| 1 | Supply of XLPE insulated FRLS heavy duty power cable conforming IS-7098 (Part-1) 1988, 1100 Volt grade, 2/3/4/8/10/12 coreISI marked with copper stranded/solid conductor. Armoured 4core x4sq.mm cable |
| 2 | Laying of one number armoured / unarmoured powercable1:1KVgradeof size not exceeding 25 sq. mm in the existing RCC hume/stoneware/G.I. pipe/ DWCPipe/ surface in existing trenchas required |
| 3 | Supplying and fixing heavy duty cable gland forP.V.C. insulated armoured cable with brass washer, rubber ringcomplete erected with cable and lead connection etc. as per specification complete. Gland size 28mm for 3/4 x 16 sq. mm |
| 4 | Supplying of ISI marked and approved make of moulded case circuit breaker(MCCB)suitable for 3phase &N,4 pole ,50Hz, 415Volts, (Ics=100%Icu)AC supply with microprocessor release with inbuilt instantaneous protection & variable trip class 7.2 Ir &6 Ir having respective breaking capacity (KA) at 415Volts cited against their range standard conforming to IS/IEC609472 . MCCB25kAcurrent rating- 40&100Amps 4Pole& micro-processor release, over load40%-100% x In.& short circuit 1.5 - 8 x Ir. adjustable. 63 Amp for each high mast |
| 5 | Supplying and fixing of analog time switch for automatic ON OFF street light of approved make in existing LT panel including connections etc. as required as per specification |
| 6 | Supplying and fixing ofMCB/Connector mounting Corrosion proof mild steel DIN Rail of thickness 2.5mm to 4mm in existing box as required as per specification |
| 7 | Supply and fixing of MH lamp single ended type ISI marked of approved make as required as per specification 400 Watt |
| 8 | Supply of non integral flood fittings of 2x400watt MH asymmercial 6 folld light type BGENF22 (without lamp) |
| 9 | Supplying and fixing of 4Pole epoxy connector nut& bolt type, 30Amp. 500Volt. In existing box as required as per specification: |
| 10 | Supply and fixing of geared induction motor for Reverse /forward uplifting of high mast light 20 mtr height of following specification . power =2 HP , gearbox output of = 85 RPM . Including gear box ,induction motor of approved make ,transportation , fixing , trail and testing etc complete job. |
| 11 | Re-wiring and fixing of high mast panal mountings including dismentaling old burnout panel mounting ,cleaning , rewiring & fixing all mountings, fixing MH lamp integrals etc complete work including wiring material with testing . All work complete. |
| 12 | Main fuse HRC fuse (DIN) 32 Amp type - 3NA78120RC size 000 seimens make |
| 13 | controlling fuse HRC fuse (DIN) 10 Amp type - 3NA78030RC size 000 seimens make |
| 14 | Fuse bases (DIN) size 000 type- 3NH3030-0RC siemens make |
| 15 | LV HRC contact covers size 000 type - 3NX3115 |
| 16 | Seimens 3-pole Power Contactor , with an AC coil ,rated for 40 A ,415 V Type 3RT2028-1A..08KA0 Size S0 |
| 17 | Seimens 3-pole Power Contactor , with an AC coil ,rated for 16 A ,415 V , 1NO Type 3RT2018-1A..18K Size S00 (for reverse forward motor operation) |
| 18 | S00 - Mechanical Interlock & Installation kit for reversing contactors . Each kit contains: Mechanical interlock, 2 Connecting clips for 2 contactors, wiring modules on the top & bottom . Type 3RA2913-2AA1 |
| 19 | Auxiliary Contact Blocks (S0) size -S0 , 2NO+2NC type -3RH2911-1HA22 |
| 20 | Auxiliary Contact Blocks (S00) size -S00 , 1NO type 3RH2911-1HA10 |
| 21 | Thermal overload relay (3RU) size S0 ,Set current value of the inverse- time delayed overload release A 20 -25 Amp . type 3RU2121-4DB00-8K |
| 22 | Normal opaque push button - Green with 1NO contact block, ”START” + Normal opaque push button - Red with 1NC contact block, “STOP” + Normal opaque push button - Black with 1NO contact block, “REVERSE” in metal enclosure code :3SB5803-8AH3 Please Enable Macros to View BoQ information |