| 1 | Excavation in foundation and trenches ( For pipes and pits ) up to all depths in all classification of earth work such as pick work ,jumper work ,saturated soil including bailing or pumping out water ,blasting soft/hard rock or chiseling soft/hard rock where blasting is prohibited in all lifts including trimming & dressing of sides, leveling of beds to correct grade i/c shoring /strutting ,planking ,timbering & dewatering wherever required ,stacking the usable & unusable material /soil separately & after laying ,jointing & testing of pipes ,returning the useable soil in trenches in 15 cm ,layers including consolidating of such deposited layer by ramming & watering & then deposing of all surplus excavated soil / unusable material as directed with in all leads and lifts including restoration of unmetalled surfaces to its original condition and including cost of diversion for traffic , night signals ,fixing caution boards ,crossing over trenches for access to houses ,fencing etc. complete in all respects with in all lead and lifts as per direction & satisfaction of Engineer - in - charge. |
| 2 | Laying, Jointing and testing in trenches Galvanised Mild Steel tube (L) of following dia including tube fitting complete in all respects with in all lead and lifts as per direction & satisfaction of Engineer - in - charge (earth work in trenches is to be measured and paid for separately). |
| 3 | 50mm dia (L) |
| 4 | 32mm dia (L) |
| 5 | Providing and fixing G.I. Union heavy duty ISI Marked of following dia complete fixing at site in all respects with in all lead and lifts as per direction & satisfaction of Engineer - in - charge. |
| 6 | 50mm dia |
| 7 | 32mm dia |
| 8 | Providing and Fixing Gun metal Peat valves heavy duty of following sizes of Sant/Bir/BVI or equavelent make ISI marked complete in all respect with in all leads and lifts as per the direction and satisfaction of the Engineer-in-charge. |
| 9 | 32mm dia |
| 10 | Making connection from main line to branch distribution line i/c cost of G.I Tee,Elbow, GI Union, Nipple, GI pipe Cutting, welding etc.each work to measure and paid sepertely. |
| 11 | 50mm dia |
| 12 | 32mm dia |
| 13 | Supply of submersible pumping set of KSB/Kirloskar/Kilburn/Clama/Crompton/KSB/BS make conforming to BIS; 8034-1976 latest suitable for lifting clear water (latest with uptodate ammendments) fitted with bronze impellers/suitable alloy directly coupled to squirrell case electric induction motor of same make as (manufacurer standard) conforming to BIS; 9283-1979 (latest with uptodate ammendments) and totally water proof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearings & provided with stainless steel thrust bearing plate to with stand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard,errection clamps,cable clips & depth gauge etc. The pump shall be suitable for operation on data given below:-( 7.50 HPx1 Set=7.50 HP |
| 14 | Total Head :- 86.0 Mtrs |
| 15 | Discharge required from each pump. :- 3.50 LPS |
| 16 | No. of pump required :- 1.00 Nos |
| 17 | Location of the site of installation of machinery. :- The site is located at a distance of 5 Kmts from Bharmar Railway Station |
| 18 | The Altitude of installation. :- The altitude of place is 500 mtrs above MSL |
| 19 | Type of current. :- AC Three Phsae Supply witgh |
| 20 | Rate Voltage :- 415+ 10% |
| 21 | Type of water and its source :- Clear Water frome Tube Well |
| 22 | Charactristics of water. :- Clear Water |
| 23 | a)Ambient Temperature dig.c :- 20 dig. C |
| 24 | b)Turbidity NTU :- 113 NTU |
| 25 | c)Hardness260Mg/Ltrs(as CaCO3) :- 540 Mg/Ltr |
| 26 | d) PH 7.5 :- 6.50 to 8.50 |
| 27 | e)total solid Mg /Ltrs :- 610 PPM |
| 28 | f)Other :- |
| 29 | Length of R/Main :- 345.00 Mtr |
| 30 | Dia of Rising main :- 80 mm GI (M) PE |
| 31 | No of working hours per day :- 16.00 Hours |
| 32 | Limit of pump operation. :- (-) 15 % (+) 10% of total head |
| 33 | R.P.M. of pumping set. :- 2900 RPM ( or to be specified by the tenderer) |
| 34 | Test run :- 8 Hours continueously for 7 days |
| 35 | Providing and fixing automatic pannel borad including auto start, auto stop and restart facility single phase preventer , 3 phase indicator ,timer ,relay, selector switch, auto and manually start stop facilty, prevention of of phase reversal imbalance and overload and fixed with compatible starter in sheet enclosure with cabling complete in all respect to deliver results. |
| 36 | Supply of Kirloskar/Kilburn /IVC/Fouress/Gled/BHEL/ Leader make Cast Iron double flanged sluice valve of class PN 1.6 confirming to BIS-780-1984 (to be provided on delivery side) of equal size to one dia more than the dia delivery of pump and capable of with standing nominal seat test pressure of 16 kg/cm². |
| 37 | Supply of Kirloskar/Kilburn/IVC/Fouress /Gled/BHEL/Leader make Cast iron double flanged swing check type reflux valve 80mm dia class PN 1.6 confirming to BS 5312-1984 having bye pass arrangement to be provided on delivery side and shall be suitable for withstanding nominal seat pressure of 16 kg/cm². |
| 38 | Supply of Kirloskar/Kilburn/IVC/Fouress /Gled/BHEL/Leader make Cast iron double flanged swing check type reflux valve 80mm dia class PN 1.6 confirming to BS 5312-1984 having bye pass arrangement equal to dia of Rising main and shall be suitable for withstanding nominal seat pressure of 16 kg/cm². |
| 39 | Providing & laying PVC insulated jointless, flat water proof copper cable of Siemens/Finolex/ Grandlay/ Gloster make conforming to BIS:1554 (Part I) -1988 or latest with up to date ammendments of suitable size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment /accessories such as thimbles, flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or trenches under floor. The type, size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost. |
| 40 | On supply side of 3½ core coper cable 4.00 mm^2 ( From HPSEB Meter to Switch &Starter). |
| 41 | On motor side 3 core flat joint less copper cable of size 2.50 mm^2 ( From Switch & Starter to Motor) pump installed in the bore. |
| 42 | Supply & errection of floor power shunt capacitor conforming to BIS 2834-1986 latest with upto date ammendments of GEC/Siemen/ Havells L&T make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually of requirement KVAR according to BHP of motor offered including cable Siemens/Gloster/ICC make from busbar chamber to capacitor & also including Standard/ L&T/Kilburn/Indo asian make ICTP switches conforming to BIS 4064- 4064-1978 or latest with HRC fuses. |
| 43 | P/Laying Column assembly of G.I./MSERW pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set . The pipe shall conform to relevant BIS codes & capable of with standing the feild test pressure equal to 1.5 times the operating pressure including all type of fittings such as bends, tapers/ reducers, flanges, rubber gaskets 3mmthick, nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer-in-Charge. Column assembly = (Size to be specified by the tender)NOTE:- Actual laying to be done as per final drawings to be approved by the Engineer in charge. |
| 44 | Errection of all equipments including the cost of tees, bends tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge. |
| 45 | Supply of submersible pumping set of (KSB/Kalama/Kirloskar/Johnston/Cromption/BS) make conforming to BIS; 8034-1976 latest suitable for lifting clear water (latest with uptodate ammendments) fitted with bronze impellers/suitable alloy directly coupled to squirrell case electric induction motor of same make as (manufacurer standard) conforming to BIS; 9283-1979 (latest with uptodate ammendments) and totally water proof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearings & provided with stainless steel thrust bearing plate to with stand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard,errection clamps,cable clips & depth gauge etc. The pump shall be suitable for operation on data given below:- |
| 46 | Total Head :- 72.00 mtr |
| 47 | Discharge required from each pump. :- 11.80 LPS |
| 48 | Repair of starter MEI Make including cost of replacement of contact fingers, Thimbles etc complete within all leads and lifts as per entire satisfaction of Engineer in charge. |
| 49 | T/Well Kala Naal 30HP |
| 50 | T/Well Bharmar-1st 20HP |
| 51 | Providing and fixing PVC jointless flat water proof copper cable of finolex/Gloster as per BIS-1554 Part-I-1998 latest with upto date ammendments suitable for the pump sets offered i/c all other electrrical equipment/accessories such as thimbles flexible pipe solder nuts bolts cable, gland etc laid in pipe for trenches under floor. The type & size will be subject to approval of HPSEB authority in case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer without extra cost ) as per the entire satisfaction of the Engineer In charge |
| 52 | T/Well Bharmar-2nd 3 Core Cable 10mm sqare |
| 53 | P/F Nut and Bolt of required size complete within all leads and lifts as per entire satisfaction of Engineer in charge. |
| 54 | P/F Rubber Sheet (Champion Make) of required size complete within all leads and lifts as per entire satisfaction of Engineer in charge. Please Enable Macros to View BoQ information |