| 1 | Percentage BoQ BoQ_Ver3.0 Percentage Normal INR Only INR Select, At Par, Excess (+), Less (-) IOCL Tender Inviting Authority: Executive Engineer(E) PWD M-253 Name of Work:- RMO of electrical and mechanical installations on PWD roads in East District under M-253 New Delhi during 2026-27 (SH:- Replacement of damaged street light poles at Yamuna Bridge Vikas Marg and other associated work under Sub-Division M-2532) NIT No.:05/EE(E)/PWD M-253/2026-27 Estimated Cost:-27,44,909/- Name of the Bidder/ Bidding Firm / Company : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Sub Head Item Code / Make Quantity Units Estimated Rate inRs. P Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Rs. P TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Supply and erection of flange mounted hot dip Galvanized Octagonal Poles of 8 mtrs. height made from 3 mm thick HT Steel plate, having bottom dia of 130-135 mm. & top dia of 70 mm with base plate of size 200mm x 200mm x 16mm thick complete with connection window having flash cover with round sleeve at an approx.. height of 2 mtrs from the base for cable termination etc. on the existing cement concrete pedestal as required i/c supplying and fixing of the following accessories in connection window for cable termination: -a) 6 mm thick laminated / backalite sheet of suitable size- 1 Nob) 63 Amp 4 Way termination block- 1 No.c) 6 Amp 10 KA, SPMCB,'C' Characteristics Curve - 1 nos. |
| 3 | Supply and erection of flange mounted hot dip Galvanized Octagonal Poles of 10 Mtr. Height made from 3 mm thick HT Steel plate, having bottom dia of 175 mm. & top dia of 70 mm with base plate of size 275mm x 275mm x 16mm thick complete with connection window having flash cover with round sleeve at an approx.. height of 2 mtrs from the base for cable termination etc. on the existing cement concrete pedestal as required i/c supplying and fixing of the following accessories in connection window for cable termination: -a) 6 mm thick laminated / backalite sheet of suitable size- 1 Nob) 63 Amp 4 Way termination block- 1 No.c) 6 Amp 10 KA, SPMCB,'C' Characteristics Curve - 1 No |
| 4 | Construction of reinforced cement concrete pole foundation of size 650 mm (L) x 650 mm (W) and 1600 mm (D) Providing and laying in position M-20 (1:2:4) i/c excavation of earth, cantering & shuttering, providing & placing in position reinforcement TMT bars of 12 mm dia -1700 mm long (approx.)-8 nos. & reinforcement ring of cold twisted bar of 8 mm dia - 2800 mm (approx.) - 10 nos. (at 150 mm spacing), providing & positioning of 4 Nos. 20mm diameter x 750mm long MS anchor bolts with nuts & washers with suitable sized anchor plates, providing & placing of 1 m length 63 mm O.D. DWC HPDE pipe for cable entry & exit and providing & laying in position cement concrete of M-20 grade (1:2:4) etc complete as reqd. |
| 5 | Repairing of existing cement concrete pedestal to make it suitable for installation of new 10M G.I. poles i/c cutting of cement concrete in suitable depth as per site condition, welding of suitable M.S Plate having pole mounting bolts as per PCD of Pole with the existing foundation bolts with suitable strengthening arrangement, finishing of base with CC as per requirement at site etc complete as reqd. |
| 6 | Fabrication, Supplying & Fixing of Galvanized arm street light pole bracket (single/double/triple over hang / ring type) with tightening bolt & other required accessories as per approved design etc. complete as reqd. |
| 7 | Supplying and drawing following sizes of PVC insulated copper conductor multicore cable in the existing poles and bracket from cable termination connector to the fitting i/c providing suitable copper lugs connections etc. as reqd i/c dismantling of old damaged cable & credit for old dismantled cable as and where basis etc as required.3 core x 1.5 sq. mm |
| 8 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench / surface, complete as required.63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 9 | Supplying and Laying of one number PVC insulated and PVC sheathed / XLPE aluminium conductor armoured power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe etc complete as reqd.4x 16 sq.mm |
| 10 | Fabrication, supplying and installation of cable junction box IP66 weather proof for outdoor installations with knockouts for cable entry with outside dimensions as 270x225x135 single door (Hinged -R) and having following accessories mounted inside the junction box with making suitable arrangement for installation on 8/10 mtr streetlight pole with MS U Clamp , drilling small hole in existing streetlight pole for pole wiring, connection, testing etc complete as required. (i) 6-32Amp SP MCB -1No(ii) 63 Amp 4 Way termination block- 1 No. |
| 11 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required |
| 12 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required |
| 13 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 14 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy >135 lm/Watt). Supplying, installation, Testing & Commissioning of Street light LED fixture, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP66,IK-10, CRI >80 , under voltage and over voltage protection, EMIEMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).150 watt |
| 15 | Supplying, Installation, testing & commissioning of outdoor type front openable double door compartmentalized cubical Feeder Pillar of suitable size & depth duly fabricated with 2 mm thick CRCA sheet steel with heavy duty locking arrangement, dust & vermin proof duly powder coated in approved shade complete with 4 strip aluminium bus bar of 200 Amp. capacity of high conductivity with DMC/ SMC bus bar supports, two nos. earth studs, MV danger notice plate, power & control wiring, connection, interconnections etc. and fixing the same on MS angle iron frame of suitable size duly fabricated with 50mm. x 50mm. x 6mm. (NS) having 4 nos 90 cm long legs out of which 45 cm duly grouted in cement concrete 1:2:4 (1 cement : 2 sand : 4 stone aggregate 20mm) complete with following switchgears & accessories therein i/c dismantling the existing worn-out panel & credit for old panel under buy back, making good the damages etc complete as reqd.INCOMER:i) 1 No. 125 Amp, 25KA . 415 Volts TP MCCB ii) RYB LED phase indication lamps with protection MCB's- 1 Setiii) 95 Amp. TP Power contactor AC-3 rating with NO NC aux contacts- 1 No.iv) 24 Hr. digital Timer with Auto/Manual switch- 1 No.v) Space for installation of BSES energy meter- 1 No. OUTGOINGS: i) 63 Amps 415 Volts TP MCCB of 16 KA (Ics = Icu = 100%)- 4 Nos. |
| 16 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete with hinges, sliding door bolt & godown lock on the openable part of structure etc as reqd. |
| 17 | Credit for old worn out dismantle material under buy back including dismantling from site and making good the damages etc. complete as reqd.Street light Poles 8 / 10 Mtr with accessories (Assorted) |
| 18 | Street light Fitting (Assorted) |
| 19 | Al conductor armoured / unarmoured cable (Assorted) Total in Figures 2744909.0 167350.0 Twenty Seven Lakh Forty Four Thousand Nine Hundred & Nine Only Quoted Rate in Figures Select 0.0 0.0 INR Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |