| 1 | Wiring point for light in 1.5 sq mm FRLSH PVC insulated multi strand single core copper conductor cable (drawn through existing concealed steel conduit) 5 Amp. modular type switch and ceiling rose / angle/ batten holder on 3 mm thick Phenolic laminated sheet mounted over existing M.S switch board box/ junction box with supply of all material, labour & T&P etc required for proper completion of the work as directed at site by the Engineer in charge. with modular switch and /ceiling rose /angle holder /batten holder complete in all respects as directed including matching colour wash. |
| 2 | Wiring point for ceiling fan in 1.5 sq mm FRLSH PVC insulated multi strand single core copper conductor cable (drawn through existing concealed steel conduit) 5 Amp. modular type switch and ceiling rose on 3 mm thick Phenolic laminated sheet mounted over existing M.S switch board box/ junction box with supply of all material, labour & T&P etc required for proper completion of the work as directed at site by the Engineer in charge. with modular switch and /ceiling rose /angle holder /batten holder complete in all respects as directed including matching colour wash. |
| 3 | Wiring point for plug in 1.5 sq mm FRLSH PVC insulated multi strand single core copper conductor cable (drawn through existing concealed steel conduit) 5 Amp. modular type switch and 3 pin socket on 3 mm thick Phenolic laminated sheet mounted over existing M.S switch board box/ junction box with supply of all material, labour & T&P etc required for proper completion of the work as directed at site by the Engineer in charge. with modular switch and /ceiling rose /angle holder /batten holder complete in all respects as directed including matching colour wash. |
| 4 | S/F of surface/flush mounting 12 way SPN distribution board with additional metal door without MCB complete in all respect and as directed at site Cat B |
| 5 | S/F of surface/flush mounting 8 way SPN distribution board with additional metal door without MCB complete in all respect and as directed at site Cat B |
| 6 | Supply/fixing of 5-32 Amp. MCB 9 KA. C-Curve Cat- A |
| 7 | Supply and burring of Safe Earthing Electrode T-19 (Hot Dip Galvanized), Length up to 2000mm, outer pipe 50mm, inner pipe 25, terminal Dia 12 mm, outer GI pipe of 16 swg and inner GI pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame with hinged cover & masonry husing (from electrode terminal to switch board, cost of 25 x 3 G.I . strip will be extra) Make: As approved in U.P. P.W.D., & C.P.R.I. Certified. |
| 8 | S/F of one number 8 to 6 SWG G.I. Wire in 15mm dia. G.I. Pipe for earthing, laid in ground or in wall duly concealed including the cost of cement, sand labour. T and P other material required for proper completion of the work as directed at site. |
| 9 | Supply and fixing of power plug with 20A/240 V flush type modular switch and 5 pin 20 A/250 V flush type universal modular socket on concealed M.S. box including supply of all materials labour T&C etc. required for proper complete in all respects. |
| 10 | S/F of electronic fan regulator Modular 120-280 V ISI Marked on the existing switch board including making connection , required materials, labour T/P for proper completion of work to the satisfaction of engineer in charge of work. |
| 11 | Supply and wiring of submain with two number 4 sq. mm & 01 no. earth wire of 2.5 sq mm FRLSH PVC insulated 1100 V multi strand single core copper conductor cable inexisting PVC conduit including supply of all materials labour. & T&P etc required for proper completion of workas directed by E/I |
| 12 | Supply and wiring of submain with two number 6 sq. mm & 01 no. earth wire of 4 sq mm FRLSH PVC insulated 1100 V multi strand single core copper conductor cable inexisting PVC conduit including supply of all materials labour. & T&P etc required for proper completion of workas directed by E/I |
| 13 | Supply and wiring of submain with two number 10 sq. mm & 01 no. earth wire of 6 sq mm FRLSH PVC insulated 1100 V multi strand single core copper conductor cable inexisting PVC conduit including supply of all materials labour. & T&P etc required for proper completion of workas directed by E/I |
| 14 | Supply and fixing of LED Tube Light with batten suitable for up to 1 X 22 watt LED tube light fitting including tube on Surface complete in all respect. CAT- AAA |
| 15 | S/F of following 4 Module size (125 mm x 75mm ) module GI box alongwith Modular base and cover Plate for Modular switches in resess etc. |
| 16 | S/F of following 6 Module size (200 mm x 75mm ) module GI box alongwith Modular base and cover Plate for Modular switches in resess etc. |
| 17 | S/F of following 12 Module size (200 mm x 150 mm ) module GI box alongwith Modular base and cover Plate for Modular switches in resess etc. |
| 18 | S/F of 20 mm dia PVC condute pipe |
| 19 | Supply and fixing of Exhaust Fen |
| 20 | S/F of water tight oblong 10 watt LED bulk head lumnaries having pressure die cast housing with driver set confirming to IP 65 and above protection JK 08 Complete in all respects |
| 21 | S/F of sheet encloure surface/flush mounting with 20 Amp. 2 pin and earth metal clad scaping earth plug and socket complete in all respect and as directed at site Cat A |
| 22 | Supply & fixing of LED street light fitting with mandatory driver set having die cast Aluminium body and lenses suitable for 110Watt to 130 Watt and diffuser/ reflecto with driver set suitable for 110 to 130 watt. Confiming to IP 66 Protection having company LOGO Engraved complete in all respects. including Labour. 12100-14300 system lumens High Power with lenses,>110lm/W,PP>0.95,THD<10%,at full load,CR1>70, Potted driver set Not Circuitory Phase to phase protection at 440V and >300V auto cut and restart feature with 5 year warrantee. Cat-AAA Please Enable Macros to View BoQ information |