| 1 | Supply and erection of 08 Mtrs. long swaged / step down type Steel Tubular Pole (Bottom Specification: 6.00m. Length x 139.70mm. O.D x 4.85mm. Thickness, Top Specification: 2.00m. Length x 88.90mm. O.D x 3.25mm. Thickness ) with earth work in excavation of foundation of size 3’-0” x 3’-0” x 3’-0” = 0.76 Cum in all type of soil including rough dressing and leveling the bed etc. complete with transportation, T&P and labour charges as per the direction of the Engineer-in-Charge. |
| 2 | Supply of all materials, labor, T&P for providing C.C. (1:1½:3) with hard granite broken chips of size 12mm including cost, transportation, sundries, conveyance, royality of all materials etc. complete as per direction of the Engineer-in-Charge. upto ground level : 1 x 3’-0” x 3’-0” x 2’-8” = 24.00 cft. Couping portion: 1 x 2’-0” x 2'-0\\" x 2’-0” =8cft. (-) Volume of pole up to top of couping : 3.14 x (0'-5½\\") /4 x 4'-8\\"=(-) 0.74 cft.=31.26cft. or say 0.88cum 4nos. |
| 3 | Supply of all materials, labour, T&P and transportation for centering and shuttering of the couping portion etc. complete as per direction of the Engineer-in-Charge. 4 x1’-6” x 1’-6” =9 sq.ft. Or say 0.83 sqm 4nos. |
| 4 | Supply & Fixing of lighting Fixtures of 120 Watt LED Street light having powder coated pressure die-cast Aluminium housing Clear toughened glass having folowing specification :(i)LED : LM80 certified high power LED(ii)Lens Suitable secondary lens for better(iii)Gear : Integral,Electronic constant current driver of min.85% efficiency(iv)Inernal wiring: Teflon insulated,Cu.Conductor(v)Hardware: SS & Ms zinc plated & passivity (vi)Ingress protection:IP66(vii)Lumen maintenance :50,000 Hrs @ L70(viii) Operating temperature : -10°C to 50°C(ix) Rated voltage & frequncy :240V,50 Hz AC |
| 5 | Supplying and fixing of 4 Arm Bracket having the following specification with welding of 1'-6\\" medium gauge M.S Pipe opened at an angle of 120ºC and top cover of dia 3½'' fixing in the of Tubular pole including cost of materials,labour,T&P and transportation etc.complete as per direction of the Engineer-in-Charge. |
| 6 | Supply and stringing of 2core 10sqmm unarmoured Al. cable with help of No.8 GI wire including supply and fixing of G.I pole clamp febricated 25mm x 6mm G.I flat etc complete as per direction of the Engineer-in-Charge. (Make: POLY CAB/Havells/Glostar/KEI) |
| 7 | Supply and erection of galvanized 'D' iron complete with suitable pole clamp 75mm x 88mm porcelain shackle insulator & 15mm dia galvanized bolt & nut including painting. |
| 8 | Supply and fixing of Galvanized stringing screw 12\\" x 5/8\\" dia. |
| 9 | Supply and fixing of 3 phase outdoor type panel board made of 16 SWG- C.R sheet of size 3'-0\\" x 2.'-0\\" x 1'-5\\" ( L x B x D) with epoxy grey powder coated. The panel board consisting of the following accessories.(i) Neon Indicator - 1 nos.(ii) Ring Copper Socket - 1 set.(iii) Timer - 1 no. (iv) Toggle Switch - 1 no.(v) 32 Amp Single pole Contactor - 1 no.(vi)Single phase 32 Amp Single pole MCB-3nos.(vii) Stud Connector-1 no.(viii) Single phase Copper Bus bar-4 nos.(ix)(ix) Danger Board - 1 no. with complete wiring with 10sq.mm / 4sq.mm / 2.5sq.mm copper wire as per direction of the E.I.C. Three Years On-Site Maintenance. |
| 10 | Wiring PVC conduit with Modular Type Switch Recessed wiring to light point/fan point/exhaust fan point/call bell point with 1.5 sqmm. FR PVC insulated single core multistrand copper conductor of ISI marked with 20mm dia non-metallic PVC flexible conduit with 5 Amp, 250 V Modular type switch ISI marked and ceilling rose ISI marked mounted on MS box having front Bakelite’s cover of suitable size, MS box with 1.5 sqmm FR PVC insulated single core multistrand copper conductor as earth wire including all accessories and connection as per direction of Engineer- in charge. (Make:WIRE FINOLEX/ L&T/ANCHOR/HAVELS/HPL/V GUARD) |
| 11 | Supply and drawing of following sizes FR PVC insulated single core multistrand copper conductor in existing surface/recessed steel /PVC conduct as required. |
| 12 | 2 x 2.5 sq mm |
| 13 | 2 x 4 sq mm |
| 14 | Supply and fixing of 20 watt LED Batten mounted Tube light fitting(Make:BAJAJ/CG/Havells/PHILIPS/SISKA etc.) |
| 15 | Supply,Delivery,Installation and testing of ceiling fan 0'-48'' size excel model etc.Complete as per direction of E.I.C(Make:BAJAJ/CG/HAVELLS/USHA) |
| 16 | Installation testing commissioning of resistance type ceilling fan regulator in existing switch box including connection with 1.5 sq.mm FR PVC Insulated single core Multistand copper earthing the regulator as required. |
| 17 | Cable trenching in all types of soil excepting rocky soil including excavation of earth, bricks laying and filling of sand and loose earth to the original ground level with surface dressing after laying of 01 no 1.1 K.V.PVC insulated PVC sheathed armored underground cable size 04 core x 10sq.mm inside the trench and removal of surplus earth to a lead up to 05 KM. |
| 18 | Supply and stringing of 4core x 10sq PVC insulated PVC sheated armored underground aluminium cable for power supply from Panel Board to street light poles including cost of materials,labour,T&P and transportation etc.complete as per direction of the E.I.C (Make: POLY CAB/Havells/Glostar/KEI)Three Years On-Site Maintenance. |
| 19 | Supply and laying of 50 mm dia HDPE Pipe inside the trench for laying of cable including cost of materials,labour,T&P and transporataion as per direction of the Engineer-in-Charge. |
| 20 | Supply and wiring of 3 core 1.5 mm square round flexible copper cable from junction box to light fitting (Make-Finolex/Polycab/kei/Gloster) as per the direction of the E.I.C. |
| 21 | Supply and fixing of Timer etc.complete with transportation,T&P and labour charges as per the direction of the Engineer-in-Charge. |
| 22 | Supply and fixing of 3 phase 4 pole 40 Amp.240 Volt Contactor etc.Complete with transportation,T&P and labour charges as per the direction of the Engineer-in-charge. |
| 23 | Supply and fixing of 4 way MCB of 63 Amp.etc.complete with transportation,T&P and labour charges as per the direction of the Engineer-in charge. |
| 24 | S/F \\"C\\" SERIES SP MCB/SPN MCB/TP MCB &TPN MCB.Supply and fixing of 5 amp to 32 amp rating 240 V \\"B\\" series miniature circuit breaker suitable for lighting and other loads of the following poles in the existing MCB DB ISI marked complete with connections testing and commissioning etc as required.Single Pole. |
| 25 | Supply and fixing of 4 pole Poceline connector for street light pole including necessary connections. |
| 26 | Supply and Fixing of fixtures of 60 watt LED Street Light Fitting having powder coated pressure die-cast Aluminum housing Clear toughened glass having following specifications:LED : LM80 certified high power LED:LENS:Suitable Secondary lens for better light distrubution:Gear: Integral,Electronic constant current driver of min.85% efficiency.Internal Wiring:Teflon Insulated,Cu.Conductor:Hardware:SS & Ms zinc plated & passivated :Ingress protection:IP66:Lumen maintenance : 50,000 Hrs@ L70 Operating temperature :--10°C to 50°C Rated voltage & frequency:240V,50Hz AC : Current:<0.65 A:Pf:>0.95:Ithd:<10%:Efficacy:>85m/W:CCT:5700K:CRI:>70 |
| 27 | Earthing with G.I earth pipe 3 meter long 40 mm dia ISI marked including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc with charcoal and salt as required. |
| 28 | Supply and laying 6 SWG G.I wires ISI marked at 0.5 meter below ground level for conductor earth elctrode including soldering etc.as required. Please Enable Macros to View BoQ information |