| 1 | Supply, Fixing Testing and Commissioning of Medical Grade Copper Pipe used should be half drawn, Tampered seamless phosphorous Deoxidized non-arsenic and degreased confirming to latest BS:EN: 13348, LLOYD Certified, including casing conduct etc. of suitable size & quality for underground and Overhead pipes and all Accessories like bends, tees, reducers etc. (Complete in all respect.) 12 MM (OD)x0.9 MM thick |
| 2 | Supply, Fixing Testing and Commissioning of Medical Grade Copper Pipe used should be half drawn, Tampered seamless phosphorous Deoxidized non-arsenic and degreased confirming to latest BS:EN: 13348, LLOYD Certified, including casing conduct etc. of suitable size & quality for underground and Overhead pipes and all Accessories like bends, tees, reducers etc. (Complete in all respect.) 15 MM (OD)x0.9 MM thick |
| 3 | Supply, Fixing Testing and Commissioning of Medical Grade Copper Pipe used should be half drawn, Tampered seamless phosphorous Deoxidized non-arsenic and degreased confirming to latest BS:EN: 13348, LLOYD Certified, including casing conduct etc. of suitable size & quality for underground and Overhead pipes and all Accessories like bends, tees, reducers etc. (Complete in all respect.) 22 MM (OD)x0.9 MM thick |
| 4 | Supply, fixing testing and commissioning of Terminal Outlets gas specific for the services indicated (viz. O2, Air & Vacuum) and to accept only compatible quick connect Pin/Geometric Index type adapters as per ISO 7396 standard. Manufactured in compliance with CE and ISO 13485. BS type Oxygen outlet with matching probe/Adaptor. |
| 5 | Supply, fixing testing and commissioning of Terminal Outlets gas specific for the services indicated (viz. O2, Air & Vacuum) and to accept only compatible quick connect Pin/Geometric Index type adapters as per ISO 7396 standard. Manufactured in compliance with CE and ISO 13485. BS type Medical Air outlet with matching probe/Adaptor. |
| 6 | Supply, fixing testing and commissioning of Terminal Outlets gas specific for the services indicated (viz. O2, Air & Vacuum) and to accept only compatible quick connect Pin/Geometric Index type adapters as per ISO 7396 standard. Manufactured in compliance with CE and ISO 13485. BS type Vacuum outlet with matching probe/Adaptor. |
| 7 | The Bed Head Panel (size 2.5ft) shall be wall-mounted and fabricated using high-grade extruded aluminum profiles with a powder-coated finish, ensuring corrosion resistance and long-term durability. The panel shall be equipped with five (05) medical gas outlet points conforming strictly to BS Standard, color-coded as per HTM 02-01 / ISO 7396-1 guidelines.Accessories shall include one (01) wall-mounted stainless steel utility basket for suction unit/suction Jar. The complete assembly shall comply with HTM 02-01, ISO 7396-1, and IEC 60601 standards |
| 8 | Supply, fixing, testing and commissioning of Gas lockable AVSU/CONTROL-CLOSING VALVE BOXES with integrated alarm system as required. Microprocessor based module. Digital LED display of \\"Normal\\", \\"High\\" & \\"Low\\". Digital pressure unit display options - psi/ bar or kg/cm2. Audio Mute option. 3 Gases AVSU |
| 9 | The Nurse Call System proposed herein is designed to serve 40 patient beds with a basic patient calling functionality. Each bed shall be equipped with a bed head panel-integrated push-button call unit, allowing patients to alert nursing staff promptly. The Bed Calling Unit is a microcontroller-based device that manages all room modules. It features five soft-touch keys: HELP, CARE, CALL, CODE BLUE, and CLEAR. The CALL key initiates a nurse call, while the CLEAR key is used by attending staff to cancel it. The unit includes CODE BLUE functionality for emergency doctor alerts. It fits into a three-module electrical switch outlet and operates on less than 500 mW at 24VDC. |
| 10 | The Console Unit displays real-time bed numbers using a multi-colour 7-segment display (0.5\\" R, G, B). It features voice alerts for incoming calls, enhancing nurse responsiveness. The unit includes three functional keys: - TEST: Flashes all display windows to verify device functionality. -RESET: Clears all data. - ACK: Acknowledges patient calls, stabilizes the flashing display, and silences the voice module until the call is cleared. It connects to the Nurse Call Hub via a 2-wire connector. The unit is available in table-top or wall-mounted formats, with dimensions of 310 x 40 x 205 mm. It operates on 230V AC power and weighs approximately 3.5 kg. The enclosure is made of powder-coated mild steel with vinyl/PVC labeling. |
| 11 | The HUB Unit is microcontroller-based and interfaces with up to 16 bed modules and the nurse station console. It features a 16x2 green backlit LCD display to show module status and uses terminal strips for easy wiring. It connects to Door Indicators, Bed Calling Units, and Toilet Calling Units via a 4-wire connector. The unit is wall-mounted with vertical orientation and measures 205 x 60 x 255 mm. The enclosure is made of powder-coated mild steel with vinyl/PVC stickers |
| 12 | Cabling & Accessories (Shielded cable, connectors, etc.) |
| 13 | Supply, fixing, testing and commissioning of indigenous 12mm isolation valve. |
| 14 | Supply, fixing, testing and commissioning of indigenous 22mm isolation valve. |
| 15 | Supply, fixing, testing and commissioning of Indigenous BPC Oxygen Flow Meter with Humidifier Bottle. (0-15L/Min) |
| 16 | Supply, fixing, testing and commissioning of indigenous Ward Vacuum unit with Vacuum Collection Jar size 600ml as per BS: EN: IS 10079-3 and CE marked. |
| 17 | Supply, fixing, testing and commissioning of indigenous Ward Vacuum unit with Vacuum Collection Jar size 1000ml as per BS: EN: IS 10079-3 and CE marked. |
| 18 | Supply, Fixing, testing and Commissioning of Indigenous Low-Pressure Tube Please Enable Macros to View BoQ information |