enclosure out door type made out of 3.15 mm thick CRCA sheet, with top edge tappered, dust and vermin proof , having locking arrangement at front and opening arrangement from front & rear both including fixing arrangement on pole/gorunting in floor, with colour coded FRP with compression cable glands for entry & exit of cables, powder coated including taking out old existing complete all as specified or directed by Engr-in-Charge. |
| 38 | M & L for earthing complete with Galvanized Steel earth plate electrode 60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25 M deep below ground level) with top edge of the plate not less than 1.5 M below normal ground level, connected to and including GI iron strip of size 25x4 mm flat by means of GI bolts, nuts, and washers, protected by 40mm bore Gl light grade ISI marked pipe upto and including test points. Earthing plate shall be surrounded by alternate layers 15cm thick of charcoal or coke and common salt all around bottom and top, 20mm dia Gl medium grade pipe for watering and including funnel, wire mesh, PCC chamber pit made with PCC (1:3:6) type C2 (using 20mm graded crushed store aggrgate) including necessary form work, excavation and earth work in any type of soil, returning filling in and disposal of surplus soil to a distance not exceed ing 50 M, pit cover 40 mm thick made with RCC (1:2:4) type B-1 (using 20mm graded crushed store aggrgate) including TMT reinforcement 80 mm dia @ 75 mm C/C both way, MS handle of 12 mm dia, cover rest on MS angle iron frame 40x40x6mm embeded in concrete duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, complete all as as shown in electrical plate No-3 of SSR Part-l, complete all as specified and as directed by Engr-in-Charge. |
| 39 | Deduct Schedule of Credit of Rs (-) 147191.00 (Minus) as listed in Schedule 'A' (Contd). Contract Sum shall be arrived after deducting the credit amount.Note :- Tenderers will not quote against this item being a firm amount. Please Enable Macros to View BoQ information |