| 1 | Supply and fixing including Taking out and removing old unserviceable XPLE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 50 Sqmm 3.5 core in trenches,through pipe,under culvert or in air complete all as directed including using existing Cable cushioning and cable protection complete as directed. |
| 2 | Replacement of Earthing complete with GI earth plate 60cmx60cmx6mm thick electrode and 25X4MM GI strip as earthing lead. buried directly in ground ( earth pit not less then 2.25 metres deep below ground level ) with top edge of the plate not less then 1.5 metres below normal ground level. connected to GI wire earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No. 5 and incl earth work, PCC pit and RCC cover, watering pipe 20 mm dia light grade, funnel, wire mesh, protection pipe 15 mm dia light grade up to 7.5 mtr length of earth wire, charcoal dust and salt etc and connected to earthing test point all as specified or directed and testing complete all as specified. (Earthing for poles for earth continuity wire) |
| 3 | Supply and replacement of MCCB of capacity 100 Amp, 35KA, 4 Pole, 415Volts grade. |
| 4 | Supply, fixing & laying in repair GI pipe light grade 50mm bore in trench, under floor, wall and on pole for cable protection. |
| 5 | Dismantling and taking down old unserviceable rusted meter box complete all as speacied and as directed. |
| 6 | S & F sheet moulded compund(smc) meter box fire retardant type of size not less than 580mmx500mmx250mm,wall thickness 2.5mm (base & lid) to enclouse 04 nos single phase electric meters with hinged type front operated door having transparent acrylic sheet and proper locking arrangement and flush mounting in wall including refixing the serviceable electric meters dismantling and making electrical connections including cleaning of disturbed areas and making good the disturbed surface and matching with existing specifications complete all as specified and directed.Make:-Hensal,Retail,sintex |
| 7 | S & F of sheet metal enclosures distribution boards, double door ,VTPN, 415 volts 4 ways (one incoming three phase & twelve out goings single phase )for MCCB & MCB,s comprising three phase four wire copper strip bus bar of appropriate capacity complete all as specified and directed and comprising of the following a) MCCB FOUR POLE 100 AMPS AC 415 VOLTS 16 KA=01 NO (for incoming ) (b) MCB SP 63 amps = 04 Nos (for outgoings) . ( Note :- (i)The DB shall be VTPN series of Make : Schneider ,cat part no: A9HVD04L or equivalent make of L&T/ ABB/Legrand . (ii) The DB shall be flush fixed and making good the disturbed surface matching with existing specifications shall be part of job at no extra cost.(iii)connection of the MCCBs/ MCBs with cable shall be made through appropriate size pin /bottle type thimble properly crimped.(iv) All the vacant holes of the DB shall be provided with blank plates of appropriate size. (v) Double continuous earth wire shall be provided for each three phase DB from earthing mains dolly. (vi) cutting chasing shall be part of job at no extra cost . |
| 8 | Supply and fixing for MCB SPN 63 amps 240 Volt 'B' series complete all as specified and as directed. |
| 9 | Supply and fixing for MCB SPN 40 amps 240 Volt 'C' series complete all as specified and as directed. |
| 10 | Supply and fixing for MCB SP 6 to 32 amps 240 Volt 'B' series complete all as specified and as directed. |
| 11 | Taking down the unservicable /burnt sub main wiring from wooden batten and Supply & fixing for submain wiring in and including PVC conduit 1.8 mm thick ,32 mm dia with two run of PVC insulated, unsheathed multistranded copper conductor of 10 sqmm(FRLS) and one run of PVC insulated,unsheathed multistranded copper conductor 10 sqmm (green in colour) for earth continuity conductor and connected to common earth dolly with thimble etc, complete all as specified and directed. (Two run of 10 sqmm plus one run 10 sqmm of earth wire will be measured as 1RM) Note: (a) Insulation test of point wiring (b) colour coding is to be maintained .(Ph-Red, N-Black,Earth- Green) |
| 12 | Taking down old unserviceable aluminium point wiring (light, fan, socket , power socket and bulk head fittings) from PVC/matelic conduit,on surface wiring, on wooden batten/casings & caping complete, including fixture and fittings such as switches, ceiling roses,pendents holder, regulators, sockets and defective main switch/DB/MCB/Metal plug etc. by unscrewing carefully from boards etc complete all as specfied and directed. |
| 13 | M & L for modular point wiring for one light/one fan controlled by one switch with 1.5 sqmm single core PVC insulated unsheathed multistranded copper conductor (FRLS) with in and including PVC concealed conduit having thickness not less than 1.8 mm thick (ISI Marked) with all accessories including suitable modular plate (Inner and outer) and modular metalic boxes of suitable sizes (for mounting switches/sockets/regulators etc) including 1.5 sqmm single core PVC insulated unsheathed multistranded copper conductor (FRLS) as earth continuity conductor connected to common earth dolly in and including cutting chiseling for concealed piping and making good disturbed surface area and white wash /colour wash to matching with the existing colour and all as specified and directed.Note: (a) Insulation test of point wiring (b) colour coding is to be maintained .(Ph-Red, N-Black, Half -Yellgulators/ ceiling roses etc.)ow, Earth- Green) |
| 14 | All as per item no 13 above but for One 5 Amp modular socket outlet on independent board. |
| 15 | All as per item no 13 above but for One 5 Amp modular socket outlet on same board. |
| 16 | M & L for modular point wiring for one light/one fan controlled by one switch with 2.5 sqmm single core PVC insulated unsheathed multistranded copper conductor (FRLS) with in and including PVC concealed conduit having thickness not less than 1.8 mm thick (ISI Marked) with all accessories including suitable modular plate (Inner and outer) and modular metalic boxes of suitable sizes (for mounting switches/sockets/regulators etc) including 2.5 sqmm single core PVC insulated unsheathed multistranded copper conductor (FRLS) as earth continuity conductor connected to common earth dolly in and including cutting chiseling for concealed piping and making good disturbed surface area and white wash /colour wash to matching with the existing colour and all as specified and directed.Note: (a) Insulation test of point wiring (b) colour coding is to be maintained .(Ph-Red, N-Black, Half -Yellgulators/ ceiling roses etc.)ow, Earth- Green) |
| 17 | M & L for replacement of existing un-serviceable switch piano with modular switch 1 way 6A, 1 module ISI marked complete all as specified and directed. |
| 18 | M & L for replacement of existing un-serviceable switch piano with modular switch 1 way 16A, 1 module ISI marked complete all as specified and directed. |
| 19 | M & L for replacement of existing un-serviceable socket with modular socket 16 amp AC 230 volts ,2 module ISI marked complete all as specified and directed. |
| 20 | M & L for replacement of existing un-serviceable socket with modular socket 6 amp AC 230 volts ,2 module ISI marked complete all as specified and directed. |
| 21 | Supply and fixing modular fan regulator step type120W-2module |
| 22 | M & L for ceiling rose 65 x 50mm three terminals complete all as specified and directed. |
| 23 | S & F for lamp holder/batton holder/angle holder insulated body with back bakelite plate suitable for batten fittings. |
| 24 | M & L for Inverter LED batten with square profile and polycarbonate channel,lithium Ion battery with charging time 8 hours to 10 hours and back up time upto 4 hours of capacity 20 watt 230 volt,complete with all accessories internally pre wired and including connecting up with three core twisted flexible copper conductor cable with suitable size mounting on rectangular PVC black complete all as specified and directed, |
| 25 | S&F LED Tube Light 20 watt LUMILINE Basic all purpose surface and wall mounted LED batten with polycarbonate housing and integrated electronic driver. complete inicluding taking down old one as directed . |
| 26 | Supply and fixing sheet metal enclousre for DBs when MCB to be used double door powder coated factory made flush fixed complete with 200 amps rated bus bar 240 volts single phase 12 ways complete all as specified and directed. |
| 27 | Supply and fixing sheet metal enclousre for DBs when MCB to be used double door powder coated factory made flush fixed complete with 200 amps rated bus bar 240 volts single phase 08 ways complete all as specified and directed. |
| 28 | Excavation in trenches in soft / loose soil not exc 1.5 mtr wide and not exe 1.5mtr deep and getting out complete, all as specified. |
| 29 | Returning filling in including spreading, leveling, watering and well ramming to a layer not exceeding 25cm all as directed. |
| 30 | Removal of excavated material n.exe 50mtr and depositing where directed at a level not exe 1.5 mtr above the starting point. |
| 31 | Sand cushioning to under ground cable using fine sand (8 cm before & 15 cm after laying of cable) complete all as specified. |
| 32 | Brick sub class 'B' of standard size for protection of cable, brick laid across the cable all as specified. |
| 33 | Taking down carefully 1200/1400mm sweep ceiling fan of any make from the hook and carry to the wksp including rehanging after repair the same at existing position after cleaning dirt,oiling, greasing of fan complete all as specified and directed by Engr-in-Charge . NOTE :- Total service time from taking down to rehanging must not exceed 3 Days. APenalty of Rs 200.00 per fan per day ( or part there of) upto a maximum of Rs 2000.00 shall be imposed in case work not excueted within specified time. |
| 34 | All as per serial item No-33 above but for Exhaust fan 225mm to 450mm sweep. |
| 35 | All as per serial item No-33 above but for pedestall/wall mounting fan of any type and any description. |
| 36 | M&L for Strip opening of ceiling fan 1200 sweep and carrying out rewinding with proper grade/guage super enamelled copper winding wire so as to achieve original specifications i.e current rating and RPM including replacement of rubber real ,nut bolt,clamp as required and reasembling etc complete all as specified and directed by Engr-in-Charge. Note :- RPM test of ceiling fan with suitable tachometer will be done in the presence of Engineer -in -Charge. |
| 37 | All as per srl item No.36 above but ceiling fan of 1400mm sweep. Note :- RPM test of ceiling fan with suitable tachometer will be done in the presence of Engineer -in -Charge. |
| 38 | All as per serial item No-36 above but for wall mounting/pedestal fan of any type and any description. |
| 39 | Material and labour for re-winding of exhaust fan/bracket fans/wall mounting fans/pedestal fans 225mm to 300 mm sweep after strip opening of motor with proper grade/guage of super enamelled copper wiring so as to achieve original specifications i.e current rating and RPM including all insulating materials, bushes etc re-assembling complete all as specified and directed by Engr-in-Charge. Note :-RPM test of ceiling fan with suitable tachometer will be done in the presence of Engineer -in -Charge. |
| 40 | Material and labour for re-winding of exhaust fan/bracket fans/wall mounting fans/pedestal fans of 450 mm sweep after strip opening of motor with proper grade/guage of super enamelled copper wiring so as to achieve original specifications i.e current rating and RPM including all insulating materials, bushes etc re-assembling complete all as specified and directed by Engr-in-Charge. Note :-RPM test of ceiling fan with suitable tachometer will be done in the presence of Engineer -in -Charge. |
| 41 | Supply & fixing ball bearings suitable for ceiling fans of size 6201 complete all as specified and directed by Engr-in-Charge complete ,Make:SKF or technocommerically equivalent make of NBC/URB. |
| 42 | All as per srl item no 41 but of size 6202 complete, Make: SKF or technocommerically equivalent make of NBC/URB. |
| 43 | All as per srl item no 41 but of size 6203 complete, Make: SKF or technocommerically equivalent make of NBC/URB. |
| 44 | All as per srl item no 41 but of size 6204 complete, Make: SKF or technocommerically equivalent make of NBC/URB. |
| 45 | M and L for Replacement of PVC plug top 5 Amp, 240Volts (ISI marked) complete all as specified and directed make Anchor /SSK /Plaza /Havells |
| 46 | Taking out existing worn out /defective gun metal bush and material & labour for new gun-metal bush to the ceiling fans of any size/make incl reassembling and testing etc complete all as specified and directed by Engr-in-Charge. |
| 47 | Taking out existing defective/worn out condenser any size/make and material and labour for condensor of capacity 2.5 mfd ,220 Volts including making connections etc complete all as specified and directed by Engr-in-Charge, |
| 48 | All as per srl item No.47 here-in-before but of capacity 3.15 mfd capacity. |
| 49 | Taking out defective fan regulator any type and make and supply & fix electronic step type fan regulator 5 stage speed variation ISI marked including making connection etc and cutting to the required size of 3 mm thick bakelite sheet where required complete all as specified and directed, |
| 50 | M&L for Replacement old damaged/ unserviceable connection wire with new flexible, PVC insulated, multi-stranded, copper wire, 0.75 Sqmm, twine core, FRLS, complete all as specified and directed. |
| 51 | Taking out worn out/cracked canopy and supply & fixing canopy with screws to the ceiling fans of any size/make etc complete. (Set of 2 pieces) |
| 52 | M&L for Replacement old damaged/ unserviceable/ rusted nut, bolt with new nut, bolt of 10mm dia and 50mm long, mild steel including spilt mild steel safety pin, complete all as specified and directed |
| 53 | M&L for Replacement old damaged/ unserviceable ceiling fan hanging clamp/ assembly with new hanging clamp/ assembly, mild steel including rubber reel, complete all as specified and directed |
| 54 | M and L for lathe work/polishing/greasing and fixed new ball bearing in ceiling fan/exhaust fan complete all as specified and directed |
| 55 | M & L For meaking Hole for exhaust fan 300 mm sweep complete re plastring and meaking Good as per existing surface. |
| 56 | Supply and fix in replacement exhaust fan made of sturdy engineering plastic complete with lovers shutter,1200 rpm,300 mm sweep voltage 230v,50 HZ |
| 57 | Note:- The contract sum shall be arrived at after deduction of amount of Sch of credit. Please Enable Macros to View BoQ information |