| 1 | PART-A WORK |
| 2 | Construction of 01 Nos. 33 KV Mundera bay, Gorakhpur at 132 KV Sub-station Shatrughanpur which shall be done with details of works mentioned as below :- |
| 3 | Erection of structure parts the job consist of shorting, counting, shifting of all materials structure parts, nuts and bolt etc from store to erection site, proper erection of structure as per drawing and all other associated works. |
| 4 | 36 KV Single phase CT (400/200/1-1A) |
| 5 | 36 KV CT (400/200/1-1A) Junction box |
| 6 | 36 KV Line isolator including fixing of its operating Boxes & Mechanism coupling link pipe etc. |
| 7 | 36 KV Bus isolator including fixing of its operating Box & Mechanism coupling link pipes etc. |
| 8 | Erection & commissioning of 36 KV VCB with structure |
| 9 | Erection of New 33KV Tripple feeder control and relay panel in control room at s/s including grouuting,earthing & termination of control cable, as per cable schdules including providing & fixing cable glands of appropriate sizes and ferrules etc. all other associated works as per technical specification. |
| 10 | Laying of control cable from control panel/Relay Panel to breaker /CT/PT already erected through cable trenches including removal of trench cover, dressing as per cable schedule including clamping at a distance 2 mtr. with 25x3 mm. Aluminium Strip (To be provided by Contractor). |
| 11 | i) 2x2.5 mm2 |
| 12 | ii) 4x2.5 mm2 |
| 13 | iii) 6x2.5 mm2 |
| 14 | laying &stringing of 33kV Main bus bar of moose conductor having length 6 meter (01 No. of each phase) |
| 15 | cutting & making holes in various equipment's base plates & fixing of accurate size cable glands (To be provided by Contractor) binding the numbering tags on both side of cable, making termination including all internal connection at each equipment Iike CB,CT,CT Junction box,control panel etc.on both ends with correct ferruling for each core of cables alongwith preparation of interconnection Drawing and commissioning of the panel in co-ordination with T&C wing including providing 02 sets of Hard copies. This also include resetting of trench cover on trenches after completion of work. (ferrules & Cable glands to be provided by Contractor) |
| 16 | Safe carriage of various items like as Galvanized sub-station structure parts ,33KV C.B. , 33KV CT, 33KV PI, 33KV Isolater and Earthing rod 40 mm etc. from various S/S under ETC Gorakhpur to 132KV S/S Shatrughanpur,distance around 50KM (Approx) using private truck including loading at various substation and unloading at 132KV S/S Shatrughanpur using hydra with required manpower,T&P in scope of contractor. |
| 17 | Earthing of Equipments |
| 18 | Laying of 32/40 mm MS round bar 700 mm below ground level including cutting, welding, painting excavation of trench and its back filling of Trench after laying oF Earth Mat including shifting of MS round Bar from storage Place at the Sub-Station to Switchyard. |
| 19 | Fabrication of 3 meter long electrode with MS rod having 150 mm conical shape by due cutting,straightening etc.and then its piercing vertically its side the ground with top 700 mm below ground level and its welding with earth mat including shifting MS Round bar from storage place at the Sub Station to switchyard. |
| 20 | Cutting, stringing, bending, laying of following size MS flat for earthing of main and auxiliary structure, equipment structure, T/F body including fans/DM/M.Box, CT, PT, CB, LSI/BSI equipment etc including welding with main earthmat 700 mm below ground level with object to each excavation of trenches its back filling. painting with synthetic enemal green color above ground and all associated work to complete the job satisfactorily excluding cost of MS flat. |
| 21 | 50x6 mm |
| 22 | 25x6 mm |
| 23 | Painting of M.S.Earthing strips by rubbing with sand paper and wire brush then painting with one coat of red oxide primer & 2 coats (The 2nd coat of paint shall be applied at the gap of 48 hrs when Ist coat of paint is done and checked by concerned S.D.O./J.E.) Ist quality synthetic enamel paint of asian make in Bus green /Black colour as per details below: |
| 24 | 50x6 mm |
| 25 | 25x6 mm |
| 26 | Complete jumpering and interconnection work of different equipments from 33KV Main Bus i.e. BI, CB, CT, PT, LI etc. by Twin ACSR Panther conductor including cutting, tilting & tightening with PG Clamps/terminal clamps at both ends as per technical standard and direction of supervising engineer. |
| 27 | Switchyard Lighting |
| 28 | Supply and fixing of new generation energy saving environment friendly long life versatile pressure die casting aluminium outdoor high beam flood light with high power of LED street light luminaries 120 watt of Havells/CGL/any standard make.Transportation up to site and any other job requested to properly execute the complete work. |
| 29 | Providing & fixing of G.I. Pole Bracket of 40 mm dia. 'B' Class 1.20 Meter long M.S. Pipe of (ID 35 mm & OD 40 mm) bent at angle of 300 for fixing of 125 / 110 Watt LED Lamp Fittings with the help of M.S. Bracket Clamps of suitable size for fixing on G.I. Column Structure at designated place. |
| 30 | Providing & Installation of junction box on gantry structure of size 200×200×150 mm made of MS sheet of 16 gauge with Hinged Door, Painted with Smoke Grey Colour Synthetic Enamel Paint on all sides and Fitted with 1 No.6 Amp. ,1 no. Terminal Bock & 16amp fuse fixed on mica sheet and back side ms clamp alongwith pvc pipe fixing on junction box half round GI Pipe OD 50mm for mounting the 120watt LED light upon gantry mounting of 02 no.bracket upon gantry and fixing of GI pipe complete with nut & bolts and washers. |
| 31 | Supply and fixing of 415Volt AC lightining DB with canopy for outdoor installation rating 415Volt,200Amp.3-phase of size 750X500X300 mm with MS sheet thickness 14SWG duly powderc coated of good quality.The receptacle shall be double door (1 front & 1 inside door for operating the MCB withaout opening door) and single door opposite site shall be provided inclunding 04 No. allumimium insulated bus bar size 25*6 mm for incoming,04 pole MCB of rating 32Amp.06No. double pole MCB rating 16/32 amp.,12No.MCB,100Amp. MCB isolater-01No. of Havells/any standrad make ,01 no. ampmeter,01 no.voltmeter having selector switch & 3 phase indication lamp with proper connections. |
| 32 | Laying of 2C/4C*2.5sq mm size control cable from LT ACDB cubical to various junction boxes for Switchyard Lighting through excavated trench of suitable size covering the cables with river sand and brick lining along and over the cable, then back filling & levelling of the trench cover after laying of cables. |
| 33 | Laying of above control cable from LT Lighting junction box to LED street light fitting by clamping with suitable M.S. strip clamp with proper dressing. |
| 34 | PART-B SUPPLY |
| 35 | 40MM Electrod 3 meter long |
| 36 | 40 MM Earthing Mat |
| 37 | 50*6 mm MS Flat |
| 38 | 25*6 mm MS Flat |
| 39 | GI perforted cable tray (75 mm) |
| 40 | 33kV CT Clamp for Twin Panther |
| 41 | 33kV Isolater clamp for Twin Panther |
| 42 | 33kV C.B. clamp for Twin Panther |
| 43 | 36kV Bus Post Insulater for terminal support |
| 44 | 36kV Bus Post Clamp |
| 45 | PG Clamp Moose to Moose |
| 46 | PG Clamp Moose to Panther |
| 47 | PG Clamp Panther to Panther Please Enable Macros to View BoQ information |