| 1 | Supply Portion |
| 2 | Supply of three bolted type PG clamp made of Alu alloy LM-6 suitable for panther to panther conductor. |
| 3 | Supply of four bolted type PG clamp made of Alu alloy LM-6 having 04 nos bolts suitable for moose to panther conductor. |
| 4 | Supply of junction box suitable for 145 KV CT having teriminal connectors and complete in all respect as per std technical specifications. |
| 5 | Supply of junction box suitable for 145 KV PT having teriminal connectors and complete in all respect as per Std technical specifications. |
| 6 | Supply of 145 KV isolator clamp made of Alu LM-6 alloy suitable for ACSR panther as per sample. |
| 7 | Supply of 145 KV CT clamp made of Alu LM-6 alloy suitable for ACSR panther conductor. |
| 8 | Supply of 145 KV CB clamp made of Alu LM-6 alloy suitable for ACSR panther conductor. |
| 9 | Supply of 145 KV PT clamp made of Alu LM-6 alloy suitable for ACSR panther conductor. |
| 10 | Supply of 145 KV LA clamp made of Alu LM-6 alloy suitable for ACSR panther conductor. |
| 11 | Supply of 145 KV end termination clamp made of Alu LM-6 alloy suitable for ACSR panther conductor as per sample. |
| 12 | Supply of Perforated Cable Trays width 150 mm |
| 13 | Supply of single tension gun fittings suitable for ACSR panther conductor along with all associated accessories. |
| 14 | Supply of 40mm dia MS electrodes of 3 meter length. |
| 15 | Portable AFF mechanical foam type Fire Extinguisher complete with initial charge hose pipe and all other accessories and fittings as per IS 1024 trolley mounted 45/50 lit. cap. |
| 16 | Fire extinguisher carbon dioxide as per IS Specn. No. 2878/198622.5 Kg. |
| 17 | Fire extinguisher carbon dioxide as per IS Specn. No. 2878/19869 Kg. |
| 18 | Fire extinguisher carbon dioxide as per IS Specn. No. 2878/19864.5 Kg. |
| 19 | Supply of LED Flood luminariestype FL-1 light 150 W as per technical specification of some standard make as per sample. |
| 20 | Erection of main structure including all allied works complete in all respect. department shall provide each and every nuts and bolts of the structure. the work shall be strictly carried out as per drawing and technical specification. |
| 21 | Erection of aux structure including all allied works complete in all respect. Department shall provide all material including nuts and bolts of the structure. The work shall be strictly carried out as per drawing and technical specification. |
| 22 | Erection of equipments as per instruction manual and technical specification including shifting of material equipment from store to erection site including all other associated work with the help of crane which will be provided by contractor at his own cost for completion of the job satisfactorily. |
| 23 | 145 KV CB WITH STRUCTURE |
| 24 | 145 KV BUS ISOLATOR |
| 25 | 145 KV LINE ISOLATOR |
| 26 | 145 KV CTs |
| 27 | 145 KV PTs |
| 28 | 120 KV LAs |
| 29 | 145 KV CT JUNCTION BOX |
| 30 | 145 KV PT JUNCTION BOX |
| 31 | 132 KV DISTANCE PROTECTION PANEL |
| 32 | Interconnection of equipments with specified conductor with 132 KV main bus including cutting, bending of conductor and jumpering, clamping as per drawing and technical specification to complete the 132 KV bay in all respect. |
| 33 | Stringing and proper sagging of new overhead 132 KV Jack bus of three phases with ACSR panther conductor for approx 12 mtr span. The work involves cutting of conductor, making of busbar of suitable length, fitting of tension fittings, hoisting of 70/120 KN disc insulator etc and stringing. All material shall be supplied bybthe department free of cost and work also include shifting all material from store to site in switchyard and all other associated works to complete the job satisfactorily. |
| 34 | Earthing of substation structure and various equipments and cable racks with etc. with already laid earthmat laid 800 mm below ground by various size MS flat including excavation and backfilling of earth after completion of work, straightening, bending, cutting, welding and drilling holes including painting of MS flat with one coat of red oxide and two coat of bus green paint above ground and in trenches and one coat of red oxide and two coat of black bituminous paint of best quality on all underground joints for proper completion of work. |
| 35 | 25x6mm |
| 36 | 50x6mm |
| 37 | 75x10mm |
| 38 | Laying and dressing of control cable in trenches after removal of trench covers as per cable schedule including clamping with 25x3 mm Al strip and GI nut and bolts including cutting, peeling of the control cable. |
| 39 | 2x2.5 sqmm |
| 40 | 4x2.5 sqmm |
| 41 | 10x2.5 sqmm |
| 42 | Termination of cables as laid above as per cable schedule (provided by contractor) including making necessary holes in panel base plate or junction box as per site requirement including fixing of cable gland of appropriate size. Supply and fixing ferrules on each core of cable and its termination and other associated work to complete the job satisfactorily. (Glands will be provided by department free of cost.) |
| 43 | Earthing of 132 KV LAs with 75x10 mm MS flat after making rectangular configuration along with six nos (03 meter length) 40 mm dia MS electrodes as per drawing and technical specifications. Work includes fabrication of 3 meter long electrodes with MS rod having 150 mm long conical shape. |
| 44 | Dismantling of existing capacitor bank structure along with dismantling of associated busbar and substation structure and fencing (excluding civil dismantling work). Work also includes shifting of material from switchyard to substation store as per directions of supervising engineer. Please Enable Macros to View BoQ information |