| 1 | Excavation in trenches n.exc 1.5 mtrs wide and not exv 1.5 M deep in soft/loose soil and getting out all as specified and directed. |
| 2 | Returning, filling in incl spreading, levelling and well ramming in layers not exc 25 cm in soft / loose soil all as specified and directed. |
| 3 | Removing excavated soil to a distance not exc 50M and depositing where directed at level not exc 1.5 m above starting point complete all as specified and directed. |
| 4 | M&L for bituminous road cutting / Footpath to a width of 60cm and depth 90cm for laying of LT cable and making good with PCC (1:3:6) type B1(using 20mm grade stone aggregate) complete all as specified and directed. |
| 5 | Taking down Old U/S LT cable of size 25 sqmm to 185 sqmm all as specified and directed by Engr-In-Charge. |
| 6 | Supply, laying, testing and commissioning of LT XLPE insulated, sheathed, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of size 3.5 core x 300 sq.mm. (laid in trenches, ducts, pole, wall etc.) complete all as specified and as as directed by engineer in charge.Note: (i) Necessary test results like continuity test, megger tests, shall be submitted to Engineer-in-Charge before the cable is laid. (ii) Excavation earth work will be measured and paid separately. |
| 7 | Supply, laying, testing and commissioning of LT XLPE insulated, sheathed, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of size 3.5 core x 240 sq.mm. (laid in trenches, ducts, pole, wall etc.) complete all as specified and as as directed by engineer in charge. |
| 8 | Supply, laying, testing and commissioning of LT XLPE insulated, sheathed, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of size 3.5 core x 185 sq.mm. (laid in trenches, ducts, pole, wall etc.) complete all as specified and as as directed by engineer in charge including taking down old cable complete all as specified and as directed. |
| 9 | Supply, laying, testing and commissioning of LT XLPE insulated, sheathed, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of size 3.5 core x 150 sq.mm. (laid in trenches, ducts, pole, wall etc.) complete all as specified and as as directed by engineer in charge including taking down old cable complete all as specified and as directed. |
| 10 | Supply, laying, testing and commissioning of LT XLPE insulated, sheathed, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of size 3.5 core x 120 sq.mm. (laid in trenches, ducts, pole, wall etc.) complete all as specified and as as directed by engineer in charge including taking down old cable complete all as specified and as directed. |
| 11 | Supply, laying, testing and commissioning of LT XLPE insulated, sheathed, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of size 3.5 core x 95 sq.mm. (laid in trenches, ducts, pole, wall etc.) complete all as specified and as as directed by engineer in charge including taking down old cable complete all as specified and as directed. |
| 12 | Supply, laying, testing and commissioning of LT XLPE insulated, sheathed, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of size 3.5 core x 70 sq.mm. (laid in trenches, ducts, pole, wall etc.) complete all as specified and as as directed by engineer in charge including taking down old cable complete all as specified and as directed. |
| 13 | Supply, laying, testing and commissioning of LT XLPE insulated, sheathed, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of size 3.5 core x 50 sq.mm. (laid in trenches, ducts, pole, wall etc.) complete all as specified and as as directed by engineer in charge including taking down old cable complete all as specified and as directed. |
| 14 | Supply, laying, testing and commissioning of LT XLPE insulated, sheathed, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of size 3.5 core x 35 sq.mm. (laid in trenches, ducts, pole, wall etc.) complete all as specified and as as directed by engineer in charge including taking down old cable complete all as specified and as directed. |
| 15 | Supply, laying, testing and commissioning of LT XLPE insulated, sheathed, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of size 3.5 core x 25 sq.mm. (laid in trenches, ducts, pole, wall etc.) complete all as specified and as as directed by engineer in charge including taking down old cable complete all as specified and as directed. |
| 16 | Supply & Laying GI Pipe 100 mm medium grade in the trench crossings/obstructions for cable protection, including cutting of existing road and making good the disturbed surfaces complete all as specified and as directed. |
| 17 | M&L for earthing complete with galvanized steel plate earth electrode 60cmx60cmx6mm thick surrounded by char coal and salt buried directly in ground vertically in pit of depth not less then 2.25 mtr below ground level with top edge of the earth plate at depth of not less then 1.5 mtr below ground level surrounded from all sides by char coal dust and common salt in alternate layers of 15 cm depth and earth plate electrode connected to galvanised earth lead strip of size 32X6 mm by means of GI nuts bolts, check nuts and washers and connected to earthling test point drawn through 40 mm dia GI pipe for protection of GI pipe including 20mm dia GI pipe for watering GI funnel , PCC earth pit (1:3:6) type C-2 with CI frame and RCC cover all as shown in electrical Plate No 3 on SSR Part-I including testing all as directed by Engr-In-Charge.NOTES: 1) The unit rate shall also include for earth work in any type of soil, PCC (1:3:6) type C1 chamber, pre-cast RCC (1:2:4) type B-1 using 20mm graded stone aggregate cover 50mm thick reinforced with TMT bars 8mm dia @ 100mm c/c both ways, funnel with watering pipe 20mm dia medium grade, GI protection pipe light grade 40mm dia and wire mesh complete in addition to item No. 1(a) to (e) of preamble (notes) under sub-heading earthing, specified on Sl. Page Nos. 422 & 423 of SSR Part-II. 2) Earthing lead and GI protection pipe beyond 7.5m will be measured and paid separately. |
| 18 | M&L earth continuity conductor or main earthing lead of size 32x6mm galvanised iron strip fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to ples or any other indicated situation for loop earthing etc complete all as specified and as directed. |
| 19 | Supply and Fixing of outdoor LT Panel / LT Pillar Box of minimum dimensions 1.8m x 1.4m x 0.6m size with following specifications.Fabrication Details :CPRI approved Main frame 3.15mm thick CRCA sheet, partition sheets / covers / doors of 2 mm thick CRCA sheet, gland plates 2 mm thick MS sheet (undrilled), base frame on ICMS channel with provision of incoming and outgoing cable entry at the bottom for outdoor installation, free standing floor mounted with degree of protection IP- 65 and locking arrangements.Bus bar details :Material shall be alluminum bus bar, sleeving heat shrinkable type, with bus bar sizes for phase 50mmx20mm aluminium Flat, neutral 50x10mm aluminium flat and bus bar support of epoxy type.Painting Detais :Pillar box shall be powder coated and painted with two coats of synthetic enamel spray paint over a coat of redoxide primer. Please Enable Macros to View BoQ information |
| 20 | Supply and Fixing of outdoor LT Panel / LT Pillar Box of minimum dimensions 1.8m x 1.4m x 0.6m size with following specifications.Fabrication Details :CPRI approved Main frame 3.15mm thick CRCA sheet, partition sheets / covers / doors of 2 mm thick CRCA sheet, gland plates 2 mm thick MS sheet (undrilled), base frame on ICMS channel with provision of incoming and outgoing cable entry at the bottom for outdoor installation, free standing floor mounted with degree of protection IP- 65 and locking arrangements.Bus bar details :Material shall be alluminum bus bar, sleeving heat shrinkable type, with bus bar sizes for phase 50mmx20mm aluminium Flat, neutral 50x10mm aluminium flat and bus bar support of epoxy type.Painting Detais :Pillar box shall be powder coated and painted with two coats of synthetic enamel spray paint over a coat of redoxide primer. Please Enable Macros to View BoQ information |