| 1 | 1.0) Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. (a) Group C |
| 2 | 2.0) Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. |
| 3 | 2.1) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 4 | 2.2) 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 5 | 3.0) Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 6 | 4.0) Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 7 | 4.1) 5/6 A switch |
| 8 | 4.2) 15/16 A switch |
| 9 | 4.3) 3 pin 5/6 A socket outlet |
| 10 | 4.4) 6 pin 15/16 A socket outlet |
| 11 | 5.0) Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 12 | 5.1) 6 way , Double door |
| 13 | 5.2) 8 way , Double door |
| 14 | 5.3) 12 way , Double door |
| 15 | 5.4) 16 way, Double door |
| 16 | 6.0) Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 17 | 6.1) Single pole |
| 18 | 6.2) Double pole |
| 19 | 7.0) Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 20 | 7.1) 20 mm |
| 21 | 8.0) Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 22 | 8.1) 3 x 1.5 sq. mm |
| 23 | 8.2) 3 x 2.5 sq. mm |
| 24 | 8.3) 3 x 4 sq. Mm |
| 25 | 9.0) Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. |
| 26 | 9.1) 1 or 2 Module (75mmX75mm) |
| 27 | 9.2) 4 Module (125mmX75mm) |
| 28 | 9.3) 6 Module (200mmX75mm) |
| 29 | 9.4) 8 Module (125mmX125mm) |
| 30 | 9.5) 12 Module (200mmX150mm) |
| 31 | 10.0) Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 32 | 11.0) Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 33 | 12.0) Supplying and fixing single pole blanking plate in theexisting MCB DB complete etc. as required. |
| 34 | 13.0) Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. (i) 63A |
| 35 | 14.0) Supply and Fixing of 48 mm dia x 1 Mtr Long GI Pipe bracket for mounting of LED street light fitting on wall/pole including bending the pipe to required shape, 2 Nos of 25x5 mm flat iron clamp with nuts, bolts& washer, painting the flat iron clamp with primer and finish paint, etc. as required. |
| 36 | 15.0) Brush Less Direct Current (BLDC) Fan without RemoteSupply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 37 | 16.0) Numbering of ceiling fan/ exhaust fan/ fluorescent fittings as required. |
| 38 | 17.0) LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥120 <135 lm/Watt)Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report,CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).(i) 45 watt |
| 39 | 18.0) LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥120 and <135 lm/Watt).Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3 2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).(i) 100 W |
| 40 | 19.0) Supplying, Installation, Testing & Commissioning of 2C X 6 Sq.mm. size of 1.1 KV grade multicore aluminium conductor XLPE insulated and PVC sheathed armoured cable as per IS : 7098:1988 with upto date amendments. |
| 41 | 20.0) Supply & Replacement of Heavy Duty Exhaust Fans of size 12\\" (300 mm) 1 Phase 900 rpm i/c connections,making good the damages ,iron angle & painting with screws,nuts & bolts etc. complete as required. |
| 42 | 21.0) Supply & Replacement of Heavy Duty Exhaust Fans of size 15\\" (380 mm) 1 Phase 900 rpm i/c connections,making good the damages ,iron angle & painting with screws,nuts & bolts etc. complete as required. |
| 43 | 22.0) Supply & Replacement of Heavy Duty Exhaust Fans of size 18\\" (450 mm) 1 Phase 900 rpm ( i/c connections,making good the damages ,iron angle & painting with screws,nuts & bolts etc. complete as required. |
| 44 | 23.0) Installation, Testing and Commissioning of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. As required.(a) Upto 450 mm sweep |
| 45 | 24.0) Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. (i) Upto 35 sq. mm (clamped with 1mm thick saddle) Please Enable Macros to View BoQ information |