| 1 | Supply and erection of Galvanized Octagonal Pole shall be in single piece section. This shall not be any circumferential weld joint. The pole shall be hot dip galvanized as per the IS-2629/ IS-2633 / IS- 4759 standards with average coating thickness of 70 micron. The galvanizing shall be done in single dipping. The pole shall be bolted on a pre-cast foundation with a set of four foundation bolts for greater rigidity. The galvanized mounting decorative Sword type Double Armed Bracket with SS dome shall be supplied along with the poles for installation of the luminaries as per the design. |
| 2 | The pole shall have door of approximate 500mm length at the elevation of 3000mm from the base plate. The door shall be vandal resistance and shall be weather proof to ensure safety of inside connection. The door shall be flush in one side with double hinge arrangement with the extension surface and shall have suitable locking arrangement with 4 pin Loop in Loop out system with 16 Amp. MCB and connector arrangement. There shall also be suitable arrangement for the purpose of earthing. The pole shall be adequately strengthened at the location of the door to compensate for the loss in section. The door should be in special locking arrangement to avoid theft of inside accessories (As per sample & direction of EIC) |
| 3 | Specification of the Pole: |
| 4 | Height of pole: 9 Mtrs. |
| 5 | Top of dia: (A/F)100 mm |
| 6 | Bottom of dia:(A/F)175 mm |
| 7 | Thickness of the Sheet: 03mm |
| 8 | Base plate dimensions: (LxBxT) 275mm x 275mm x 16mm |
| 9 | Foundation of Pole : Steel Grade EN-8 |
| 10 | J-Bolt size (no. x dia): 4 x 24mm |
| 11 | Pitch Circle dia(PDC) : 275 mm |
| 12 | Bolt Length: 750mm |
| 13 | Projected Bolt Length: 125mm |
| 14 | Single/Double Arm Designer Bracket Length: 1½ Mtrs. Long each. (Make: Bajaj/BPP/Crompton/Skipper/Utkarsh) Three Years On-Site Maintenance. Manufacture test certificate of pole & arm to be submitted after completion of the work satisfactorily. |
| 15 | Supply of all materials, labour, T&P and transpiration for providing earth work, filling in foundation with clean coarse river sand, RCC M-20 using 12mm size hard granite Stone Chips with centering, sheltering including cutting, bending, binding & tying the Grills and cost of M.S. Rod, binding wire, providing 6mm thick Cement plaster finished smooth over RCC surface, painting two coats of paint with weather proof cement paint over one coat of primer and carriage of excavated materials within 5 kms lead by mechanical means with cost, conveyance, royalty, taxes etc. all complete as per the OPWD specification & direction of E.I.C. Three Years On-Site Maintenance. |
| 16 | Supply and erection of 08 Mtr. long swaged / step down type G.I Hot Galvanised Tubular Pole (Bottom Specification: 6.00m. Length x 139.70mm. O.D x 4.85mm. Thickness, Top Specification: 2.00m. Length x 88.90mm. O.D x 3.25mm. Thickness) & baseplate of size 300mm x 300mm x 6mm with earth work in excavation of foundation of size 3’-0” x 3’-0” x 3’-0” = 0.76 Cum in all type of soil including rough dressing and leveling the bed etc. complete with transportation, T&P and labour charges as per the direction of the Engineer-in-Charge. Three Years On-Site Maintenance. Manufacture test certificate of pole to be submitted after completion of the work satisfactorily. (Make: Bajaj / Skipper / Transrail / Valmont / Utkarsh) |
| 17 | Supply of all materials, labor, T&P for providing C.C. (1:1½:3) with hard granite broken chips of size 12mm including cost, transportation, sundries, conveyance, royality of all materials etc. complete as per direction of the Engineer-in-Charge. upto ground level : 1 x 3’-0” x 3’-0” x 2’-8” = 24.00 cft. Couping portion: 1 x 2’-0” x 2'-0\\" x 2’-0” =8cft. |
| 18 | (-) Volume of pole up to top of couping : 3.14 x (0'-5½\\")² /4 x 4'-8\\"= (-) 0.74 cft. = 31.26cft. Or say 0.88cum for 2nos. |
| 19 | Supply of all materials, labour, T&P and transportation for centering and shuttering of the couping portion etc. complete as per direction of the Engineer-in-Charge. 4 x1’-6” x 1’-6” =9 sq.ft. Or say 0.83 sqm for 2nos. |
| 20 | Supply and fixing of 4 Arm Bracket having the following specification with welding of 1’-6” medium gauge G.I Hot Galvanised bended at an angle of 120º and top cover of dia 3½\\" fixing in the top of Tubular pole including cost of materials, labour, T&P and transportation etc. complete as per direction of the Engineer-in-Charge. Three Years On-Site Maintenance. Manufacture test certificate of pole to be submitted after completion of the work satisfactorily. |
| 21 | Supply and stringing of 2core 10sqmm unarmoured Al. cable with help of No.8 GI wire including supply and fixing of G.I pole clamp febricated 25mm x 6mm G.I flat etc complete as per direction of the Engineer-in-Charge. (Make: POLY CAB/Havells/Glostar/KEI) |
| 22 | Supply and erection of galvanized 'D' iron complete with suitable pole clamp 75mm x 88mm porcelain shackle insulator, 16sqmm string wire & 15mm dia galvanized bolt & nut including painting. |
| 23 | Supply and fixing of Galvanized stringing screw 12\\" x 5/8\\" dia. |
| 24 | Supply of all materials, labour, T&P and Transportation for Febrication of G.I Channel size 2\\" x 2\\" x 1/4\\" including suitable arrangement for fixing of flood lights & spot/spike lights and the same to be fixed up in wall surface with help of nut & bolt etc as per direction of EIC. |
| 25 | Supply & Fixing of 300Watt LED Flood light made up of pressure die-cast Aluminium housing with toughened glass and high power LED's and secondary lenses with IP-66 protection. System efficacy > 110LPW 10KV SPD included. Three Years On-Site Warranty & Maintenance (Make: Bajaj/ Havells / Crompton / HPL / Jaquar/ Wipro/ K-Lite) |
| 26 | Supply and fixing of lighting Fixtures of 120 Watt. LED Street Light having powder coated pressure die-cast Aluminum housing Clear toughened glass having following specification: |
| 27 | LED : LM80 certified high power LED |
| 28 | Lens : Suitable secondary lens for better light distribution |
| 29 | Gear : Integral, Electronic constant current driver of min. 85% efficiency |
| 30 | Internal Wiring : Teflon insulated, Cu. Conductor |
| 31 | Hardware : SS & Ms zinc plated & passivity |
| 32 | Ingress protection : IP66 |
| 33 | Lumen maintenance : 50,000 Hrs @ L70 |
| 34 | Operating temperature : -10ºC to 50ºC |
| 35 | Rated voltage & frequency : 240V, 50Hz AC |
| 36 | Wattage : 120±10% |
| 37 | Current : < 0.65A |
| 38 | Pf : > 0.95 |
| 39 | Ithd : < 10% |
| 40 | Lumen : 14400 lm |
| 41 | Efficacy : >120lm/W |
| 42 | CCT: 5700K |
| 43 | CRI : >70 |
| 44 | IK Rating : IK10 |
| 45 | Protections: Open & Short circuit protection, reverse polarity protection and surge protection. (Make: Bajaj/ Havells/ Crompton/ Jaquar/ HPL/ Wipro). Manufacture test certificate of pole & arm to be submitted after completion of the work satisfactorily. Three Years On-Site Maintenance. |
| 46 | Supply and fixing of 3 phase outdoor type panel board made of 16 SWG- C.R sheet of size 3'-0\\" x 2.'-0\\" x 1'-5\\" ( L x B x D) with epoxy grey powder coated. The panel board consisting of the following accessories. |
| 47 | (i) Neon Indicator - 3 nos. |
| 48 | (ii) Ring Copper Socket - 4 nos. |
| 49 | (iii) 3 phase Timer - 1 no. |
| 50 | (iv) Toggle Switch - 1 no. |
| 51 | (v) 63 Amp 4 pole Contactor - 1 no. |
| 52 | (vi) 3 phase 63 Amp 4 pole MCB-2 nos. |
| 53 | (vii) Stud Connector 4 way, 1 no. |
| 54 | (viii) 3 Phase Copper Bus bar - 4 nos. |
| 55 | (ix) Danger Board - 1 no. with complete wiring with 10sq.mm / 4sq.mm / 2.5sq.mm copper wire as per direction of the E.I.C. Three Years On-Site Maintenance. |
| 56 | Supply & fixing of 8\\" x 10\\" G.I junction box with locking arrengement, welded with G.I tubular pole having connector and MCB to be fix inside the box for power supply to Semi Highmast fittings. |
| 57 | Earthing with G.I earth pipe 3 meter long 40 mm dia ISI marked including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc with charcoal and salt as required. |
| 58 | Supply and laying 6 SWG G.I wires ISI marked at 0.5 meter below ground level for conductor earth elctrode including soldering etc. as required. Please Enable Macros to View BoQ information |