Name of Work:- PROVN OF MAIN STANDBY HT 11 KV UNDER GROUND CABLE 95 SQMM AND CONNECTED WORKS AT 2003 STN UNDER GE (AF) GURGAON
Sl. No.
Item Description
1
Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom suface to required level complete all as specified and directed by Engineer- in- Charge.
2
Returning filling in,. Including spreading, levelling,. Watering and well ramming soil in layers not exceeding 25 cm thick complete all as specified and directed by Engineer- in- Charge.
3
Removing excavated material (ie soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point complete all as specified and directed by Engineer- in- Charge.
4
M & L for dry washed and screened sand cushioning to underground cables with 8cm thick before laying of cables and 15cm thick after laying and stretching of cable all as specified and directed .Note : Compacted Thickness 18 cm shall be considered for measurement and payment purpose.
5
Supply and laying factory made unreinforced precast concrete cable cover class HV, type -I flat size 300mmx180mmx40mm laid in trenches over underground cables complete all as specified and directed by Engineer- in- Charge.
6
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade 95 Sqmm 3 core complete all as specified and directed by Engineer- in- Charge.
7
Supply and fix cable jointing kit for 11 KV grade cable for in door termination, Cold shrink type, joint complete with jointing material and accessories suitable for3 core XLPE, armoured, Al conductor cable of size 95 sqmm complete all as specified and directed by Engineer- in- Charge.
8
M&L Boring road crossing of size 100 mm dia at suitable depth not less than 1 mtr by using machiniery/ Equipments complete without damaging surfaces for passing pipes/cables etc complete all as specified and directed by Engineer- in- Charge.
9
Material & labour for 80 mm dia GI steel tubing light grade for protection of cable/ earth continuty conductor fixed to poles/ walls/ roof or laid in floors, road, crossing or ducts fixed with clamps , bolts nuts and wahser etc complete all as specified and directed by Engineer- in- Charge.
10
M&L HT cable route marker / HT joint marker made out of Jodhpur stone of size 250 mm widthx150 mm depth x900mm height size with top oval shaped, engraved with 'HT cable' duly painted with approved colour with writing letter for both side, all as specified and directed.Route Marker shall be burried in ground upto a depth of 45cm below the natural Ground Level complete all as specified and directed by Engineer- in- Charge. Please Enable Macros to View BoQ information