| 1 | Supply, Installation, testing & commissioning of 150W Spun Aluminium housing with pressure die cast heat sink, Ring Spun Aluminium Grey finish powder coated, Cover, Clear Polycarbonate. Mains Terminal 3-way 10A, suitable for terminating up to max. 2.5Sq.mm incoming cable, cable entry through mounting pipe, SS Hardware, IP 65 Ingress Protection, Potted driver: BIS approved (Electrical Safety as per IS 15885), High Surge Protections Potted Driver with 4KV internal + 10KV SPD, Electrical Protection, High Voltage, Short Circuit, Rated Voltage (V) 240 Frequency (Hz) 50 Operating Voltage Range (V) 120-270, (A) @ 240V 0.657 Wattage (W) @240V 150 Reverse Polarity & Open Voltage Protection, THD<10%, PF>0.95, Correlated Colour Temperature (CCT) K 3000K, suitable for existing arm. |
| 2 | Sample to be produced before installation of fittings. LM79 test report shall be submitted from in-house NABL accrediated LAB. Manufacture test certificate of Light fittings shall be submitted after completion of the work satisfactorily. Three Years On-Site Maintenance. (Make: Philips(Non-Ecolink)/ Bajaj/ Havells/ Crompton/ Jaquar/ HPL/ WIPRO) |
| 3 | Dismantle of Decorative Poles by mechanical means. Cleaning both Pole, base, arm using sand paper,colouring the pole with two coats of primer and two coats of grey paint, fixing of 2nos double pole MCB of inside I/C and connector, Covering the I/C with G.I Sheet with help of suitable GI nut & bolt and refixing the pole with help of GI nut & bolt as per direction of EIC. |
| 4 | Supply and drawing of following sizes FR PVC insulated single core multistrand copper conductor in existing surface. |
| 5 | 2 x 2.5 sq mm + 1 x 1.5 sqmm |
| 6 | Supply and laying of size 04 core x 10sq.mm PVC insulated PVC sheathed armoured underground aluminium cable for power supply from Panel Board to street light poles including cost of materials, labour, T&P and transportation etc. complete as per direction of the E.I.C. (Make: Polycab/Havells/Glostar/KEI) Three Years On-Site Maintenance. |
| 7 | Supply and laying of size 04 core x 16 sq.mm PVC insulated PVC sheathed armoured underground aluminium cable for power supply from Pole to Panel Board including cost of materials, labour, T&P and transportation etc. complete as per direction of the E.I.C. (Make: POLY CAB/ Havells/ Glostar/ KEI) Three Years On-Site Maintenance. |
| 8 | Supply and laying of 50 mm dia HDPE Pipe inside the trench for laying of cable including cost of materials, labour, T&P and transportation as per direction of the Engineer-in-Charge. Three Years On-Site Maintenance. |
| 9 | Supply and fixing of 3 phase outdoor type panel board made of 16 SWG- C.R sheet of size 3'-0\\" x 2.'-0\\" x 1'-5\\" ( L x B x D) with epoxy grey powder coated. The panel board consisting of the following accessories. |
| 10 | (i) Neon Indicator - 3 nos. |
| 11 | (ii) Ring Copper Socket - 4 nos. |
| 12 | (iii) 3 phase Timer - 2 nos. |
| 13 | (iv) Toggle Switch - 1 no. |
| 14 | (v) 63 Amp 4 pole Contactor - 2 nos. |
| 15 | (vi) 3 phase 63 Amp 4 pole MCB-2 nos. |
| 16 | (vii) Stud Connector 4 way, 1 no. |
| 17 | (viii) 3 Phase Copper Bus bar - 4 nos. |
| 18 | (ix) Danger Board - 1 no. with complete wiring with 10sq.mm / 4sq.mm / 2.5sq.mm copper wire as per direction of the E.I.C. Three Years On-Site Maintenance. |
| 19 | Supply & Fixing of 300Watt LED Flood light made up of pressure die-cast Aluminium housing with toughened glass and high power LED's and secondary lenses with IP-66 protection. System efficacy > 110LPW 10KV SPD included. Make: Bajaj /Crompton /Havells /HPL /Wipro /K-Lite /Jaquar Sample to be produced before installation of fittings. Manufacture test certificate of fittings to be submitted after completion of the work satisfactorily. Three Years On-Site Maintenance. |
| 20 | Earthing with G.I earth pipe 3 meter long 40 mm dia ISI marked including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc with charcoal and salt as required. |
| 21 | Supply and laying 6 SWG G.I wires ISI marked at 0.5 meter below ground level for conductor earth elctrode including soldering etc. as required. Please Enable Macros to View BoQ information |