| 1 | Provision of Electrical inquiry by providing one semi skilled manpower who will note down the complaints, forwarding the complaints to the maintenance perssonel, perusing the same for fast resolution of complaint and recording of compliance after attending the same i/c Monitoring of AFDFD system and attending the minor complaint as per direction of Engineer in charge along with availability of required tools etc.complete as reqd.Note : Mininmum Wages with all the statutary requirement shall be ensured. |
| 2 | Replacement/Provision of following material for repairing & attending petty maintenance work by engaging adequate manpower as required at site for repairing of HT/LT panels, capacitor panels, existing wiring work like fluorescent fitting, ceiling fans, wall/pedestal fans, Main board, Sub Main board, Compound Lighting, water pumps & switchgears, Geysers, Split AC, water coolers, etc i/c dismantling, connection, fixing, testing etc as required |
| 3 | 5/6A Piano type Switches |
| 4 | 15/16A Piano type Switches |
| 5 | 5/6A 3/5 pin piano type Socket outlet |
| 6 | 15/16A 3/6 pin piano type Socket outlet |
| 7 | industrial Plug Top 20A |
| 8 | Metal clad Industrial Socket 20 A |
| 9 | Capacitor - 2.5 MFD/3.5 MFD |
| 10 | Fan regulator - electronic step type - 150W |
| 11 | 3 mm thick hylem sheet |
| 12 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS/HFFR PVC insulated copper conductor single core cable etc as required. |
| 13 | Group \\"B |
| 14 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable and 1.5 sq.mm. FRLS/HFFR PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/pvc conduit including dismantling as required. |
| 15 | Group 'B' |
| 16 | Wiring for light/ power plug with 2X4 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No 4 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable for loop earthing as required. |
| 17 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 18 | 3 x 1.5 sq. mm |
| 19 | 6 x 1.5 sq. mm |
| 20 | 3 x 2.5 sq. mm |
| 21 | 3 x 4 sq. mm |
| 22 | 6 x 4 sq. mm |
| 23 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required |
| 24 | 20 mm |
| 25 | 25 mm |
| 26 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 27 | 5/6 amps switch |
| 28 | 5/6 amps socket |
| 29 | 15/16 A switch |
| 30 | 6 pin 15/16 A socket outlet |
| 31 | 2 way 5/6 A switch |
| 32 | Bell push |
| 33 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. |
| 34 | 1 or 2 Module (75mmX75mm) |
| 35 | 3 Module (100x75mm) |
| 36 | 6 Module (200mmX75mm) |
| 37 | 8 Module (125mmX125mm) |
| 38 | 12 Module (200mmX150mm) |
| 39 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 40 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required |
| 41 | Supplying and fixing brass batten/ angle holder including connection etc. as required. |
| 42 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 43 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. |
| 44 | Providing and fixing plain 16/0.20mm (0.50sqmm) twin flat flexible, FRLS PVC insulated, copper conductor cable, in PVC sleeve of suitable size on the floor/ wall, or side of the table/ door etc. as required |
| 45 | Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required |
| 46 | 4 Pair |
| 47 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 48 | 2 + 6 way, Double door |
| 49 | 2 + 12 way, Double door |
| 50 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 51 | 4 way (4 + 12), Double door |
| 52 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 53 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 54 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 55 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 56 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with onnections, testing and commissioning etc. as required |
| 57 | 100 A |
| 58 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 59 | Single pole |
| 60 | Double pole |
| 61 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \\"C\\" curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 62 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 63 | Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required |
| 64 | Above 4.5 metre and upto 6.5 metre |
| 65 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 66 | Upto 35 sq. mm |
| 67 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required |
| 68 | Supply and fixing of following type exhaust/ wall/ ceiling/ pedestal fans suitable for operation on 230V, 50 Hz single phase AC Supply i/c dismentaling/ refixing, minor civil works if reqd. making connection testing and commissioning etc complete as reqd. (Make: Crompton/ Bajaj/ Almonard/ Havells/ Usha/Orient) |
| 69 | 150 mm sweep axial high speed exhaust fan |
| 70 | 300 mm sweep heavy duty exhaust fan |
| 71 | 400 mm sweep wall fan |
| 72 | 200 mm sweep ventilation fan with front louvers |
| 73 | Supplying and fixing of weather proof PVC Pole box of size 200 mm X 250 mm X 100 mm deep (Nominal), including providing and fixing Din Rail, 01 No SPMCB,01 No 4 way Neutral link,01 No heavy duty MS clamp, fixed with the help of nut &Bolt washer, making connection etc complete as reqd.(Make - M/S Sintax or SS Make) |
| 74 | Supply of fallowing size of PVC insulated, PVC sheathed copper conductor armoured cable of 1.1KV Grade i/c making connections, testing etc complete as reqd. (ISI Make) |
| 75 | 3 x 1.5 Sq mm |
| 76 | 3 x 4 Sq mm |
| 77 | Supplying and fixing of 50mm dia G.I. pipe (medium class) for 4.5 mtr pole from foundation for street light i/c provide of 40mm GI pole bend on top for fixing of compound light with welding or clamp etc as required |
| 78 | Replacement and fixing following accessiries on the existing switch box/ cover/ on wall including connections etc. as reqd. |
| 79 | 15/16 Amp. Pin Plug Top |
| 80 | 25 mm PVC flexible pipe |
| 81 | Providing and fixing of fallowing wattage B22 LED bulb etc complte as reqd.(Make: Havells/ Bajaj/ Philips) |
| 82 | 9 W LED bulb |
| 83 | Providing and fixing of following electrical item suitable for 230 v, 50 Hz single phase supply i/c connection etc complete as reqd.(Make: Havells/ Anchor/Bajaj/Cona) |
| 84 | 15/16 Amp Combo box with 1 Nos. switch socket |
| 85 | Supplying and fixing LED bulkhead suitable for operation on 220 volt 50 Hz A.C. supply i/c connection, wiring, fixing on of wall etc. complete as reqd. |
| 86 | 12 W LED bulkhead |
| 87 | LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS: 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI ≥80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K/ 5700°K /6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq. mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 88 | 36 watt |
| 89 | Supplying and fixing of 32 mm dia X 2.00 metres long G.I. pipe (medium class) bracket for mounting of fluorescent / HPMV / HPSV street light fitting on pole including bending the pipe to the required shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts, bolts and washer, painting the flat iron with primer and finish paint etc. as required. |
| 90 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥105 <120 lm/Watt)Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -5 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%, THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66, IK-10, CRI ≥70, under voltage and over voltage protection, EMI-EMC As per CISPR -15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM- 21-11 report, CCT 3000°K/ 4000°K/ 5700°K/ 6500°K (As per ANS Bin), SDCM (Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq. mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 91 | 45 watt |
| 92 | 100 watt |
| 93 | S/Fixing of following size 1.1 KV Grade PVC insulated copper conductor flexible cable in the existing M.S. Tray/Surface/Wall including S/F saddles, screws, thimbles i/c making connections, testing etc. complete as required. |
| 94 | 3 Core 2.5 Sqmm |
| 95 | SITC of following capacity LED BATTEN fitting suitable for 220V, 50Hz a.c supply complete with dismantling the old life expired, irrepairable fitting, making connection etc. complete as reqd. (Make - Panasonic/ Havells /CG/ Philips/Oregenal /Wipro/ Bajaj ) |
| 96 | 4 feet, 20/25 Watt |
| 97 | Brush Less Direct Current (BLDC) Fan without RemoteSupply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply, earthing etc. complete as req. |
| 98 | 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 99 | Providing and fixing of PVC channel/ casing caping of following size on the wall with fixing accessories including cover suitable for drawing of copper wires and protection etc complete as reqd |
| 100 | 25mm x 16mm |
| 101 | 32mmx16mm |
| 102 | 50mm x 16mm |
| 103 | S/F of readymade extension board having 3 Nos. 15A switch, 3/6 pin 15A sockets & Indicator I/c flexible cable (Aprox. 2 Mtrs.) complete with making intercoinnection etc. as reqd. |
| 104 | S/F MS extension board of size 200x150x75mm deep on surface or in recess having 3 nos. 5A switches & sockets and 01 no. 15A Switch & Socket on suitable size phenolic laminated sheet complete with making interconnections, testing, commissioning etc. as reqd. |
| 105 | S/F of readymade extension board having 3 Nos. 5A switch, 3/6 pin 5A sockets I/c flexible cable (Aprox. 2 Mtrs.) complete with making intercoinnection etc. as reqd. |
| 106 | Supplying, fabricating and fixing of MS frame made out of following members i/c cutting, welding, grouting and painting the MS members etc. complete as reqd. |
| 107 | 40mmx40mmx5 mm MS angle iron. |
| 108 | 40mmx5mm MS flat. |
| 109 | S/F of 1.5 Litre Stainless Steel Electric Kettle with Power Indicator, 1500 Watts, Auto Cut-off, detachable 360 Degree Connector, Boiler for Water. Make Milton Euroline Go Electro or SS make. |
| 110 | Rewinding of ceiling fan/exhaust fan including disconnnection & dismantling, replacement of faulty bearings, oiling/greasing, etc.as required. |
| 111 | Rewinding of exhaust fan above 12\\" including disconnnection & dismantling, replacement of faulty bearings, oiling/greasing, etc.as required. |
| 112 | Overhauling and servicing of ceiling fan/exhaust fan including disconnection & dismantling, cleaning, replacing worn out parts like bearing, quarter pin, lock nuts, rubber bush, refixing, etc. complete as required. |
| 113 | Less credit for dismantled electrical material property of contractor @3% of Total \\"A\\" |
| 114 | Note:-1. Electrical complaints are to be attended within 2 Hr. of its reporting otherwise penalty of Rs. 500/- per complaint will be levied. 2. The Agency has to submit police verification record & ID proof of each staff.3. The firm shall provide each staff with working cell phone.4. The staff may be deputed for duty as per instruction of concerned SDE (E)/JTO (E).5. Penalty shall be imposed in case of absence of any staff as per T & C of contract.6. The Estimated Rates are inclusive of GST / other Input Tax Credit (ITC) taxes as applicable & Freight Charges (Unloading & Stacking) etc., the contractor shall quote accordingly.7. The contractor shall provide correct tariff heads & other details to enable BSNL claim Input Tax Credit.8. The bidder who submits the offer with concessional Goods and Service Tax (GST) shall submit the proof of applicable concessional GST. In case the Concessional GST is not creditable to BSNL it should be included in the price of the goods/services.9. The FF & packing amount quoted shall not be subject to change after bid evaluation /ordering on account of change of copper, lead base price, change in duties & taxes of item etc.10. Bidder must mandatorily mention HSN & SAC numbers.11. Evaluation of bids: - The evaluation and comparison of responsive bids shall be done on the basis of Net cost to BSNL on the prices of the goods & Services (i.e. complete work) offered along with all applicable Taxes, packing Forwarding Freight & Insurance charges etc. exclusive of GST.Declaration by Bidder1. We hereby declare that in quoting the above prices, we have taken into account the entire credit on inputs available under the GST Act introduced w.e.f. 1 July 2017 and further extended on more items till date.2. We hereby certify that HSN/SAC shown in column 17 are correct & credit of GST for the amount shown in column 10 above are admissible as per GST Laws.Name of bidder:Seal of Company: GST No./(s) Please Enable Macros to View BoQ information |