| 1 | Supply, installation, testing & commissioning of 5- Way RMU,11 KV on the existing plinth with rated voltage 12KV, 630A, 21KA-3sec, Outdoor type, extensible type on both sides, Internal arc 21KA for 1 Sec for Tank, floor mounted with internal copper bus bars, SF6 Insulated, completely Motorised, with modems and with SCADA compatible Overload and earth fault protection Relay The unit shall have front cable entry (Suitable for termination of 1R x 3C x 95/120/185 Sq.mm Cable. As per the following switch gears and Technical Specifications enclosed Annexure –I. Make: Siemens, ABB, Schneider Electric, and Eaton, 3rd party inspection :- IRS, LLYODS, RITES, PDIL, EIL, MECON or any other authorized organization as approved by VPA |
| 2 | Supply, installation, testing & commissioning of 3- Way RMU,11 KV on the existing plinth with rated voltage 12KV, 630A, 21KA-3sec, Outdoor type, extensible type on both sides, Internal arc 21KA for 1 Sec for Tank, floor mounted with internal copper bus bars, SF6 Insulated, completely Motorised, with modems and with SCADA compatible Overload and earth fault protection Relay The unit shall have front cable entry (Suitable for termination of 1R x 3C x 95/120/185 Sq.mm Cable. As per the following switch gears and Technical Specifications enclosed Annexure-I. Make: Siemens, ABB, Schneider Electric, and Eaton, 3rd party inspection :- IRS, LLYODS, RITES, PDIL, EIL, MECON or any other authorized organization as approved by VPA 3rd party inspection :- IRS, LLYODS, RITES, PDIL, EIL, MECON or any other authorized organization as approved by VPA |
| 3 | Supply of 3C x 95 Sq. mm XLPE insulated IS: 7098 / II / 85 H.T. cable for working voltage 11 K.V Earthed with Stranded Compacted Circular Aluminium Conductor Screened with Extruded Semi-conducting compound, XLPE Insulated in combination with Copper Tape, cores laid up, inner sheath of Thermoplastic tape, galvanised flat steel strip armoured and overall Extruded PVC Type ST- 2 Outer Sheathed cable etc. complete with all material, tools and tackles as directed by Engineer-In-Charge as per Annexure II Make: KEI / Polycab / Gloster / RR Kabel / RPG / Finolex / Havells |
| 4 | Supply and transportation of 1.1 KV grade following LT Cable XLPE insulated, armoured aluminium cable, PVC overall sheathed multi stranded aluminium conductor Cable conforming to IS 7098 / Part-I /1554-1 complete with all material, tools and tackles as directed by Engineer-In-Charge.Brands: Finolex / Gloster / RPG / Havells / Polycab / KEI / RR Kable / 3.5 C X 120 Sq.mm |
| 5 | 3.5 C X 50 sq.mm. |
| 6 | 3.5 C X 25 sq.mm |
| 7 | Laying / clamping / drawing of the HT / LT cables in existing trench / to wall / pole / through existing HDPE pipe including and brick protection with all materials tools and tackles as directed by Engineer –in-charge. Note: Cable will be supplied by VPA at free of cost. |
| 8 | Excavation of trenches in Hard / dense soil of required width for laying of HDPE / GI pipes, cables and retrieving the existing cables etc., including dressing of sides, ramming of bottoms, measurement 1.5m depthx0.5m width required length (as per sight requirement) including getting out the excavated soil and the returning the soil including consolidating each deposit layer by ramming, watering etc., and disposing of surplus excavated soil as directed by engineer in charge and complete all labour and material. |
| 9 | Supply, laying / Clamping of 110 mm diameter PE-100 grade HDPE pipe to the pole with existing clamps / in existing trench as directed by Engineer-in-Charge complete with all labour tools, tackles and materials.MAKES: KSP/ SUDHAKAR / NANDI. |
| 10 | Supply and providing of CI earth station using 80mm diameter flanged CI pipe of length 2.5 Mtrs duly perforated and with suitable PCC covering as per IS 3043 in a pit of suitable depth filled with alternate layers of salt and charcoal as directed by engineering in-charge including all labour and material. |
| 11 | Supplying, fixing, connecting and commissioning of 50 x 6 mm GI earth strip in recess/surface/clamped through PCC etc., from earth to switch gear/equipment including connecting the same at both ends as directed by engineer in charge including all labour and material. |
| 12 | Supply and providing of Heat shrinkable Indoor End termination kit suitable to 3 Core 95 Sq.mm 11KV grade armoured Aluminium conductor cable as directed by Engr. I/c complete with all materials labour tools and tackles. Brand: Raychem /M-Seal/3 M |
| 13 | Supply and providing of Heat shrinkable Outdoor End termination kit suitable to 3 Core 95 Sq.mm 11KV grade armoured Aluminium conductor cable as directed by Engr. I/c complete with all materials labour tools and tackles.Brand: Reychem/M-Seal/3 M |
| 14 | Supply and providing of Heat shrinkable Straight through joint kit suitable to 3 Core 95 Sq.mm 11KV grade armoured Aluminium conductor cable as directed by Engr. I/c complete with all materials labour tools and tackles.Brand: Reychem/M-Seal/3 M |
| 15 | Foundation and erection charges with special T&P, for RMU’s duly providing foundation bolts with nuts with M20 CC work vibrated concreting mixing with necessary steel reinforcement, including excavation of earth complete with all materials labour tools and tackles as directed by Engr.I/c. |
| 16 | Providing and fixing G.I tubular gate (double shutters) with 40 mm dia, G.I. pipe including diagonal pipes and frame welded to approved chain linked mesh of 75 x 25 mm size (3.15 mm x 5 mm dia) including painting with one priming coat and two coats of synthetic enamel paint of approved colour and shade (total three coats) etc., with locking arrangement, necessary MS flats, iron pintels etc., including fixing in CC bed block as directed with 12 mm dia, bolts and nuts, washers etc., as required complete with all material, tools tackles as directed by Engineer- in- charge. |
| 17 | Supplying and fixing galvanized steel chain linked mesh of 50 mm x 50 mm openings and 10 gauge as per IS 2721-2003 including bending, tying with G.I. wire / welding etc., as directed by the EIC complete with all material, tools tackles as directed by Engineer- in- charge. |
| 18 | Providing random rubble masonry with C.M 1:5 in plinth and foundations including necessary dressed stones at corners and junctions, curing etc., complete. All labour and materials. |
| 19 | Removing & Relaying of PCC bricks from the road with damage to the bricks directed by Engineer-in-charge including all labour and tools. |
| 20 | Supply and providing of R.C.C. M30 mix graded granite as coarse aggregate and river sand as fine aggregate including mixing, depositing in position, tamping, finishing and curing for making of plinth etc. as directed by Engineer-in-charge including all labour and tools. |
| 21 | Plastering with CM 1:6, 12mm thick including racking out joints cleaning the surface curing etc. as directed by Engineer- in- charge with all labour and material. |
| 22 | Supply and providing of P.C.C. 1:3:6 with 20 mm graded granite as coarse aggregate and river sand as fine aggregate including mixing, depositing in position, tamping, finishing and curing for base concreting, road cutting, coping etc. as directed by Engineer-in-charge including all labour and tools. |
| 23 | Supply and fabrication of steel by using suitable flats, angles, channels of required sizes to provide the RMUs, AB Switch erection & VCB breaker, for clamping of cable including cutting, bolting, riveting, drilling, welding etc. including providing one coat of zinc rich epoxy paint primer complete as directed by engineer in charge. |
| 24 | Dismantling of existing 4 pole / 6 pole structure duly removing of pin / disc insulators, busbar jumpers, channels. Cross bracings etc., and to handover to E/M or General stores including loading, unloading and transportation as directed by Engr. I/c |
| 25 | Removal of existing B.G. rail pole / Tubular pole / spun pole duly breaking the coping and base PCC, excavating the earth upto 0.5mts depth from the ground level cutting the pole refilling the excavated earth and making the surface good to match the surroundings, returning the removed pole to E/M section stores /general stores as directed by Engineer in charge including all labour and material |
| 26 | Supply, fixing connecting and commissioning of LT panel, 3 phase and neutral, floor mounted, Outdoor type, thickness of 3 mm with hinged door of following switch gears of approved brands with necessary 600 amps aluminium bus bar arrangement with IP55 Protection including with 2 coats of approved shade of enamel paint over one coat of red-oxide, thickness of 14 SWG connecting the incoming and outgoing cables duly provided lugs and glands including proper termination as directed by engineer in charge including all labour material tools and tackles. Incomer: 4 pole, 415 V, 400 A , 36/35 KA breaking capacity MCCB - 1no ; Out goings: 4 pole,415 V, 250A, 36/35 KA breaking capacity MCCB - 2 nos; Out goings:4 pole,415 V,100A, 16 KA breaking capacity MCCB - 3 nos Elmeasure Digital multiplication meter, model No: LG 6400 – 01 No LED Indications – 3Nos (colours :R,Y, B).MCCB Brand: ABB/ Schneider/ L&K/ Siemens. Specification as per annexure -IV |
| 27 | Dismantling, Removing of the existing 20/25/30 mtrs High Mast from existing RCC foundation with all accessories and duly removing of Lantern carriage & Head frame assembly with all accessories on the mast including wire ropes, cables, luminaries, control gear boxes etc., without damage to the material and providing a crane assistance, including transportation loading and un-loading labour tools and tackles as directed by engineer in-charge. |
| 28 | Transportation, erection & commissioning of the 20/25/30 mtrs High Mast on existing RCC foundation with all accessories and duly assembly, fixing and commissioning of Lantern carriage & Head frame assembly with all accessories on the mast including wire ropes, cables, luminaries, control gear boxes etc., and providing crane assistance, including transportation loading and un-loading labour tools and tackles, as directed by engineer in-charge. Note: High Mast & Luminaries will be supplied by VPA at free of cost. |
| 29 | Providing of suitable shallow foundation as per the drawing with 1:2:4 concrete for 20 mtrs high mast with all material and labour including excavation as directed by engineer in-charge. |
| 30 | Supply of set of foundation stainless steel bolts for 20/25/30 mtrs High Mast lighting tower shallow foundation. |
| 31 | Supply, Transportation, Installation, Testing and Commissioning of 250KVA outdoor 11/0.433 KV Transformer with all test reports. The Transformer shall be designed and manufactured as per Energy Efficiency Level - 2 at basic Insulation level conforming to ISS 2026 (Part- I to Part - II) with latest ammended and as per IS 1180 Part-I : 2014 latest ammended, OCTC with initial filling of oil as per IS 335-1993. The Technical Specifications details of the Transformer enclosed Annexure–V Makes: Voltamp (Voltamp Transformers Ltd., Vadodara) / Schneider / ABB / Siemens / Kirloskar / BHEL. 3rd party inspection :- IRS, LLYODS, RITES, PDIL, EIL, MECON or any other authorized organization as approved by VPA |
| 32 | Supply of 4 core x 2.5 sq.mm, PVC insulated and sheathed FRLS/FRLS-H round copper cable for voltage up to 1.1KV as per IS 694 / 1990. Make: Havells / KEI/ Polycab / Gloster / KSP/ RR Kabel/ RPG / GEMSCAB. |
| 33 | Transportation and laying/ drawing of 4 core x 2.5 sq.mm multi stranded copper cable through the existing PVC pipe including connecting to switch gear with suitable lugs and junction box as directed by Engineer in-charge complete with all materials, labour, tools and tackles. |
| 34 | Supply and fixing of PCC cable root Indicators of size 152mm round / 102mm x 102mm / 152mm x 152mm as directed by engineer in charge including all labour and material. |
| 35 | Removing of HT/LT overhead conductor from the poles including with jumpers, insulators, etc., and the material handover to E/M Stores / General stores as directed by Engr. I/c complete with all labour tools and tackles. |
| 36 | Supply & Fixing of Thermo Plastic cable Junction boxes with IP 66 / 67 weather proof, for outdoor installation on the pre-fabricated angular frame duly fitted with 1 No two pole 10 Amps MCB including provision for cable entry and terminal etc., size : 130 X 130 X 77 complete as directed by the engineering in-charge.Make: HENSEL / Sadhrish / Net tune. |
| 37 | Supply, Installation, Testing and Commissioning of IOT based 40KVA (or higher capacity) smart GSM based group controlling existing street lighting ;circuits including integration with cloud based CMS software, communication setup, testing for enabling user to monitoring of all electrical parameters over three phase power system with fault alerts based on defined parameters for over voltage, under voltage, low voltage, High voltage, power off, 4 system fault etc., Technical specification enclosed Annexure – VI. |
| 38 | Supply, laying / Clamping of 78 mm outer dia and 63 mm Inner dia double walled corrugated HDPE duct made as per specification BSEN-500 86/IS 14930 Par-II to the pole with existing clamps / in existing trench as directed by Engineer-in-Charge complete with all labour tools, tackles and materials. MAKES: KSP/ SUDHAKAR / NANDI Please Enable Macros to View BoQ information |